EC500 Controller Handbook
Copyright © 2019 Eaton Corporation. All Rights Reserved.
Issue A March 2019
Page 25 of 107
➢
To use multiple battery banks
•
Install one current monitoring channel for each Battery string
•
Set
Number of Batt. Fuse
equal to number of battery banks. System supports maximum 5
banks in this mode.
•
Set
Number of Batt. LVD
as per selection of configuration. It can be one LVD for all Battery
banks or individual LVD for individual Battery bank.
Configuration
–
1
Configuration
–
2
Monitoring
The following information is available about Multiple Battery Banks:
Parameter
Description
Where to find:
Battery
n
Voltage
Battery terminal voltage. Number of batteries is
equal to number of battery fuses configured.
Display
:
Menu>System
Status>Battery
Web:
Battery n Current
Individual Battery current. Number of battery
currents displayed is equal to number of battery
LVDs configured.