EC500 Controller Handbook
Copyright © 2019 Eaton Corporation. All Rights Reserved.
Issue A March 2019
Page 93 of 107
Home Screen:
System Block Diagram with key system values, latest alarm,
Status and RTC date and time.
Entry
Input:
Joystick
(Up / Down / Left / Right / Enter)
Access Security:
Read Only,
Write Access with PIN Protection
User interface functions:
View system values
View and change alarms
View status messages
Start / Stop control functions
Change operating settings
Audio & LED Indicators
Power On:
Green
Critical / Major Alarm:
Red
Minor Alarm:
Yellow
Audible Alarm Indicator:
Enabled/Disabled (default: Enabled)
Language
Language (standard):
English
Language options:
One additional language supported, available to special request
POWER, MECHANICAL & ENVIRONMENTAL
Power Input
Rated Voltage
-48V DC, nominal
Operational Range:
-36V to -60V DC
Power input connector:
RJ-45 (part of CAN bus)
Input current:
0.1A (48V)
Mechanical
Dimensions H, W, D:
43mm, 112mm, 130mm. Horizontal Mounting
Weight:
TBD
Mounting options:
Slot mount with Lock
Orientation:
Horizontal, Vertical (EC500 V2)
Environmental Specifications
Rated Operating Temp. Range:
-10°C to +50°C (14°F to 122°F)
Extended Operating Temp. Range:
-20°C to +60°C ( -4°F to 140°F)
May affect product lifetime, metering accuracy and display
contrast.
Altitude:
<3000m (9800 feet)
Humidity:
<95%RH (Non-condensing)
Location:
This unit must be installed in a restricted access location.