EC500 Controller Handbook
Copyright © 2019 Eaton Corporation. All Rights Reserved.
Issue A March 2019
Page 67 of 107
SYSTEM CONFIGURATION
OVERVIEW
The EC500 Controller supports a number of functions which are dependent upon availability of specific
hardware in the system. Some critical parameters are also controlled under this section. EC500 configuration
should be set accordingly before commissioning. Most of these configuration settings are not available on
display or Web pages, as these are related to system hardware and should not be changed at run time.
To generate a suitable configuration use the Configuration Tool
“Configurator”
. This tool generates a
configuration file which can be downloaded to the controller.
For specific requirements, this configuration file can be preloaded in the factory for quick installation &
commissioning.
The next sections describe the important System Configuration parameters.
SYSTEM INFO
The following settings relate to system hardware. These are required for correct operation of the display
screen, web pages, communication and functionalities.
Since system hardware does not change in the field, these settings are not normally editable from Web, SNMP
or Display.
Change of these settings may require a restart of controller.
Parameter
Description
Default Value
Where to find:
Rectifier Type
Select the rectifier type which will be
used in the system. This will result in
proper communication with rectifier,
rectifier parameters and alarm
reporting. Currently supported
rectifiers are:
•
HPR48-ES (3kW)
•
LPR48-ES (1.1kW)
Refer section Rectifiers on page 34 for
more details.
HPR48-ES
Configurator:
Main Menu>System
Config>System Info
Web:
Home>System Config>
System Info
System Type
Select whether it is a Single Phase (
1P-
N
), Three Phase (
3P-N
) or Phase
–
Phase (
3P-P
) system. Refer section
Rectifiers on page 34 for more details.
DC Interface
Type
The EC500 supports following options
depending upon hardware
requirements:
•
DCIF 4V2C Shunt Sensor
•
DCIF 6V7C Shunt Sensor
•
DCIO 6V3C Shunt Sensor
Refer section DC Interface Boards on
page 8 for more details.
DCIF 6V3C Shunt
Sensor
DCIF
n
Install
status
The EC500 supports up to four DCIF
boards. Depending upon the number of
DCIF 1: Installed
DCIF 2:
Not Installed