background image

22

Instruction Leaflet 

I. L. 29-888B

Effective July 2011

 Instructions for Digitrip RMS 810 Trip Unit

 

 

eaton corporation

 www.eaton.com

5  communications

One of the most important functions of the Digitrip RMS 810 

Trip Unit is its ability to communicate both information and con-

trol signals via the Eaton proprietary INtegrated COMmunications 

(INCOM

®

) Local Area Network (LAN) .  INCOM

®

 interconnects 

microprocessor based (and other) electrical distribution and control 

products, with personal computers into a comprehensive information 

and control communications network (see Section 5 .5) .  The Digitrip 

RMS 810 Trip Unit already has INCOM

®

 capability for external com-

munications built into its microprocessor chip (see Figures 2, 21, 22, 

23, and the specific wiring diagrams for your circuit breaker listed in  

Section 6) .  The receiving terminal(s) can be:

• 

An Assemblies Electronic Monitor (AEM) or Breaker Interface 

Module (BIM) for local or remote monitoring (see Figure 22 and 

references in Section 6) .

• 

A remote master personal computer (PC) - IBM

®

 compatible (see 

Figure 21 and references in Section 6) .

• 

Both an AEM or BIM (for local monitoring) and a PC for remote 

monitoring and control (see Figure 23 and references in  

Section 6) .

5.1  Trip Unit Address and Baud Rate

To enable the INCOM

®

 communications system to identify each cir-

cuit breaker individually, the Digitrip RMS 810 Trip Unit has a unique 

3-digit "ADDRESS", which INCOM

®

 uses to identify the Trip Unit and 

the circuit breaker it controls .

NOTICE

NEW DIGITRIP MODEL 810 TRIP UNITS, AND TRIP UNITS PROVIDED AS A 

PART OF NEW CIRCUIT BREAKERS, WILL ALREADY CONTAIN A FACTORY-

SET BAUD RATE AND ADDRESS, WHICH IN GENERAL WILL NOT APPLY 

TO YOUR NETWORK.  FOR PROPER COMMUNICATIONS, EACH TRIP UNIT 

ADDRESS AND BAUD RATE MUST BE SET TO THE VALUES APPLICABLE 

FOR YOUR NETWORK.  SIMILARLY, PRIOR TO THE INSTALLATION OF A 

TRIP UNIT INTO ITS CIRCUIT BREAKER, OR PRIOR TO INSTALLATION OF 

A CIRCUIT BREAKER INTO ITS COMPARTMENT (AFTER MAINTENANCE 

FOR EXAMPLE), THE USER SHOULD VERIFY THAT THE BAUD RATE AND 

ADDRESS ARE CORRECT. FAILURE TO USE THE CORRECT BAUD RATE 

OR ADDRESS CAN CONFUSE THE COMMUNICATIONS SYSTEM.  IT IS 

RECOMMENDED THAT THE APPROPRIATE BAUD RATE, ADDRESS, AND 

CIRCUIT BREAKER CELL LOCATION OR BUS OR CIRCUIT REFERENCE BE 

RECORDED IN THE SPACES PROVIDED ON THE TRIP UNIT DISPLAY PANEL, 

FOR FUTURE REFERENCE (SEE FIGURE 1).

The User can view the present address and assign a new 3-digit 

address by the following procedure .

otee:

N

The breaker need not be open and may be carrying current .

1 .  Press-and-continue-to-hold-in the "TRIP RESET" push-button (see 

Figures 1 and 20) .

2 .  Watch the display window, and after about 5 seconds the param-

eter value will disappear, and either the letter "H" or "L" (baud rate 

code), followed by the 3-Digit address (between "001" and "999", 

there is no "000") will appear .  (You do need to continue to hold-in 

the "TRIP RESET" push button .)

3 .  To increment the address, press and release the (Black) 

"DEMAND RESET push button near the display window (see 

Figure 1) .  The address will increase by one unit each time you 

press the (Black) "DEMAND RESET push button .  If you press-

and-hold the (Black) "DEMAND RESET" push button, the address 

will increase continuously, slowly at first, and then faster as you 

continue to hold the button in .  (You do need to continue-to-hold-

in the "TRIP RESET" push-button while you do this .)

4 .  To decrement the address, press and release the (Black) "STEP" 

push button (see Figure 1) .  The address will decrease by one 

unit each time you press the (Black) "STEP" push button .  If you 

press-and-hold the (Black) "STEP" push button, the address will 

decrease continuously, slowly at first, and then faster as you con-

tinue to hold the button in .  (You do need to continue to hold-in 

the "TRIP RESET" push button while you do this .)

5 .  The letter "H" refers to the High 9600 Baud rate; and the letter "L" 

refers to the Low 1200 Baud Rate .  An " X in the Baud Rate field 

indicates that neither "H"igh nor "L”ow Baud Rate has been select-

ed .  Press and release the (Black) "TEST" push button to change 

the baud rate .  (You do need to continue-to hold-in the "TRIP 

RESET" push button .)  Suggestion: Before you press and release 

the (Black) "TEST" push button, set the "TEST AMPS" switch to "1 

", to minimize the effect of an "unintended test", which can occur, 

if your other finger would happen to come off the "TRIP RESET 

push button .

otee:

N

For correct communications, be sure to use the terminating resistor at 

the end of the twisted pair (last element in the INCOM

®

 chain) (see Figures 

21, 22, and 23, and refer to the IMPACC

®

 Wiring Specification listed in 

Section 6) .

6 .  When the address and baud rate code in the display window are 

correct, release the "TRIP RESET" push button to save the values 

into the Trip Unit's non-volatile memory, and the kA, MW or MWh 

value will return to the display window .  If control power is lost, 

the Trip Unit will still know its (new) address and baud rate .

otee:

N

If control power is lost while you are changing the address or baud rate, 

i .e .: while you are still holding-in the "TRIP RESET" push button, the display 

will go blank and when the control power is restored, the Trip Unit will still 

retain the previous address and baud rate values, as if you had not been trying 

to change them .

NOTICE

AS SHOWN IN FIGURE 1, TO THE LEFT AND BELOW THE DISPLAY WINDOW, 

IS A SPACE TO RECORD THE INCOM

®

 ADDRESS.  BECAUSE TRIP UNITS 

AND CIRCUIT BREAKERS OF THE SAME RATING ARE INTERCHANGEABLE, 

IF MORE THAN ONE HAS BEEN WITHDRAWN FOR MAINTENANCE AT ONE 

TIME, IT IS CRITICAL THAT THE EACH UNIT BE RETURNED TO ITS CORRECT 

CELL LOCATION SO THAT THE CIRCUIT HAS THE CORRECT ADDRESS.  

FOR EXAMPLE, IF TWO IDENTICAL BREAKERS (ONE WHOSE TRIP UNIT 

ADDRESS IS "001" AND THE OTHER WHOSE TRIP UNIT ADDRESS IS 

"100") WERE SWITCHED, THE INCOM

®

 COMMUNICATIONS SYSTEM WILL 

RESPOND PER THE INFORMATION FROM EACH TRIP UNIT'S ADDRESS 

NUMBER AND NOT THE NEW CELL POSITION.

5.2  Remote Master Computer

To communicate with a remote master (IBM

®

 compatible) personal 

computer, install a Eaton Computer Operated Network Interface 

(CONI) card or Master INCOM Network Translator (MINT) into the 

computer frame (chassis) .  The connections in the network are then 

made by twisted pairs of wires as shown in Figure 21 .

Summary of Contents for Cutler-Hammer Digitrip RMS 810

Page 1: ...persedes I L 29 888A 5 97 Instruction Leaflet I L 29 888B Instructions for Digitrip RMS 810 Trip Unit BCS Switchgear Inc Switchgear Circuit Breakers Parts Tech Support bcsswitchgear com 888 599 0486 N...

Page 2: ...7 No Instantaneous Current Setting 18 3 8 Ground Fault Current Setting 18 3 9 Ground Fault Time Delay Setting 19 4 Test Procedures 19 4 1 General 19 4 2 When To Test 19 4 3 Testing Provisions 20 4 4...

Page 3: ...lay Time Settings 18 Figure 17 Instantaneous Current Settings 18 Figure 18 Ground Fault Current Settings 18 Figure 19 Ground Fault Time Delay Settings 19 Figure 20 Integral Test Panel Lower Right Corn...

Page 4: ...uit breaker The Digitrip RMS 810 Trip Unit is designed for use in industrial circuit breaker environments where the ambient temperatures can range from 20 C to 85 C 4 F to 185 F and rarely exceed 70 t...

Page 5: ...in the LED RED and will continue to send a TRIP signal to LOCKOUT the circuit breaker until the Trip Unit is RESET The Digitrip RMS 810 Trip Unit can be RESET in two ways Either press and release the...

Page 6: ...l control power to operate its protection systems It operates from current signal levels and control power derived through current sensors inte grally mounted in the circuit breaker The Digitrip RMS 8...

Page 7: ...Current Setting Pick up Adj Time Delay Setting Opt I Squared T Curve Shape Opt Zone Interlocking Ground Fault Time Memory X X X X X X X X X X X X X X X 3 8 3 9 3 9 1 1 5 3 9 Trip Unit Over Temp TRIP X...

Page 8: ...Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Figure 3 Digitrip RMS 810 Type LI Figure 4 Digitrip RMS 810 Type LS Figure 5 Digitrip RMS 810 Type LSI F...

Page 9: ...e non adjustable release is pre set at eleven 11 times the installed rating plug current In The DlScriminator is enabled for approximate ly ten 10 cycles following the initial current flow through the...

Page 10: ...D TIME DELAY COORDINATION ONLY IS INTENDED THE ZONE INTERLOCKING TERMINALS MUST BE CONNECTED WITH JUMPER WIRES AS SPECIFIED ON THE CONNECTION DIAGRAMS FOR YOUR BREAKER SEE SECTION 6 SO THE TIME DELAY...

Page 11: ...Power and Energy Values 1 2 1 2 Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X X Energy Consumption MWh Reverse Energy Consumption X X X X X X X X X...

Page 12: ...will trip and the instantaneous override LED will light If breaker is open it will not close 1 3 ROM ERROR Nonfatal memory error Protection functions still operate but may be up to 12 out of tolerance...

Page 13: ...breaker positive flow of power If the power flows in the opposite direction i e bottom to top the value of power will not be displayed continuously Instead the power value in the display window will a...

Page 14: ...ttings without having to remove the circuit breaker from its enclosure For example if one expects a circuit to carry 600 A initially but then increase to 1400 A in the future one could initially insta...

Page 15: ...IP RELAY ALARMS MAY BE ERRATIC OR NONFUNCTIONAL IF WRONG VOLTAGE IS USED The relays operate when the Trip Unit detects the following condi tions as shown in Figure 2 Short Circuit Trip Alarm High Load...

Page 16: ...TESTS ON THE CIRCUIT BREAKER SEE ALSO THE SPECIFIC DIELECTRIC TEST PROCEDURES IN THE APPLICABLE CIRCUIT BREAKER INSTRUCTION LEAFLET LISTED IN SECTION 6 Figure 12 Auxiliary Power Module 1 6 Auxiliary...

Page 17: ...In Multiples of Rating Plug Amperes Ir Ir Ir In I n Ir 3 3 Long Delay Time Setting There are eight 8 available Long Delay Time Settings as illustrated in Figure 14 ranging from 2 to 24 seconds These...

Page 18: ...ts please see Sections 1 1 3 DlScriminator High initial Current Release and 1 1 4 OVERRIDE Fixed Instantaneous for available fast acting high short circuit pro tection 3 8 Ground Fault Current Setting...

Page 19: ...LED SEE FIGURE 11 AND INSTRUCTIONS FOR TESTING YOUR SPECIFIC CIRCUIT BREAKER LISTED IN SECTION 6 PTM OR TRIP UNIT DAMAGE OR FAILURE CAN RESULT FROM ENERGIZING PTM AT MORE THAN 600 VOLTS VERIFY THAT NO...

Page 20: ...o perform all of its Protection Functions with out the external control power and without the display and commu nication functions available results of the tests could be confusing When performing a s...

Page 21: ...At least one of the various protection settings will be less than 6x In and the circuit breaker will trip the LED related to that function will light RED and the reason for TRIP code will appear in t...

Page 22: ...ee Figure 1 The address will increase by one unit each time you press the Black DEMAND RESET push button If you press and hold the Black DEMAND RESET push button the address will increase continuously...

Page 23: ...IBM Twisted Pair No 18 AWG See Section 5 5 Cut off Shield at last Device Do Not Ground Breaker with RMS 810 Trip Unit 3 View A Refer to circuit breaker connection diagrams referenced in Section 6 for...

Page 24: ...he appropriate data decode and display it in a useful manner Following an over current trip operation the sequence of coded data varies slightly The cause of trip and the value and phase or ground cur...

Page 25: ...ues Phase A Current IA kA Phase B Current IB kA Phase C Current IC kA X X X X X X X X X X X X X X X X X X 1 2 1 1 I I Ground Current IG kA Neutral Current ID kA n n n X X X I 1 2 1 1 View Power Energy...

Page 26: ...LOCATION BY THE COMMUNICATIONS NETWORK CAN CAUSE PERSONAL INJURY TO MAINTENANCE PERSONNEL WORKING IN THE IMMEDIATE VICINITY OF THE CIRCUIT BREAKER PROVIDE PERMISSIVE CONTROL SWITCHES OR OTHER MEANS L...

Page 27: ...32 870 Typical Time Current Characteristic Curves for Types DS II and DSL II Circuit Breakers SC 5619 Instantaneous I SC 5620 Long Delay and Short Delay LS SC 5621 Ground G 1A33600 Connection Diagram...

Page 28: ...he event that the feeder breaker Z2 would not clear the fault the main breaker Z1 will clear the fault in 0 5 s as above Fault 1 There are no interlocking signals The main breaker trip unit will initi...

Page 29: ...ote N As the current approached the overload condition prior to the overload trip operation the following Trip Unit indications would have been visible The HILD message would begin to flash in the win...

Page 30: ...30 Instruction Leaflet I L 29 888B Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Notes...

Page 31: ...31 Instruction Leaflet I L 29 888B Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Notes...

Page 32: ...etween the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contr...

Reviews: