background image

19

Instruction Leaflet 

I. L. 29-888B

Effective July 2011

 Instructions for Digitrip RMS 810 Trip Unit

 

 

eaton corporation

 www.eaton.com

3.9  Ground Fault Time Delay Setting

As illustrated in Figure 19, there are two different Ground Fault 

curve shapes, i .e ., fixed time (flat) and I

2

t response .  The shape 

selected depends on the type of selective coordination chosen .  The 

I

2

t response will provide a longer time delay in the low-end of the 

ground fault current range than will the flat response .
Five flat ( .1,  .2,  .3,  .4,  .5 sec .) and three I

2

t ( .1*,  .3*,  .5* sec .) 

response time delay settings are available .  The I

2

t response settings 

are identified by the suffix asterisk (*) that appears in the setting 

viewing window .  The I

2

t response is applicable to currents less than 

0 .625 x I

n

, (the I

n

 value is marked on the installed rating plug) .  For 

currents greater than 0 .625 x I

n

, the I

2

t response reverts to the flat 

response .

otee:

N

See also Section 1 .1 .5 on Zone Interlocking .

otee:

N

In addition to the standard Ground Fault protection, the Digitrip RMS 

810 Trip Unit also has a GROUND TIME MEMORY (GTM) function, which 

serves to protect loads in the event of a sputtering arc to ground . Without 

the GTM function, the Trip Unit would normally reset each time the arc sput-

tered, and begin to time-out all over again, so that a sputtering fault may not 

have been detected .  But with the GTM function, the Trip Unit "remembers" 

the sputtering ground current for up to five (5) times the Ground Fault Time 

Setting .  After that time, it does reset automatically .  The GTM function does 

reset rather quickly; on the 0 .1 second setting, for example, it will reset in  

0 .5 second .

4  test procedures

4.1  General

DANGER

DO NOT ATTEMPT TO INSTALL, TEST OR PERFORM MAINTENANCE ON 

EQUIPMENT WHILE IT IS ENERGIZED.  DEATH OR SEVERE PERSONAL 

INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT. 

 

DE-ENERGIZE THE CIRCUIT AND DISCONNECT THE CIRCUIT BREAKER 

BEFORE PERFORMING MAINTENANCE OR TESTS. 

 

DO NOT ATTEMPT TO PERFORM DIELECTRIC (OR HIGH POT OR HIGH 

VOLTAGE) WITHSTAND TESTS ON THE CIRCUIT BREAKER WHILE THE 

VOLTAGE DISCONNECT PLUG TO THE POTENTIAL TRANSFORMER MODULE 

IS INSTALLED. (SEE FIGURE 11 AND INSTRUCTIONS FOR TESTING YOUR 

SPECIFIC CIRCUIT BREAKER LISTED IN SECTION 6).  PTM OR TRIP UNIT 

DAMAGE OR FAILURE CAN RESULT FROM ENERGIZING PTM AT MORE 

THAN 600 VOLTS. 

 

VERIFY THAT NO VOLTAGE IS PRESENT ON THE CIRCUIT BREAKER BEFORE 

REMOVING THE VOLTAGE DISCONNECT PLUG (SEE FIGURE 11). 

 

REMOVE THE VOLTAGE DISCONNECT PLUG TO ISOLATE THE POTENTIAL 

TRANSFORMER MODULE (FIGURE 11) BEFORE PERFORMING ANY VOLTAGE 

TESTS ON THE CIRCUIT BREAKER.  REINSTALL THE PLUG ONLY AFTER 

ALL VOLTAGE TESTS HAVE BEEN COMPLETED AND CONFIRM THAT NO 

VOLTAGE IS PRESENT ON THE CIRCUIT BREAKER. 

 

REINSTALL THE VOLTAGE DISCONNECT PLUG TO RECONNECT THE 

POTENTIAL TRANSFORMER MODULE BEFORE PLACING THE BREAKER 

BACK INTO SERVICE.  REFER TO THE APPLICABLE CIRCUIT BREAKER 

INSTRUCTION LEAFLET SUPPLEMENT (LISTED IN SECTION 6) FOR 

COMPLETE INSTRUCTIONS.

CAUTION

TESTING A CIRCUIT BREAKER UNDER "TRIP CONDITIONS" WHILE IT IS IN 

SERVICE AND CARRYING LOAD CURRENT, WHETHER DONE BY LOCALLY OR 

BY REMOTE MEANS, IS NOT RECOMMENDED. 

 

ANY TRIPPING OPERATION WILL CAUSE DISRUPTION OF SERVICE 

AND POSSIBLE PERSONAL INJURY RESULTING FROM UNNECESSARY 

SWITCHING OF CONNECTED EQUIPMENT. 

 

TESTING OF A CIRCUIT BREAKER THAT RESULTS IN THE TRIPPING OF THE 

CIRCUIT BREAKER SHOULD BE DONE ONLY WITH THE CIRCUIT BREAKER 

IN THE "TEST" OR "DISCONNECTED" CELL POSITIONS OR WHILE THE 

CIRCUIT BREAKER IS ON A TEST BENCH.

4.2  When To Test

Tests can be conducted with the breaker in the "connected" cell posi-

tion while carrying load current .  However, as stated in the caution 

note in Section 4 .1, good practice will limit circuit breaker in-service 

"trip tests", where required, to maintenance periods during times of 

minimum load conditions .  Testing is accomplished with the breaker 

out of its cell or in the "Test", "Disconnected", or "Withdrawn" (or 

Removed) cell positions .

otee:

N

Since time-current settings are based on desired system coordination 

and protection schemes, the protection settings selected and preset in accor-

dance with Section 3 should not be altered during or as a part of any routine 

test sequence .

Figure 19. Ground Fault Time Delay Settings.

.1*, .3*, .5*

.1, .2, .3, .4, .5

I

Available Settings

- -------

I

I

.

Seconds with

Flat Response 

,

.

.

Shape

Returns to Flat

Responses at 

Approximately

0.625

Seconds With

“*” In

Shape

Indicates

Shape

.3 Sec.

Gnd. Fault

Time

I

n

I  t

2

I  t

2

I  t

2

Viewing Window

Summary of Contents for Cutler-Hammer Digitrip RMS 810

Page 1: ...persedes I L 29 888A 5 97 Instruction Leaflet I L 29 888B Instructions for Digitrip RMS 810 Trip Unit BCS Switchgear Inc Switchgear Circuit Breakers Parts Tech Support bcsswitchgear com 888 599 0486 N...

Page 2: ...7 No Instantaneous Current Setting 18 3 8 Ground Fault Current Setting 18 3 9 Ground Fault Time Delay Setting 19 4 Test Procedures 19 4 1 General 19 4 2 When To Test 19 4 3 Testing Provisions 20 4 4...

Page 3: ...lay Time Settings 18 Figure 17 Instantaneous Current Settings 18 Figure 18 Ground Fault Current Settings 18 Figure 19 Ground Fault Time Delay Settings 19 Figure 20 Integral Test Panel Lower Right Corn...

Page 4: ...uit breaker The Digitrip RMS 810 Trip Unit is designed for use in industrial circuit breaker environments where the ambient temperatures can range from 20 C to 85 C 4 F to 185 F and rarely exceed 70 t...

Page 5: ...in the LED RED and will continue to send a TRIP signal to LOCKOUT the circuit breaker until the Trip Unit is RESET The Digitrip RMS 810 Trip Unit can be RESET in two ways Either press and release the...

Page 6: ...l control power to operate its protection systems It operates from current signal levels and control power derived through current sensors inte grally mounted in the circuit breaker The Digitrip RMS 8...

Page 7: ...Current Setting Pick up Adj Time Delay Setting Opt I Squared T Curve Shape Opt Zone Interlocking Ground Fault Time Memory X X X X X X X X X X X X X X X 3 8 3 9 3 9 1 1 5 3 9 Trip Unit Over Temp TRIP X...

Page 8: ...Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Figure 3 Digitrip RMS 810 Type LI Figure 4 Digitrip RMS 810 Type LS Figure 5 Digitrip RMS 810 Type LSI F...

Page 9: ...e non adjustable release is pre set at eleven 11 times the installed rating plug current In The DlScriminator is enabled for approximate ly ten 10 cycles following the initial current flow through the...

Page 10: ...D TIME DELAY COORDINATION ONLY IS INTENDED THE ZONE INTERLOCKING TERMINALS MUST BE CONNECTED WITH JUMPER WIRES AS SPECIFIED ON THE CONNECTION DIAGRAMS FOR YOUR BREAKER SEE SECTION 6 SO THE TIME DELAY...

Page 11: ...Power and Energy Values 1 2 1 2 Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X X Energy Consumption MWh Reverse Energy Consumption X X X X X X X X X...

Page 12: ...will trip and the instantaneous override LED will light If breaker is open it will not close 1 3 ROM ERROR Nonfatal memory error Protection functions still operate but may be up to 12 out of tolerance...

Page 13: ...breaker positive flow of power If the power flows in the opposite direction i e bottom to top the value of power will not be displayed continuously Instead the power value in the display window will a...

Page 14: ...ttings without having to remove the circuit breaker from its enclosure For example if one expects a circuit to carry 600 A initially but then increase to 1400 A in the future one could initially insta...

Page 15: ...IP RELAY ALARMS MAY BE ERRATIC OR NONFUNCTIONAL IF WRONG VOLTAGE IS USED The relays operate when the Trip Unit detects the following condi tions as shown in Figure 2 Short Circuit Trip Alarm High Load...

Page 16: ...TESTS ON THE CIRCUIT BREAKER SEE ALSO THE SPECIFIC DIELECTRIC TEST PROCEDURES IN THE APPLICABLE CIRCUIT BREAKER INSTRUCTION LEAFLET LISTED IN SECTION 6 Figure 12 Auxiliary Power Module 1 6 Auxiliary...

Page 17: ...In Multiples of Rating Plug Amperes Ir Ir Ir In I n Ir 3 3 Long Delay Time Setting There are eight 8 available Long Delay Time Settings as illustrated in Figure 14 ranging from 2 to 24 seconds These...

Page 18: ...ts please see Sections 1 1 3 DlScriminator High initial Current Release and 1 1 4 OVERRIDE Fixed Instantaneous for available fast acting high short circuit pro tection 3 8 Ground Fault Current Setting...

Page 19: ...LED SEE FIGURE 11 AND INSTRUCTIONS FOR TESTING YOUR SPECIFIC CIRCUIT BREAKER LISTED IN SECTION 6 PTM OR TRIP UNIT DAMAGE OR FAILURE CAN RESULT FROM ENERGIZING PTM AT MORE THAN 600 VOLTS VERIFY THAT NO...

Page 20: ...o perform all of its Protection Functions with out the external control power and without the display and commu nication functions available results of the tests could be confusing When performing a s...

Page 21: ...At least one of the various protection settings will be less than 6x In and the circuit breaker will trip the LED related to that function will light RED and the reason for TRIP code will appear in t...

Page 22: ...ee Figure 1 The address will increase by one unit each time you press the Black DEMAND RESET push button If you press and hold the Black DEMAND RESET push button the address will increase continuously...

Page 23: ...IBM Twisted Pair No 18 AWG See Section 5 5 Cut off Shield at last Device Do Not Ground Breaker with RMS 810 Trip Unit 3 View A Refer to circuit breaker connection diagrams referenced in Section 6 for...

Page 24: ...he appropriate data decode and display it in a useful manner Following an over current trip operation the sequence of coded data varies slightly The cause of trip and the value and phase or ground cur...

Page 25: ...ues Phase A Current IA kA Phase B Current IB kA Phase C Current IC kA X X X X X X X X X X X X X X X X X X 1 2 1 1 I I Ground Current IG kA Neutral Current ID kA n n n X X X I 1 2 1 1 View Power Energy...

Page 26: ...LOCATION BY THE COMMUNICATIONS NETWORK CAN CAUSE PERSONAL INJURY TO MAINTENANCE PERSONNEL WORKING IN THE IMMEDIATE VICINITY OF THE CIRCUIT BREAKER PROVIDE PERMISSIVE CONTROL SWITCHES OR OTHER MEANS L...

Page 27: ...32 870 Typical Time Current Characteristic Curves for Types DS II and DSL II Circuit Breakers SC 5619 Instantaneous I SC 5620 Long Delay and Short Delay LS SC 5621 Ground G 1A33600 Connection Diagram...

Page 28: ...he event that the feeder breaker Z2 would not clear the fault the main breaker Z1 will clear the fault in 0 5 s as above Fault 1 There are no interlocking signals The main breaker trip unit will initi...

Page 29: ...ote N As the current approached the overload condition prior to the overload trip operation the following Trip Unit indications would have been visible The HILD message would begin to flash in the win...

Page 30: ...30 Instruction Leaflet I L 29 888B Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Notes...

Page 31: ...31 Instruction Leaflet I L 29 888B Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Notes...

Page 32: ...etween the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contr...

Reviews: