background image

13

Instruction Leaflet 

I. L. 29-888B

Effective July 2011

 Instructions for Digitrip RMS 810 Trip Unit

 

 

eaton corporation

 www.eaton.com

1.2.1.2  Instrumentation - Power and Energy Values

The Digitrip RMS 810 Trip Unit displays power and energy values .  By 

using the circuit breaker current sensors and an integrally mounted 

Potential Transformer Module shown in Figure 11, power and energy 

values are computed and displayed in the four-digit display window 

on the face of the Trip Unit .
The power and energy parameter values displayed in the window on 

the face of the Trip Unit include:

• 

Peak Demand in MW (Megawatts),

• 

Present Demand in MW (Megawatts), and

• 

Energy (Consumed) in MWh (Megawatt-hours)

Three "Green" LEDs, as shown in Figure 1, are provided to indicate 

which value is displayed .  The same "STEP" push-button pressed and 

released to view the different values of current and voltage is also 

pressed and released to view the power and energy values .
The 

Peak Demand

 parameter is based on a sampling window of 

fifteen (15) minutes .  Power is repeatedly averaged over this interval 

and the maximum average is displayed as Peak Demand . The dis-

played value is the highest or peak value since the (Black) “Demand 

Reset”, push-button was last pressed and released . The demand 

window is not a "sliding window" . It is more like a 'jumping window" .  

When the Trip Unit is first energized, there is a delay of 15 min-

utes before the first non-zero value is displayed .  To reset the peak 

demand value shown in the display window back to zero, press and 

release the (Black) "Demand Reset" push-button, shown adjacent to 

the "Peak Demand" label in Figure 1 .

otee:

N

The peak demand function requires that 120 VAC control power be sup-

plied to the Power / Relay Module .

The 

Present Demand

 is a power value averaged over approximately 

one second .  To view the "Present Demand" value in the display win-

dow, press and release the "STEP" push-button several times until 

the LED next to "Present MW” is lighted .
The range, assumptions and accuracy parameters for peak and pres-

ent power demand values displayed are:
Range-    

 0 to 9 .999 MW

Assumes - 

 5% < Current < 175% of the Plug Rating I

n

Sampling Window-  

15 min.

 for 

Peak Demand, 1 sec.

 for 

 

 

 Present Demand

Accuracy- 

 

± 4%

 of (Frame Rating x 600 V) for Series C

®

 

 

 R-Frame or Type SPB circuit breakers,

 

or 

 

± 4%

 of (Current Sensor Rating x 600 V) for Type 

 

 

 DS circuit breakers .

The 

Energy

 parameter is the summation of the average power over 

time and it is expressed in megawatt-hours (MWh) .  The value is 

updated approximately once a second .  The value cannot be reset 

locally .  After the maximum value is reached, the display automati-

cally rolls over to zero .
The range and accuracy parameters for energy demand values dis-

played are:
Range- 

0 to 999 .9 MWh if I

n

 

 1000 A 

0 to 9999 MWh if I

n

 > 1000 A

Assumes- 

5% < Current < 175% of the Plug Rating I

n

Accuracy- 

± 5% of (Frame Rating x 600 V x time) for Series  

 C

®

 R-Frame or Type SPB circuit breakers .

or 

± 5% of (Current Sensor Rating x 600 V x time)  

for Type DS circuit breakers .

The energy value is stored in the Trip Unit memory .  As long as the 

120 Vac control power is maintained to the Power / Relay Module, 

it can be viewed .  If the 120 Vac control power is lost and then is 

restored, the Energy value is also restored . 
The Digitrip RMS 810 Trip Unit presumes that power is flowing into 

the "top" and out of the bottom of the circuit breaker (positive flow of 

power) .  If the power flows in the opposite direction, i .e ., bottom to 

top, the value of power will not be displayed continuously .  Instead, 

the power value in the display window will alternate with the 

coded message "NPOW" .  This message, alternating with the value, 

indicates power flowing out of the top of the circuit breaker .  This 

condition will occur when a Main circuit breaker is "reverse fed" and 

can frequently occur for three breaker schemes that involve a “tie” 

breaker .  The "NPOW” message can be defeated on type 

DS

 and 

type 

SPB

 breakers only by inserting an appropriate “jumper" (see 

wiring diagram for your type of circuit breaker listed in Section 6) .

1.2.2  Messages Displayed After ALARM or TRIP

During an ALARM condition or after a circuit breaker TRIP opera-

tion, one of the coded messages listed in Table 3 will appear in 

the display window, provided control power is still available for the 

Power/Relay Module (see Section 1 .4) .  If the "STEP" push-button is 

pressed, the message will be deleted so that menu values of cur-

rents (kA) etc . can be viewed .

otee:

N

The user should view all of the currents .  The first value you see may 

not be the greatest .

Following a circuit breaker TRIP operation, the display window 

indicates the reason for trip, using coded messages such as, INST 

(Instantaneous Trip), LDT (Long Delay Trip) etc .  As with the ALARM 

function, press and release the "STEP" push-button to delete the 

reason for trip message and the display window will then show the 

values of current at the time of trip (see Notes (1), (2), and (3) under 

Table 3) .  The values remain in memory, and the "red" reason for Trip 

LED (see Figures 1 and 3 through 8) remains lighted, until the Trip 

Unit is reset by pressing and releasing the "TRIP RESET push-button 

in the lower right corner of the Trip Unit (see Figure 1) .

otee:

N

After a trip condition, RECORD all Values of interest and note which 

"RED" LEDs are lighted .  Correct the cause of the overload or fault BEFORE 

YOU RESET the Trip Unit to avoid repeated tripping .

The LOCKOUT after trip feature requires the Trip Unit to be reset 

before the breaker can be closed again .
For examples of how to interpret the display after an overload and 

after a short-circuit, see Appendix B .

1.2.1.1  ROM Error ... See I.L.

If the message, "ROM Error .  .  . See I .L .", scrolls across the display 

window, it means that a non-fatal error has been detected some-

where in the Trip Unit's non-volatile memory .  The Trip Unit will still 

function to protect the circuit, but the calibration may be degraded 

by a few percent . The Time-Current Curve tolerances may be exceed-

ed in some cases by as much as 12% .It is not necessary to trip and 

lockout the breaker . There may also be errors in values of current, 

energy, and power displayed and they could even be greater than 

12% . The scrolling message will not remain in the window constant-

ly but is repeated periodically to remind you to replace the Trip Unit .

1.3  Frame Rating, Sensor Rating (Where Applicable) and 

Rating Plugs

The 

Frame Rating

 of a circuit breaker is the maximum RMS cur-

rent it can carry continuously .  The maximum Short-Circuit Current 

Ratings of the circuit breaker are usually related to the Frame Rating 

as well .
It is often times desirable to be able to choose a current value 

(I

n

)

less than the full frame rating, to be the basis for the circuit break-

er's protection functions, without affecting its short-circuit current 

capability .  For the Digitrip RMS 810 Trip Unit the maximum continu-

ous current (I

n

) is set by the 

Rating Plug

 (and/or 

Current Sensors

Summary of Contents for Cutler-Hammer Digitrip RMS 810

Page 1: ...persedes I L 29 888A 5 97 Instruction Leaflet I L 29 888B Instructions for Digitrip RMS 810 Trip Unit BCS Switchgear Inc Switchgear Circuit Breakers Parts Tech Support bcsswitchgear com 888 599 0486 N...

Page 2: ...7 No Instantaneous Current Setting 18 3 8 Ground Fault Current Setting 18 3 9 Ground Fault Time Delay Setting 19 4 Test Procedures 19 4 1 General 19 4 2 When To Test 19 4 3 Testing Provisions 20 4 4...

Page 3: ...lay Time Settings 18 Figure 17 Instantaneous Current Settings 18 Figure 18 Ground Fault Current Settings 18 Figure 19 Ground Fault Time Delay Settings 19 Figure 20 Integral Test Panel Lower Right Corn...

Page 4: ...uit breaker The Digitrip RMS 810 Trip Unit is designed for use in industrial circuit breaker environments where the ambient temperatures can range from 20 C to 85 C 4 F to 185 F and rarely exceed 70 t...

Page 5: ...in the LED RED and will continue to send a TRIP signal to LOCKOUT the circuit breaker until the Trip Unit is RESET The Digitrip RMS 810 Trip Unit can be RESET in two ways Either press and release the...

Page 6: ...l control power to operate its protection systems It operates from current signal levels and control power derived through current sensors inte grally mounted in the circuit breaker The Digitrip RMS 8...

Page 7: ...Current Setting Pick up Adj Time Delay Setting Opt I Squared T Curve Shape Opt Zone Interlocking Ground Fault Time Memory X X X X X X X X X X X X X X X 3 8 3 9 3 9 1 1 5 3 9 Trip Unit Over Temp TRIP X...

Page 8: ...Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Figure 3 Digitrip RMS 810 Type LI Figure 4 Digitrip RMS 810 Type LS Figure 5 Digitrip RMS 810 Type LSI F...

Page 9: ...e non adjustable release is pre set at eleven 11 times the installed rating plug current In The DlScriminator is enabled for approximate ly ten 10 cycles following the initial current flow through the...

Page 10: ...D TIME DELAY COORDINATION ONLY IS INTENDED THE ZONE INTERLOCKING TERMINALS MUST BE CONNECTED WITH JUMPER WIRES AS SPECIFIED ON THE CONNECTION DIAGRAMS FOR YOUR BREAKER SEE SECTION 6 SO THE TIME DELAY...

Page 11: ...Power and Energy Values 1 2 1 2 Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X X Energy Consumption MWh Reverse Energy Consumption X X X X X X X X X...

Page 12: ...will trip and the instantaneous override LED will light If breaker is open it will not close 1 3 ROM ERROR Nonfatal memory error Protection functions still operate but may be up to 12 out of tolerance...

Page 13: ...breaker positive flow of power If the power flows in the opposite direction i e bottom to top the value of power will not be displayed continuously Instead the power value in the display window will a...

Page 14: ...ttings without having to remove the circuit breaker from its enclosure For example if one expects a circuit to carry 600 A initially but then increase to 1400 A in the future one could initially insta...

Page 15: ...IP RELAY ALARMS MAY BE ERRATIC OR NONFUNCTIONAL IF WRONG VOLTAGE IS USED The relays operate when the Trip Unit detects the following condi tions as shown in Figure 2 Short Circuit Trip Alarm High Load...

Page 16: ...TESTS ON THE CIRCUIT BREAKER SEE ALSO THE SPECIFIC DIELECTRIC TEST PROCEDURES IN THE APPLICABLE CIRCUIT BREAKER INSTRUCTION LEAFLET LISTED IN SECTION 6 Figure 12 Auxiliary Power Module 1 6 Auxiliary...

Page 17: ...In Multiples of Rating Plug Amperes Ir Ir Ir In I n Ir 3 3 Long Delay Time Setting There are eight 8 available Long Delay Time Settings as illustrated in Figure 14 ranging from 2 to 24 seconds These...

Page 18: ...ts please see Sections 1 1 3 DlScriminator High initial Current Release and 1 1 4 OVERRIDE Fixed Instantaneous for available fast acting high short circuit pro tection 3 8 Ground Fault Current Setting...

Page 19: ...LED SEE FIGURE 11 AND INSTRUCTIONS FOR TESTING YOUR SPECIFIC CIRCUIT BREAKER LISTED IN SECTION 6 PTM OR TRIP UNIT DAMAGE OR FAILURE CAN RESULT FROM ENERGIZING PTM AT MORE THAN 600 VOLTS VERIFY THAT NO...

Page 20: ...o perform all of its Protection Functions with out the external control power and without the display and commu nication functions available results of the tests could be confusing When performing a s...

Page 21: ...At least one of the various protection settings will be less than 6x In and the circuit breaker will trip the LED related to that function will light RED and the reason for TRIP code will appear in t...

Page 22: ...ee Figure 1 The address will increase by one unit each time you press the Black DEMAND RESET push button If you press and hold the Black DEMAND RESET push button the address will increase continuously...

Page 23: ...IBM Twisted Pair No 18 AWG See Section 5 5 Cut off Shield at last Device Do Not Ground Breaker with RMS 810 Trip Unit 3 View A Refer to circuit breaker connection diagrams referenced in Section 6 for...

Page 24: ...he appropriate data decode and display it in a useful manner Following an over current trip operation the sequence of coded data varies slightly The cause of trip and the value and phase or ground cur...

Page 25: ...ues Phase A Current IA kA Phase B Current IB kA Phase C Current IC kA X X X X X X X X X X X X X X X X X X 1 2 1 1 I I Ground Current IG kA Neutral Current ID kA n n n X X X I 1 2 1 1 View Power Energy...

Page 26: ...LOCATION BY THE COMMUNICATIONS NETWORK CAN CAUSE PERSONAL INJURY TO MAINTENANCE PERSONNEL WORKING IN THE IMMEDIATE VICINITY OF THE CIRCUIT BREAKER PROVIDE PERMISSIVE CONTROL SWITCHES OR OTHER MEANS L...

Page 27: ...32 870 Typical Time Current Characteristic Curves for Types DS II and DSL II Circuit Breakers SC 5619 Instantaneous I SC 5620 Long Delay and Short Delay LS SC 5621 Ground G 1A33600 Connection Diagram...

Page 28: ...he event that the feeder breaker Z2 would not clear the fault the main breaker Z1 will clear the fault in 0 5 s as above Fault 1 There are no interlocking signals The main breaker trip unit will initi...

Page 29: ...ote N As the current approached the overload condition prior to the overload trip operation the following Trip Unit indications would have been visible The HILD message would begin to flash in the win...

Page 30: ...30 Instruction Leaflet I L 29 888B Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Notes...

Page 31: ...31 Instruction Leaflet I L 29 888B Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Notes...

Page 32: ...etween the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contr...

Reviews: