background image

29

Instruction Leaflet 

I. L. 29-888B

Effective July 2011

 Instructions for Digitrip RMS 810 Trip Unit

 

 

eaton corporation

 www.eaton.com

appenDiX B:  interpreting Display codes  

 

 

    after circuit Breaker trips

Given a 1600 A frame circuit breaker with an I

n

 = 1000 A rating 

plug installed.
CASE 1e:  Overload Trip Operation and High Load Condition

Long Delay Current (Pick-up) Setting = 1 .0, 

I

r

 = 1000 A

Assume a prolonged 1500 A overload condition which results in an 

automatic breaker trip operation .  The following will occur:

• 

The Long Delay Trip LED will turn "On" (see Figure 1) .

• 

The coded message "LDT will appear in the Display Window (see 

Figure 1) .

• 

The Long Delay Relay in the Power / Relay Module (see Figures 

2 and 10) will operate to close the remote Long Delay Trip Alarm 

Contact .

Operator Actionse:

1 .  Observe the mode of trip LED and coded message in the Display 

Window .

2 .  Press and release "STEP" push-button (see Figure 1) .  This will 

clear the coded cause of trip message in the Display Window .

3.  View values of phase currents in Display Window (see  

Figure 1), e.g.: 

1.50 kA.

otee:

N

The phase current shown will be that identified by the "green" LED (see 

Figure 1) that is turned "On", assume "

I

A

" .  (It may not be the faulted phase .)

4 .  Press and release the "STEP" push-button to view current values 

similar to "I

A

", "I

B

", "I

C

", "I

G

" and "I

D

" .  Each value of phase current 

kA

 appearing in the Display Window is the value at the time of 

the trip operation .

5. 

RECORD

 all Values of interest; note which 

"RED" LEDs

 are light-

ed 

BEFORE

 resetting the Trip Unit .

6 .  Reset the Trip Unit by pressing and releasing the "Trip Reset" 

push-button (lower right corner of Trip Unit, see Figure 1) .  All 

coded messages and/or current values in the display window and 

the cause of trip LED will turn "Off", and the Remote Alarm con-

tacts in the Power / Relay Module will be reset (open) .

NOTICE

FOLLOWING 

LDT

 TRIP OPERATIONS, IT IS ESSENTIAL THAT ANY CAUSE 

OF OVERLOAD TRIP BE CORRECTED PRIOR TO RECLOSING THE CIRCUIT 

BREAKER. SHOULD IT NOT BE CORRECTED AND THE CIRCUIT BREAKER BE 

RE-CLOSED TOO QUICKLY, THEN BECAUSE OF THE INHERENT LONG TIME 

MEMORY FUNCTION (SEE NOTE IN SECTION 3.3), THE LONG DELAY TRIP 

ELEMENT WILL OPERATE FASTER THAN THE RELATED TIME-CURRENT 

CURVE INDICATES. 

 

THE AMOUNT OF TIME REQUIRED TO CLEAR THE LTM MEMORY CIRCUIT 

IS A FUNCTION OF THE LONG DELAY TIME SETTING (SEE FIGURE 5).  THE 

LONGER THE DELAY SETTING, THE LONGER THE TIME REQUIRED TO 

RESET THE MEMORY.  TOTAL MEMORY CLEARING TIME COULD BE UP TO 

TWELVE (12) MINUTES.  THE LTM CAN BE RESET QUICKLY AS DESCRIBED IN 

SECTION 4.4 (3).

The LTM memory function, simulates the conventional thermal type 

(bi-metal) circuit breaker Trip Unit, and serves a useful function by 

allowing the load conductors to cool down after an overload condition .

7 .  After correcting the cause of the overload trip (LDT), allow for the 

LTM memory circuit to reset and reclose the circuit breaker to 

restore power to the load circuit .

otee:

N

As the current approached the overload condition, prior to the overload 

trip operation, the following Trip Unit indications would have been visible .

• 

The "HILD" message would begin to flash in the window when 

the overload condition had exceeded 0 .85 x 

I

r

 for 40 seconds 

or longer .  To clear the "HILD" message and to view the present 

magnitudes of the currents, press and release the (Black) "STEP" 

push button on the display panel .  Remember to push the "STEP" 

button several times to be sure you see values of currents in all 

phases, and ground/neutral as applicable .

• 

The "High-Load" Relay in the Power / Relay Module (see Figures 

2, 10, and Section 1 .4) would have been picked up (after a 40-sec-

ond delay), to close the remote High Load Alarm Contact .  Press 

and release the "TRIP RESET" push-button to reset the High Load 

Relay Contact, or reset the Trip unit remotely by INCOM

®

 (see 

Section 5 .9) .

• 

The Long Delay LED (Figure 1) begins to flash "On" and "Off" .

• 

The message "LDPU" begins to flash in the display window when 

the current value exceeds 

I

r

 .

CASE 2e:  lnstantaneous Trip Operation

lnstantaneous Current (Pick-up) Setting = 8 x I

n

 = 8000 A

Assume a 12 kA fault occurs .
Following the TRIP operation, the following will occur:

• 

The lnstantaneous Trip LED will turn "On" (see Figure 1) .

• 

The coded message "INST will appear in the Display Window (see 

Figure 1) .

• 

The Short-Circuit Relay in the Power / Relay Module (see Figures 

2, 10, and Section 1 .4) will operate to close the Remote Short-

Circuit Trip Alarm contact .

Operator Actionse:

1 .  Observe the mode of trip LED and the "INST" message in the 

Display Window .

2.  Press and release the "STEP" push-button to view current 

values "I

A

", "I

B

", "I

C

", and "I

G

" or "I

D

" in the display window.

otee:

N

The phase current value displayed will be that identified by the "green" 

LED (see Figure 1) that is turned "On" .  (But, the first value you see may not 

be for the faulted phase .) Each value of phase current appearing in the Display 

Window, is the value at the time the trip operation was initiated .

3. 

RECORD all Values

 of interest; note which 

"RED" LEDs

 are 

lighted 

BEFORE

 resetting the Trip Unit .

4 .  The value of one phase current in display window (see Figure 1) 

will have been the 12 .0 kA fault level .

otee:

N

Had the level of the fault current been more than 28 x 

I

n

 (or 28 kA in 

this example) when the reason for trip message would be cleared (by push-

ing the "STEP" button), instead of the numerical value of current in kA, the 

"ORNG" code is displayed to show the current level exceeded maximum 

range of current sensor accuracy .

5 .  After making sure you have a record of all pertinent information 

stored in the Trip Unit memory, reset the Trip Unit by pressing 

and releasing the "Trip Reset" push-button (lower right corner of 

the Trip Unit, see Figure 1) .  All coded messages, values of cur-

rent in the display window memory, and cause of trip LEDs will 

turn "OFF", while the Remote Alarm Contacts of the signal relay 

in the Power / Relay Module will reset (open) .

6 .  Following any corrective actions and/or inspections of the circuit 

breaker and related equipment, re-close the circuit breaker to 

restore power to the load circuit .

Summary of Contents for Cutler-Hammer Digitrip RMS 810

Page 1: ...persedes I L 29 888A 5 97 Instruction Leaflet I L 29 888B Instructions for Digitrip RMS 810 Trip Unit BCS Switchgear Inc Switchgear Circuit Breakers Parts Tech Support bcsswitchgear com 888 599 0486 N...

Page 2: ...7 No Instantaneous Current Setting 18 3 8 Ground Fault Current Setting 18 3 9 Ground Fault Time Delay Setting 19 4 Test Procedures 19 4 1 General 19 4 2 When To Test 19 4 3 Testing Provisions 20 4 4...

Page 3: ...lay Time Settings 18 Figure 17 Instantaneous Current Settings 18 Figure 18 Ground Fault Current Settings 18 Figure 19 Ground Fault Time Delay Settings 19 Figure 20 Integral Test Panel Lower Right Corn...

Page 4: ...uit breaker The Digitrip RMS 810 Trip Unit is designed for use in industrial circuit breaker environments where the ambient temperatures can range from 20 C to 85 C 4 F to 185 F and rarely exceed 70 t...

Page 5: ...in the LED RED and will continue to send a TRIP signal to LOCKOUT the circuit breaker until the Trip Unit is RESET The Digitrip RMS 810 Trip Unit can be RESET in two ways Either press and release the...

Page 6: ...l control power to operate its protection systems It operates from current signal levels and control power derived through current sensors inte grally mounted in the circuit breaker The Digitrip RMS 8...

Page 7: ...Current Setting Pick up Adj Time Delay Setting Opt I Squared T Curve Shape Opt Zone Interlocking Ground Fault Time Memory X X X X X X X X X X X X X X X 3 8 3 9 3 9 1 1 5 3 9 Trip Unit Over Temp TRIP X...

Page 8: ...Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Figure 3 Digitrip RMS 810 Type LI Figure 4 Digitrip RMS 810 Type LS Figure 5 Digitrip RMS 810 Type LSI F...

Page 9: ...e non adjustable release is pre set at eleven 11 times the installed rating plug current In The DlScriminator is enabled for approximate ly ten 10 cycles following the initial current flow through the...

Page 10: ...D TIME DELAY COORDINATION ONLY IS INTENDED THE ZONE INTERLOCKING TERMINALS MUST BE CONNECTED WITH JUMPER WIRES AS SPECIFIED ON THE CONNECTION DIAGRAMS FOR YOUR BREAKER SEE SECTION 6 SO THE TIME DELAY...

Page 11: ...Power and Energy Values 1 2 1 2 Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X X Energy Consumption MWh Reverse Energy Consumption X X X X X X X X X...

Page 12: ...will trip and the instantaneous override LED will light If breaker is open it will not close 1 3 ROM ERROR Nonfatal memory error Protection functions still operate but may be up to 12 out of tolerance...

Page 13: ...breaker positive flow of power If the power flows in the opposite direction i e bottom to top the value of power will not be displayed continuously Instead the power value in the display window will a...

Page 14: ...ttings without having to remove the circuit breaker from its enclosure For example if one expects a circuit to carry 600 A initially but then increase to 1400 A in the future one could initially insta...

Page 15: ...IP RELAY ALARMS MAY BE ERRATIC OR NONFUNCTIONAL IF WRONG VOLTAGE IS USED The relays operate when the Trip Unit detects the following condi tions as shown in Figure 2 Short Circuit Trip Alarm High Load...

Page 16: ...TESTS ON THE CIRCUIT BREAKER SEE ALSO THE SPECIFIC DIELECTRIC TEST PROCEDURES IN THE APPLICABLE CIRCUIT BREAKER INSTRUCTION LEAFLET LISTED IN SECTION 6 Figure 12 Auxiliary Power Module 1 6 Auxiliary...

Page 17: ...In Multiples of Rating Plug Amperes Ir Ir Ir In I n Ir 3 3 Long Delay Time Setting There are eight 8 available Long Delay Time Settings as illustrated in Figure 14 ranging from 2 to 24 seconds These...

Page 18: ...ts please see Sections 1 1 3 DlScriminator High initial Current Release and 1 1 4 OVERRIDE Fixed Instantaneous for available fast acting high short circuit pro tection 3 8 Ground Fault Current Setting...

Page 19: ...LED SEE FIGURE 11 AND INSTRUCTIONS FOR TESTING YOUR SPECIFIC CIRCUIT BREAKER LISTED IN SECTION 6 PTM OR TRIP UNIT DAMAGE OR FAILURE CAN RESULT FROM ENERGIZING PTM AT MORE THAN 600 VOLTS VERIFY THAT NO...

Page 20: ...o perform all of its Protection Functions with out the external control power and without the display and commu nication functions available results of the tests could be confusing When performing a s...

Page 21: ...At least one of the various protection settings will be less than 6x In and the circuit breaker will trip the LED related to that function will light RED and the reason for TRIP code will appear in t...

Page 22: ...ee Figure 1 The address will increase by one unit each time you press the Black DEMAND RESET push button If you press and hold the Black DEMAND RESET push button the address will increase continuously...

Page 23: ...IBM Twisted Pair No 18 AWG See Section 5 5 Cut off Shield at last Device Do Not Ground Breaker with RMS 810 Trip Unit 3 View A Refer to circuit breaker connection diagrams referenced in Section 6 for...

Page 24: ...he appropriate data decode and display it in a useful manner Following an over current trip operation the sequence of coded data varies slightly The cause of trip and the value and phase or ground cur...

Page 25: ...ues Phase A Current IA kA Phase B Current IB kA Phase C Current IC kA X X X X X X X X X X X X X X X X X X 1 2 1 1 I I Ground Current IG kA Neutral Current ID kA n n n X X X I 1 2 1 1 View Power Energy...

Page 26: ...LOCATION BY THE COMMUNICATIONS NETWORK CAN CAUSE PERSONAL INJURY TO MAINTENANCE PERSONNEL WORKING IN THE IMMEDIATE VICINITY OF THE CIRCUIT BREAKER PROVIDE PERMISSIVE CONTROL SWITCHES OR OTHER MEANS L...

Page 27: ...32 870 Typical Time Current Characteristic Curves for Types DS II and DSL II Circuit Breakers SC 5619 Instantaneous I SC 5620 Long Delay and Short Delay LS SC 5621 Ground G 1A33600 Connection Diagram...

Page 28: ...he event that the feeder breaker Z2 would not clear the fault the main breaker Z1 will clear the fault in 0 5 s as above Fault 1 There are no interlocking signals The main breaker trip unit will initi...

Page 29: ...ote N As the current approached the overload condition prior to the overload trip operation the following Trip Unit indications would have been visible The HILD message would begin to flash in the win...

Page 30: ...30 Instruction Leaflet I L 29 888B Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Notes...

Page 31: ...31 Instruction Leaflet I L 29 888B Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Notes...

Page 32: ...etween the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contr...

Reviews: