background image

14

Instruction Leaflet 

I. L. 29-888B

Effective July 2011

 Instructions for Digitrip RMS 810 Trip Unit

 

 

eaton corporation

 www.eaton.com

where applicable) - see Section 6 for specific instructions for your 

circuit breaker type .
The 

(Current) Sensor Rating

 (where applicable) is the maximum 

RMS current the circuit breaker can carry with the specified current 

sensors installed .  The Sensor Rating can be the same or less than 

the Frame Rating, but not greater .
The 

Rating Plug

 (see Figure 9) fits into a special cavity to complete 

the Trip Unit (see Figure 1) .

Figure 9. Rating Plug.

CAUTION

BEFORE YOU FIT THE RATING PLUG INTO THE TRIP UNIT, BE SURE TO CHECK THAT 

THE BREAKER TYPE AND FRAME RATING (OR SENSOR RATING IF APPLICABLE), 

MATCH THOSE PRINTED ON THE RATING PLUG COVER.  INSTALLING A RATING PLUG 

THAT DOES NOT MATCH THE BREAKER TYPE AND FRAME RATING (OR SENSOR 

RATING, IF APPLICABLE), CAN PRODUCE SERIOUS MIS-COORDINATION AND/OR 

FAILURE OF THE PROTECTION SYSTEM.

After installing the Rating Plug, press and release the "TRIP RESET" 

push-button to turn off any illuminated LEDs .  The purpose of the 

rating plug is to set the value of I

n

, the basis for the Trip Unit protec-

tion function current settings (see Section 3 for details) .  Each circuit 

breaker frame rating represents the maximum current it can carry 

continuously .  However for proper coordination of over-current pro-

tection, it is often desirable to choose different levels of I

n

 for differ-

ent circuit breakers of the same frame rating .  An assortment of rat-

ing plugs with different I

n

 values is available for each breaker frame 

rating (see circuit breaker instruction leaflet supplements listed in 

Section 6) to give the user flexibility to change the value of I

n

 with-

out having to change the primary current sensors on the breaker .  

By changing the rating plug, the User can easily change the range 

of current protection settings without having to remove the circuit 

breaker from its enclosure .
For example, if one expects a circuit to carry 600 A initially, but 

then increase to 1400 A in the future, one could initially install 1600 

A cables and a 1600 A breaker frame with the Trip Unit rating plug 

whose I

n

 = 800 A .  Then later on when the additional load is ready 

to come on line, the rating plug could be exchanged for one with I

n

 

= 1600 A, without having to remove the breaker from its enclosure .  

The available settings would give the following choices:

Long Delay Setting
  I

r

 = I

n

 x:  .5   .6   .7   .8   .85   .9   .95  1 .0

Plug I

n

 =800 A

 

LDPU I

r

 = : 400  480  560  640  680  720  760  800 A

Plug I

n

 = 1600 A

 

LDPU I

r

 = : 800  960  1120  1280  1360  1440  1520  1600 A

otee:

N

Rating plugs from Digitrip models 500 / 600 / 700 / 800 CANNOT be 

used with model 810 Trip Units .  The connection pins are located in different 

positions, so one cannot accidentally use the incorrect type of plug .

Rating Plugs for the Digitrip RMS 810 Trip Units are marked for, and 

may be applied on both 50 and 60 Hz systems .
Rating plugs have two current ratings listed on their covers (see 

Figure 9) .

• 

The "Must Use With Frame Rated" current value (or "Sensor 

Rated", if applicable),

and

• 

" I

n

 (rated I)=" current value .

This latter value (I

n

) is the basis for the Trip Unit current settings:

• 

The instantaneous and Ground Current Settings (if applicable) are 

multiples of (I

n

) (see Sections 3 .6 and 3 .8 .) .

• 

The Long Delay Current Setting, 

I

r

  is a multiple of (I

n

) .  Long 

Delay Current Setting = 

I

r

 = LD x (I

n

) (see Section 3 .2 .) .

• 

The Short Delay Current Setting (if provided) is a multiple of 

I

r

 

which in turn is a multiple of (I

n

) .  Short Delay Current Setting = 

SD x 

I

r

 = SD x LD x (I

n

) (see Section 3 .4) .

Polarity 

Marks

Hinged 

Cover

Battery

Rating Plug 

is for Type 

SPB Circuit 

Breakers Only

Rating Plug 

for R-Frame 

and DS 

Breakers 

are Similar

Values for Short 

Delay S1 and S2 

Instantaneous 

M1 and M2 

Settings

Pull Tab to 

Remove 

Battery

Rating Plug 

Identification

"Battery 

Check" 

Push 

button

Battery "OK" 

if LED Lights 

"GREEN" when 

"Battery Check" 

Button is 

Pushed

Rating Plug 

Retention 

Screw

Battery 

Removal Tab

Polarity

-

+

Summary of Contents for Cutler-Hammer Digitrip RMS 810

Page 1: ...persedes I L 29 888A 5 97 Instruction Leaflet I L 29 888B Instructions for Digitrip RMS 810 Trip Unit BCS Switchgear Inc Switchgear Circuit Breakers Parts Tech Support bcsswitchgear com 888 599 0486 N...

Page 2: ...7 No Instantaneous Current Setting 18 3 8 Ground Fault Current Setting 18 3 9 Ground Fault Time Delay Setting 19 4 Test Procedures 19 4 1 General 19 4 2 When To Test 19 4 3 Testing Provisions 20 4 4...

Page 3: ...lay Time Settings 18 Figure 17 Instantaneous Current Settings 18 Figure 18 Ground Fault Current Settings 18 Figure 19 Ground Fault Time Delay Settings 19 Figure 20 Integral Test Panel Lower Right Corn...

Page 4: ...uit breaker The Digitrip RMS 810 Trip Unit is designed for use in industrial circuit breaker environments where the ambient temperatures can range from 20 C to 85 C 4 F to 185 F and rarely exceed 70 t...

Page 5: ...in the LED RED and will continue to send a TRIP signal to LOCKOUT the circuit breaker until the Trip Unit is RESET The Digitrip RMS 810 Trip Unit can be RESET in two ways Either press and release the...

Page 6: ...l control power to operate its protection systems It operates from current signal levels and control power derived through current sensors inte grally mounted in the circuit breaker The Digitrip RMS 8...

Page 7: ...Current Setting Pick up Adj Time Delay Setting Opt I Squared T Curve Shape Opt Zone Interlocking Ground Fault Time Memory X X X X X X X X X X X X X X X 3 8 3 9 3 9 1 1 5 3 9 Trip Unit Over Temp TRIP X...

Page 8: ...Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Figure 3 Digitrip RMS 810 Type LI Figure 4 Digitrip RMS 810 Type LS Figure 5 Digitrip RMS 810 Type LSI F...

Page 9: ...e non adjustable release is pre set at eleven 11 times the installed rating plug current In The DlScriminator is enabled for approximate ly ten 10 cycles following the initial current flow through the...

Page 10: ...D TIME DELAY COORDINATION ONLY IS INTENDED THE ZONE INTERLOCKING TERMINALS MUST BE CONNECTED WITH JUMPER WIRES AS SPECIFIED ON THE CONNECTION DIAGRAMS FOR YOUR BREAKER SEE SECTION 6 SO THE TIME DELAY...

Page 11: ...Power and Energy Values 1 2 1 2 Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X X Energy Consumption MWh Reverse Energy Consumption X X X X X X X X X...

Page 12: ...will trip and the instantaneous override LED will light If breaker is open it will not close 1 3 ROM ERROR Nonfatal memory error Protection functions still operate but may be up to 12 out of tolerance...

Page 13: ...breaker positive flow of power If the power flows in the opposite direction i e bottom to top the value of power will not be displayed continuously Instead the power value in the display window will a...

Page 14: ...ttings without having to remove the circuit breaker from its enclosure For example if one expects a circuit to carry 600 A initially but then increase to 1400 A in the future one could initially insta...

Page 15: ...IP RELAY ALARMS MAY BE ERRATIC OR NONFUNCTIONAL IF WRONG VOLTAGE IS USED The relays operate when the Trip Unit detects the following condi tions as shown in Figure 2 Short Circuit Trip Alarm High Load...

Page 16: ...TESTS ON THE CIRCUIT BREAKER SEE ALSO THE SPECIFIC DIELECTRIC TEST PROCEDURES IN THE APPLICABLE CIRCUIT BREAKER INSTRUCTION LEAFLET LISTED IN SECTION 6 Figure 12 Auxiliary Power Module 1 6 Auxiliary...

Page 17: ...In Multiples of Rating Plug Amperes Ir Ir Ir In I n Ir 3 3 Long Delay Time Setting There are eight 8 available Long Delay Time Settings as illustrated in Figure 14 ranging from 2 to 24 seconds These...

Page 18: ...ts please see Sections 1 1 3 DlScriminator High initial Current Release and 1 1 4 OVERRIDE Fixed Instantaneous for available fast acting high short circuit pro tection 3 8 Ground Fault Current Setting...

Page 19: ...LED SEE FIGURE 11 AND INSTRUCTIONS FOR TESTING YOUR SPECIFIC CIRCUIT BREAKER LISTED IN SECTION 6 PTM OR TRIP UNIT DAMAGE OR FAILURE CAN RESULT FROM ENERGIZING PTM AT MORE THAN 600 VOLTS VERIFY THAT NO...

Page 20: ...o perform all of its Protection Functions with out the external control power and without the display and commu nication functions available results of the tests could be confusing When performing a s...

Page 21: ...At least one of the various protection settings will be less than 6x In and the circuit breaker will trip the LED related to that function will light RED and the reason for TRIP code will appear in t...

Page 22: ...ee Figure 1 The address will increase by one unit each time you press the Black DEMAND RESET push button If you press and hold the Black DEMAND RESET push button the address will increase continuously...

Page 23: ...IBM Twisted Pair No 18 AWG See Section 5 5 Cut off Shield at last Device Do Not Ground Breaker with RMS 810 Trip Unit 3 View A Refer to circuit breaker connection diagrams referenced in Section 6 for...

Page 24: ...he appropriate data decode and display it in a useful manner Following an over current trip operation the sequence of coded data varies slightly The cause of trip and the value and phase or ground cur...

Page 25: ...ues Phase A Current IA kA Phase B Current IB kA Phase C Current IC kA X X X X X X X X X X X X X X X X X X 1 2 1 1 I I Ground Current IG kA Neutral Current ID kA n n n X X X I 1 2 1 1 View Power Energy...

Page 26: ...LOCATION BY THE COMMUNICATIONS NETWORK CAN CAUSE PERSONAL INJURY TO MAINTENANCE PERSONNEL WORKING IN THE IMMEDIATE VICINITY OF THE CIRCUIT BREAKER PROVIDE PERMISSIVE CONTROL SWITCHES OR OTHER MEANS L...

Page 27: ...32 870 Typical Time Current Characteristic Curves for Types DS II and DSL II Circuit Breakers SC 5619 Instantaneous I SC 5620 Long Delay and Short Delay LS SC 5621 Ground G 1A33600 Connection Diagram...

Page 28: ...he event that the feeder breaker Z2 would not clear the fault the main breaker Z1 will clear the fault in 0 5 s as above Fault 1 There are no interlocking signals The main breaker trip unit will initi...

Page 29: ...ote N As the current approached the overload condition prior to the overload trip operation the following Trip Unit indications would have been visible The HILD message would begin to flash in the win...

Page 30: ...30 Instruction Leaflet I L 29 888B Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Notes...

Page 31: ...31 Instruction Leaflet I L 29 888B Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Notes...

Page 32: ...etween the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contr...

Reviews: