background image

26

Instruction Leaflet 

I. L. 29-888B

Effective July 2011

 Instructions for Digitrip RMS 810 Trip Unit

 

 

eaton corporation

 www.eaton.com

5.7  System Power Factor (Remote)

The Digitrip RMS 810 can send the present value of the system 

power factor to a remote terminal even though system power fac-

tor is not available for local display in the Trip Unit window The range 

assumptions and accuracy for the system power factor function 

values are:
Range  - 

From -0 .5 (lagging) to +0 .5 (leading)

Assumes - 

Balanced three-phase load, per ANSI Std . C 12 .1

Current  - 

> 20% of Frame Rating for Series C® R-Frame or  

 

 

Type SPB circuit 

 

 

breakers .

Current  - 

> 20% of [Current] Sensor Rating for Type DS cir 

 

 

cuit breakers .

Accuracy - 

± 0 .02

5.8  Remote Closing and Tripping of Circuit Breakers

The Digitrip RMS 810 Trip Unit can respond to commands from the 

remote master computer to "TRIP" the circuit breaker remotely; 

and furthermore, if the circuit breaker has been equipped with the 

applicable optional electrical operator or spring release feature, 

the Digitrip RMS 810 Trip Unit can respond to commands from the 

remote master computer to "CLOSE" the circuit breaker remotely .  

The CLOSE command causes the "Communications Close" contact 

in the Power Relay Module to close (see wires CC1 and CC2 in 

Figure 2), making the circuit breaker's closing control circuit, and 

releasing it to close (see the connection diagram applicable for your 

circuit breaker listed in Section 6) .
When the Electrical Operator or Spring Release option is purchased 

for the circuit breaker, the Communications Close contact is wired 

into the close release circuit at the factory .  The TRIP command 

causes the Digitrip RMS 810 Trip Unit to operate the circuit breaker's 

trip release (see " 

 

 

" in Figure 2) .  The trip release remains locked-

out, so that the circuit breaker cannot be reclosed, until the Trip Unit 

is reset (see Section 5 .9) .  The Trip Unit displays "EXTT" in its window 

and sends back the "EXTT message over INCOM to the remote 

master computer .  (Note that the values of the currents through the 

circuit breaker will be "zero" when it is OPEN .)

WARNING

UNEXPECTED SIGNALS TO "CLOSE' OR "TRIP' A CIRCUIT BREAKER FROM 

A REMOTE LOCATION BY THE COMMUNICATIONS NETWORK CAN CAUSE 

PERSONAL INJURY TO MAINTENANCE PERSONNEL WORKING IN THE 

IMMEDIATE VICINITY OF THE CIRCUIT BREAKER.  PROVIDE PERMISSIVE 

CONTROL SWITCHES, OR OTHER MEANS, LOCALLY AT THE CIRCUIT 

BREAKER FOR MAINTENANCE PERSONNEL TO USE IN CONTROLLING 

REMOTE "CLOSE" OR "TRIP" SIGNALS.  FOR DETAILED INFORMATION 

CONCERNING THE BREAKER CONTROL CIRCUITS NECESSARY TO 

IMPLEMENT PERMISSIVE CONTROL LOCALLY, REFER TO THE CIRCUIT 

BREAKER CONNECTION DIAGRAMS LISTED IN SECTION 6.

5.9  Remote Resetting of the Trip Unit

NOTICE

BEFORE RESETTING TRIP UNIT, BE SURE TO: 

  • RECORD DISPLAY VALUES OF ALL PERTINENT PARAMETERS. 

  • NOTE WHICH CAUSE OF TRIP LEDS ARE LIGHTED "RED”. 

  • CORRECT THE CAUSE OF THE OVERCURRENT OR FAULT CONDITION  

     THAT CAUSED THE BREAKER TO TRIP. 

 

BECAUSE THE AUTOMATIC LOCKOUT-AFTER-TRIP FEATURE OF THE 

DIGITRIP RMS 810 TRIP UNIT MAINTAINS THE CIRCUIT BREAKER IN A 

"TRIP-FREE" CONDITION.  THE TRIP UNIT MUST BE RESET AFTER EACH 

TRIP OPERATION (WHETHER INITIATED BY OVER-CURRENT CONDITIONS 

OR BY REMOTE INCOM

®

 / IMPACC

®

 SIGNAL), BEFORE THE BREAKER CAN 

BE CLOSED AGAIN.  THE RESET CAN BE ACCOMPLISHED EITHER LOCALLY 

BY PRESSING AND RELEASING THE "TRIP RESET" PUSH BUTTON (SEE 

FIGURE 1), OR REMOTELY BY THE IMPACC

®

 SYSTEM.

Although the reset can be accomplished locally by pressing and 

releasing the "TRIP RESET push button (see Figure 1), it is some-

times inconvenient or untimely to go to the circuit breaker in order 

to reset the Trip Unit .  For such cases where the circuit breaker is 

far from the plant control room, the IMPACC

®

 system provides the 

User with a means for resetting the circuit breaker through the com-

munications network "Trip Unit Reset" command .  Executing the Trip 

Unit Reset command remotely from the master computer by the 

INCOM

®

 / lMPACC

®

 system is exactly equivalent to pressing and 

releasing the "Trip Reset" push-button on the front of the Trip Unit .
In addition to the Trip Unit Reset capability, the INCOM

®

 / IMPACC

®

 

communications capability of the Trip Unit provides the User with a 

means for resetting several parameter values stored in the Trip Unit's 

memory .  Using the proper commands, the User can view and reset 

the following trip event buffer parameters remotely: time of trip, val-

ues of phase and ground currents, number of electronically initiated 

trip operations, peak [power] demand, energy, and the cause of trip .

Summary of Contents for Cutler-Hammer Digitrip RMS 810

Page 1: ...persedes I L 29 888A 5 97 Instruction Leaflet I L 29 888B Instructions for Digitrip RMS 810 Trip Unit BCS Switchgear Inc Switchgear Circuit Breakers Parts Tech Support bcsswitchgear com 888 599 0486 N...

Page 2: ...7 No Instantaneous Current Setting 18 3 8 Ground Fault Current Setting 18 3 9 Ground Fault Time Delay Setting 19 4 Test Procedures 19 4 1 General 19 4 2 When To Test 19 4 3 Testing Provisions 20 4 4...

Page 3: ...lay Time Settings 18 Figure 17 Instantaneous Current Settings 18 Figure 18 Ground Fault Current Settings 18 Figure 19 Ground Fault Time Delay Settings 19 Figure 20 Integral Test Panel Lower Right Corn...

Page 4: ...uit breaker The Digitrip RMS 810 Trip Unit is designed for use in industrial circuit breaker environments where the ambient temperatures can range from 20 C to 85 C 4 F to 185 F and rarely exceed 70 t...

Page 5: ...in the LED RED and will continue to send a TRIP signal to LOCKOUT the circuit breaker until the Trip Unit is RESET The Digitrip RMS 810 Trip Unit can be RESET in two ways Either press and release the...

Page 6: ...l control power to operate its protection systems It operates from current signal levels and control power derived through current sensors inte grally mounted in the circuit breaker The Digitrip RMS 8...

Page 7: ...Current Setting Pick up Adj Time Delay Setting Opt I Squared T Curve Shape Opt Zone Interlocking Ground Fault Time Memory X X X X X X X X X X X X X X X 3 8 3 9 3 9 1 1 5 3 9 Trip Unit Over Temp TRIP X...

Page 8: ...Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Figure 3 Digitrip RMS 810 Type LI Figure 4 Digitrip RMS 810 Type LS Figure 5 Digitrip RMS 810 Type LSI F...

Page 9: ...e non adjustable release is pre set at eleven 11 times the installed rating plug current In The DlScriminator is enabled for approximate ly ten 10 cycles following the initial current flow through the...

Page 10: ...D TIME DELAY COORDINATION ONLY IS INTENDED THE ZONE INTERLOCKING TERMINALS MUST BE CONNECTED WITH JUMPER WIRES AS SPECIFIED ON THE CONNECTION DIAGRAMS FOR YOUR BREAKER SEE SECTION 6 SO THE TIME DELAY...

Page 11: ...Power and Energy Values 1 2 1 2 Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X X Energy Consumption MWh Reverse Energy Consumption X X X X X X X X X...

Page 12: ...will trip and the instantaneous override LED will light If breaker is open it will not close 1 3 ROM ERROR Nonfatal memory error Protection functions still operate but may be up to 12 out of tolerance...

Page 13: ...breaker positive flow of power If the power flows in the opposite direction i e bottom to top the value of power will not be displayed continuously Instead the power value in the display window will a...

Page 14: ...ttings without having to remove the circuit breaker from its enclosure For example if one expects a circuit to carry 600 A initially but then increase to 1400 A in the future one could initially insta...

Page 15: ...IP RELAY ALARMS MAY BE ERRATIC OR NONFUNCTIONAL IF WRONG VOLTAGE IS USED The relays operate when the Trip Unit detects the following condi tions as shown in Figure 2 Short Circuit Trip Alarm High Load...

Page 16: ...TESTS ON THE CIRCUIT BREAKER SEE ALSO THE SPECIFIC DIELECTRIC TEST PROCEDURES IN THE APPLICABLE CIRCUIT BREAKER INSTRUCTION LEAFLET LISTED IN SECTION 6 Figure 12 Auxiliary Power Module 1 6 Auxiliary...

Page 17: ...In Multiples of Rating Plug Amperes Ir Ir Ir In I n Ir 3 3 Long Delay Time Setting There are eight 8 available Long Delay Time Settings as illustrated in Figure 14 ranging from 2 to 24 seconds These...

Page 18: ...ts please see Sections 1 1 3 DlScriminator High initial Current Release and 1 1 4 OVERRIDE Fixed Instantaneous for available fast acting high short circuit pro tection 3 8 Ground Fault Current Setting...

Page 19: ...LED SEE FIGURE 11 AND INSTRUCTIONS FOR TESTING YOUR SPECIFIC CIRCUIT BREAKER LISTED IN SECTION 6 PTM OR TRIP UNIT DAMAGE OR FAILURE CAN RESULT FROM ENERGIZING PTM AT MORE THAN 600 VOLTS VERIFY THAT NO...

Page 20: ...o perform all of its Protection Functions with out the external control power and without the display and commu nication functions available results of the tests could be confusing When performing a s...

Page 21: ...At least one of the various protection settings will be less than 6x In and the circuit breaker will trip the LED related to that function will light RED and the reason for TRIP code will appear in t...

Page 22: ...ee Figure 1 The address will increase by one unit each time you press the Black DEMAND RESET push button If you press and hold the Black DEMAND RESET push button the address will increase continuously...

Page 23: ...IBM Twisted Pair No 18 AWG See Section 5 5 Cut off Shield at last Device Do Not Ground Breaker with RMS 810 Trip Unit 3 View A Refer to circuit breaker connection diagrams referenced in Section 6 for...

Page 24: ...he appropriate data decode and display it in a useful manner Following an over current trip operation the sequence of coded data varies slightly The cause of trip and the value and phase or ground cur...

Page 25: ...ues Phase A Current IA kA Phase B Current IB kA Phase C Current IC kA X X X X X X X X X X X X X X X X X X 1 2 1 1 I I Ground Current IG kA Neutral Current ID kA n n n X X X I 1 2 1 1 View Power Energy...

Page 26: ...LOCATION BY THE COMMUNICATIONS NETWORK CAN CAUSE PERSONAL INJURY TO MAINTENANCE PERSONNEL WORKING IN THE IMMEDIATE VICINITY OF THE CIRCUIT BREAKER PROVIDE PERMISSIVE CONTROL SWITCHES OR OTHER MEANS L...

Page 27: ...32 870 Typical Time Current Characteristic Curves for Types DS II and DSL II Circuit Breakers SC 5619 Instantaneous I SC 5620 Long Delay and Short Delay LS SC 5621 Ground G 1A33600 Connection Diagram...

Page 28: ...he event that the feeder breaker Z2 would not clear the fault the main breaker Z1 will clear the fault in 0 5 s as above Fault 1 There are no interlocking signals The main breaker trip unit will initi...

Page 29: ...ote N As the current approached the overload condition prior to the overload trip operation the following Trip Unit indications would have been visible The HILD message would begin to flash in the win...

Page 30: ...30 Instruction Leaflet I L 29 888B Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Notes...

Page 31: ...31 Instruction Leaflet I L 29 888B Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Notes...

Page 32: ...etween the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contr...

Reviews: