background image

4

Instruction Leaflet 

I. L. 29-888B

Effective July 2011

 Instructions for Digitrip RMS 810 Trip Unit

 

 

eaton corporation

 www.eaton.com

important Safety instructions

WARNING

DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON 

EQUIPMENT WHILE IT IS ENERGIZED.  DEATH OR SEVERE PERSONAL 

INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT.  

ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING 

WITH THE TASK, AND ALWAYS FOLLOW GENERALLY ACCEPTED 

SAFETY PROCEDURES.  EATON CORPORATION IS NOT LIABLE FOR THE 

MISAPPLICATION OR MISINSTALLATION OF ITS PRODUCTS. 

It is strongly urged that the User observe all recommendations, 

warnings and cautions relating to the safety of personnel and equip-

ment, as well as all general and local health and safety laws, codes, 

and procedures .
The recommendations and information contained herein are based 

on experience and judgment, but should not be considered to be 

all-inclusive or covering every application or circumstance which 

may arise .  If you have any questions or need further information 

or instructions, please contact your local representative, or the 

Customer Support Center for the type of circuit breaker you have .

1  General Description - Digitrip rMS 810  

     trip Unit

1.1  Basic Digitrip RMS 810 Trip Unit

The Digitrip RMS 810, illustrated in Figure 1, is a Trip Unit suitable 

for use in types DS and DSL Low-Voltage AC power circuit breakers 

and type SPB Systems Pow-R circuit breakers and Series C R-Frame 

molded case circuit breakers .  The Digitrip RMS 810 Trip Unit pro-

vides five basic functions:

Function 

Section

Protection 

1 .1 .2 – 1 .1 .5 and 3

Information 

1 .1 .1 and 1 .2

Monitors 

1 .2 .1

 

Current 

1 .2 .1 .1

 

Power and Energy 

1 .2 .1 .2

Testing 

4

Communications 

1 .4 and 5

Remote CLOSE / OPEN Control 

5 .8

Digitrip RMS 810 provides true RMS current sensing for proper cor-

relation with thermal characteristics of conductors and equipment . 

Interchangeable rating plugs are provided to establish the continuous 

current rating of each circuit breaker .  The Digitrip RMS 810 Trip Unit 

is designed for use in industrial circuit breaker environments where 

the ambient temperatures can range from -20°C to +85°C (-4°F to 

185°F) and rarely exceed 70 to 75°C (158 to 167°F)  .  If, however, 

temperatures in the neighborhood of the Trip Unit do exceed this 

range, the Trip Unit performance may be degraded .  In order to 

insure that the tripping function is not compromised due to an over-

temperature condition, the Digitrip RMS 810 microcomputer chip has 

a built-in over-temperature protection feature, factory set to trip the 

breaker if the chip temperature is excessive .  If over-temperature is 

the reason for the trip, the Long Delay Time LED will light "RED", and 

the word "TEMP" will appear in the display window .
The Trip Unit employs the Eaton custom designed integrated circuit 

microprocessor which includes a micro-computer to perform its 

numeric and logic functions .  The principle of operation is described 

by the block diagram shown in Figure 2 .
In the Digitrip RMS 810 Trip Unit, all required sensing and tripping 

power to operate its protection function is derived from the current 

sensors in the circuit breaker .  The secondary currents from these 

sensors provide the correct input information for the protector func-

tions, as well as tripping power, whenever the circuit breaker is 

carrying current .  These signals develop analog voltages across the 

appropriate sensing resistors including:

1 . 

Phase currents;

2 . 

Ground current or Neutral current (when supplied); and

3 . 

Rating plug .

 The resulting analog voltages are digitized by the custom designed 

integrated circuits .  The micro-computer, in cyclic fashion, repeatedly 

scans the voltage values across each sensing resistor and enters 

these values into its Random Access Memory (RAM) .  This data is 

used to calculate true RMS current values, which are then repeat-

edly compared with the protection function settings and other oper-

ating data stored in the memory .  The software program then deter-

mines whether to initiate protection functions, including tripping the 

breaker through the low energy trip device (Flux Transfer Shunt Trip 

or Direct Trip Actuator) in the circuit breaker .

Summary of Contents for Cutler-Hammer Digitrip RMS 810

Page 1: ...persedes I L 29 888A 5 97 Instruction Leaflet I L 29 888B Instructions for Digitrip RMS 810 Trip Unit BCS Switchgear Inc Switchgear Circuit Breakers Parts Tech Support bcsswitchgear com 888 599 0486 N...

Page 2: ...7 No Instantaneous Current Setting 18 3 8 Ground Fault Current Setting 18 3 9 Ground Fault Time Delay Setting 19 4 Test Procedures 19 4 1 General 19 4 2 When To Test 19 4 3 Testing Provisions 20 4 4...

Page 3: ...lay Time Settings 18 Figure 17 Instantaneous Current Settings 18 Figure 18 Ground Fault Current Settings 18 Figure 19 Ground Fault Time Delay Settings 19 Figure 20 Integral Test Panel Lower Right Corn...

Page 4: ...uit breaker The Digitrip RMS 810 Trip Unit is designed for use in industrial circuit breaker environments where the ambient temperatures can range from 20 C to 85 C 4 F to 185 F and rarely exceed 70 t...

Page 5: ...in the LED RED and will continue to send a TRIP signal to LOCKOUT the circuit breaker until the Trip Unit is RESET The Digitrip RMS 810 Trip Unit can be RESET in two ways Either press and release the...

Page 6: ...l control power to operate its protection systems It operates from current signal levels and control power derived through current sensors inte grally mounted in the circuit breaker The Digitrip RMS 8...

Page 7: ...Current Setting Pick up Adj Time Delay Setting Opt I Squared T Curve Shape Opt Zone Interlocking Ground Fault Time Memory X X X X X X X X X X X X X X X 3 8 3 9 3 9 1 1 5 3 9 Trip Unit Over Temp TRIP X...

Page 8: ...Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Figure 3 Digitrip RMS 810 Type LI Figure 4 Digitrip RMS 810 Type LS Figure 5 Digitrip RMS 810 Type LSI F...

Page 9: ...e non adjustable release is pre set at eleven 11 times the installed rating plug current In The DlScriminator is enabled for approximate ly ten 10 cycles following the initial current flow through the...

Page 10: ...D TIME DELAY COORDINATION ONLY IS INTENDED THE ZONE INTERLOCKING TERMINALS MUST BE CONNECTED WITH JUMPER WIRES AS SPECIFIED ON THE CONNECTION DIAGRAMS FOR YOUR BREAKER SEE SECTION 6 SO THE TIME DELAY...

Page 11: ...Power and Energy Values 1 2 1 2 Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X X Energy Consumption MWh Reverse Energy Consumption X X X X X X X X X...

Page 12: ...will trip and the instantaneous override LED will light If breaker is open it will not close 1 3 ROM ERROR Nonfatal memory error Protection functions still operate but may be up to 12 out of tolerance...

Page 13: ...breaker positive flow of power If the power flows in the opposite direction i e bottom to top the value of power will not be displayed continuously Instead the power value in the display window will a...

Page 14: ...ttings without having to remove the circuit breaker from its enclosure For example if one expects a circuit to carry 600 A initially but then increase to 1400 A in the future one could initially insta...

Page 15: ...IP RELAY ALARMS MAY BE ERRATIC OR NONFUNCTIONAL IF WRONG VOLTAGE IS USED The relays operate when the Trip Unit detects the following condi tions as shown in Figure 2 Short Circuit Trip Alarm High Load...

Page 16: ...TESTS ON THE CIRCUIT BREAKER SEE ALSO THE SPECIFIC DIELECTRIC TEST PROCEDURES IN THE APPLICABLE CIRCUIT BREAKER INSTRUCTION LEAFLET LISTED IN SECTION 6 Figure 12 Auxiliary Power Module 1 6 Auxiliary...

Page 17: ...In Multiples of Rating Plug Amperes Ir Ir Ir In I n Ir 3 3 Long Delay Time Setting There are eight 8 available Long Delay Time Settings as illustrated in Figure 14 ranging from 2 to 24 seconds These...

Page 18: ...ts please see Sections 1 1 3 DlScriminator High initial Current Release and 1 1 4 OVERRIDE Fixed Instantaneous for available fast acting high short circuit pro tection 3 8 Ground Fault Current Setting...

Page 19: ...LED SEE FIGURE 11 AND INSTRUCTIONS FOR TESTING YOUR SPECIFIC CIRCUIT BREAKER LISTED IN SECTION 6 PTM OR TRIP UNIT DAMAGE OR FAILURE CAN RESULT FROM ENERGIZING PTM AT MORE THAN 600 VOLTS VERIFY THAT NO...

Page 20: ...o perform all of its Protection Functions with out the external control power and without the display and commu nication functions available results of the tests could be confusing When performing a s...

Page 21: ...At least one of the various protection settings will be less than 6x In and the circuit breaker will trip the LED related to that function will light RED and the reason for TRIP code will appear in t...

Page 22: ...ee Figure 1 The address will increase by one unit each time you press the Black DEMAND RESET push button If you press and hold the Black DEMAND RESET push button the address will increase continuously...

Page 23: ...IBM Twisted Pair No 18 AWG See Section 5 5 Cut off Shield at last Device Do Not Ground Breaker with RMS 810 Trip Unit 3 View A Refer to circuit breaker connection diagrams referenced in Section 6 for...

Page 24: ...he appropriate data decode and display it in a useful manner Following an over current trip operation the sequence of coded data varies slightly The cause of trip and the value and phase or ground cur...

Page 25: ...ues Phase A Current IA kA Phase B Current IB kA Phase C Current IC kA X X X X X X X X X X X X X X X X X X 1 2 1 1 I I Ground Current IG kA Neutral Current ID kA n n n X X X I 1 2 1 1 View Power Energy...

Page 26: ...LOCATION BY THE COMMUNICATIONS NETWORK CAN CAUSE PERSONAL INJURY TO MAINTENANCE PERSONNEL WORKING IN THE IMMEDIATE VICINITY OF THE CIRCUIT BREAKER PROVIDE PERMISSIVE CONTROL SWITCHES OR OTHER MEANS L...

Page 27: ...32 870 Typical Time Current Characteristic Curves for Types DS II and DSL II Circuit Breakers SC 5619 Instantaneous I SC 5620 Long Delay and Short Delay LS SC 5621 Ground G 1A33600 Connection Diagram...

Page 28: ...he event that the feeder breaker Z2 would not clear the fault the main breaker Z1 will clear the fault in 0 5 s as above Fault 1 There are no interlocking signals The main breaker trip unit will initi...

Page 29: ...ote N As the current approached the overload condition prior to the overload trip operation the following Trip Unit indications would have been visible The HILD message would begin to flash in the win...

Page 30: ...30 Instruction Leaflet I L 29 888B Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Notes...

Page 31: ...31 Instruction Leaflet I L 29 888B Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Notes...

Page 32: ...etween the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contr...

Reviews: