7
GB
1
Technical data
1.1 GHG 261 ... generally
Dimensions in mm
GHG 261 ..
X = Fixing dimensions
Explosion-protected safety switch, main switch,
load disconnect switch 10 A, GHG 261
1.2 GHG 261 .. Main-switch / load disconnect switch
Enclosure:
Switch symbol:
Switching capacity acc. to IEC/EN 60947-3:
AC 3
1.3 GHG 261 .. Safety switch; maintenance-/repair -switch
Enclosure:
Switch symbol:
Switching capacity acc. to IEC/EN 60947-3:
AC 3
Classification acc to IEC/EN 62626-1:
Klasse 1
Emergency - switch acc. to IEC/EN 60204-1:
Emergency - switch - version
Rated voltage:
500 V, 50/60 Hz
Rated current:
10 A
Perm. short circuit back-up fuse:
16 A gG up to 500 V
Switching capacity:
AC 15
230 V / 6.0 A
400 V / 6.0 A
DC 13
24 V / 6.0 A
230 V / 0.4 A
Design with gold-tipped contact:
max. 400 mA
Terminals:
2 x 0.5 - 2.5 mm²
1.4 Auxiliary contact:
EU-Type Examination Certificate:
BVS 16 ATEX E 079
Marking acc. to 2014/34/EU
and standard of series EN 60079: gas
II 2 G Ex eb db IIC T6 Gb
dust
II 2 D Ex tb IIIC T80 °C Db
IECEx Certificate of Conformity:
IECEx BVS 16.0045
Category of application
standard of series IEC 60079:
gas
Ex eb db IIC T6 Gb
dust
Ex tb IIIC T80 °C Db
Rated voltage:
500 V, 50/60 Hz
Rated current:
10 A
Perm. short circuit back-up fuse:
up to U
N
400 V up to U
N
500 V
20 A gG
16 A gG
Switching capacity AC 3:
10 A
10 A
Perm. ambient temperature:
(
Deviating temperatures possible on request)
-54 °C to +55 °C
Perm. storage temperature in original packing:
-54 °C to +55 °C
Degree of protection. to EN/IEC 60529:
IP 66 (standard version)
Insulation class acc. to EN/IEC 61140:
II - plastic terminal boxes fulfil this requirement
I - with metal flange / metal cable glands
Cabel entry:
suitable cables and test torques of the
pressure screw
M20
M25
M32
Seal 1+2+3
(Ø mm / Nm)
1
2
3
min.
max.
(1)
5.5 / 1.5
7.0 / 1.0
8.0 / 1.5
10.0 / 2.0
Seal 1+2
(Ø mm / Nm)
1
2
3
min.
max.
(1)
7.0 / 1.5
9.0 / 1.4
10.0 / 2.3
13.0 / 2.6
14.0 / 3.0
17.0 / 4.0
Seal 1
(Ø mm / Nm)
1
2
3
min.
max.
(1)
9.5 / 1.0
13.0 / 1.7
13.5 / 1.3
17.5 / 2.3
17.5 / 1.5
21.0 / 1.3
Test torque for screw in thread cable entry:
2.7 Nm
3.0 Nm
5.0 Nm
Terminals:
2 x 1.5 - 2.5 mm²
Cover screws:
2.50 Nm
Terminals main contacts:
2.00 Nm
Terminals auxiliary contact:
2.00 Nm
(1)
The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can
vary by using cables with different manufacturing tolerances and material properties. Please use a suitable
combination of seals in the intermediate area, so that the cap nut can be tightened in future maintenance
work on the cable entry.