 Fig. 1

Safety instructions

Target group: 
For skilled electricians and suitable qualified, instructed 
personnel in accordance with national legislation, including 
the relevant standards and, where applicable, in acc. with  

IEC/EN 60079-14 on electrical apparatus for explosive atmospheres.

The switches GHG 261 are not suited for use in Zone 0 and Zone 20.

The temperature class and type of protection stated on the appara-
tus shall be observed. 

The requirements of the IEC/EN 60079-31  regarding excessive dust 
deposits and temperature to be considered from the user.

To ensure adherence to the temperature class stated on the type 
label of the apparatus, the permissible ambient temperature, the 
rated terminal cross section and the self heating of the apparatus 
that is mainly due to the power dissipation shall be taken into 
account (test criterion for the self heating is an overload of 10%).

They shall be used for their intended purpose and shall be in a 
perfect and clean state.

Prior to being put into  operation, the control units shall be checked 
in accordance with the instructions as per section 6.

The covers of the safety switches GHG 261 can only be removed 
when the switch is in the “ON” position.

The national safety rules and regulations for the prevention of 
accidents, as well as the safety instructions included in these 
operating instructions, that, like this text, are set in italics, shall be 
observed!

Conformity with standards

The switches GHG 261are conform to the standards specified in the  
EU-Declaration of conformity, enclosed separately.

References to standards and directives in this manual always refer to the 
latest version. additional supplements (for example, date information) 
must be observed.

Field of application

The switches GHG 261 are intended for use in potentially explosive 
atmospheres in Zones 1 and 2 as well as in Zones 21 and 22 in accord-
ance with IEC/EN 60079-10-1 and IEC/EN 60079-10-2. 

The enclosure materials used, including any external metal parts, are high 
quality materials that ensure a corrosion resistance and resistance to 
chemical substances according to the requirements for use in a ”normal 
industrial atmosphere”:

– impact resistant polyamide 
– special steel AISI 316 L.

For use in an extremely aggressive atmosphere, please contact your 
Cooper Crouse-Hinds agent for additional information on the chemical 
stability of the plastics used.

 5  Application / Properties

Due to the AC 3 motor switching capacity of the switches GHG 261, 
reliable isolation (switching) is also possible during operation.

The switches GHG 261 fulfil the isolating properties according to  
IEC/EN 60947-3.

In addition to this, the switches GHG 261 are so designed, that they also 
switch off the drive, e.g. via the contactor that precedes the auxiliary 
contact. In relation to the main contacts, this auxiliary contact is lagging 
while making and leading while breaking.

Versions with gold-tipped auxiliary contacts are suited for switching 
extra-low voltage circuits. Special attention shall be paid to the maximum 
current load (see technical data). The contact chamber of the gold-tipped 
version is marked with the letter ”G” or colour-coded.

Due to the mechanical design of the switches GHG 261, compulsory 
opening of the contacts is possible.

To prevent unauthorized switching, the switches GHG 261 can be locked 
in the ”OFF“ position by means of 3 padlocks, see fig. 1, (shackle 
diameter of the padlocks up to 4 to 6 mm).

See technical data, for the temperature class, explosion group and 
permissible ambient temperature.

The data according to sections 3 and 4 shall be taken into account during 
use.

 Applications other than those described are not permissible 

without a written declara-tion of consent from Messrs. COOPER 
Crouse-Hinds.

During operation the instructions stated in section 7 of the operating 
instructions shall be observed.

The sole responsibility with respect to the suitability and proper use 
of the control switches with regard to the basic requirements of 
these instructions (see technical data) lies with the operator.

GB

Explosion-protected safety switch, main switch,  
load disconnect switch 10 A, GHG 261

Summary of Contents for Crouse-hinds series

Page 1: ...EN IEC 62626 1 Explosionsgesch tzter Sicherheitsschalter Hauptschalter Lastrennschalter 10 A GHG 261 Explosion protected safety switch main switch load disconnect switch 10 A GHG 261 Interrupteur de s...

Page 2: ...tions 8 3 Conformity with standards 8 4 Field of application 8 5 Application Properties 8 5 1 GHG 261 Main switch load disconnect switch 9 5 2 GHG 261 Safety switch maintenance repair switch 9 6 Insta...

Page 3: ...h EN IEC 61140 II wird von den Ger ten erf llt I mit Metallflansch Metallleitungseinf hrungen Kabel und Leitungseinf hrung KLE geeignete Leitungen und Pr fdrehmomente der Druckschraube M20 M25 M32 Dic...

Page 4: ...net Die eingesetzten Geh usematerialien einschlie lich der au enliegenden Metallteile bestehen aus hochwertigen Werkstoffen die einen anwen dungsgerechten Korrosionsschutz und Chemikalienresistenz in...

Page 5: ...6 2 ffnen des Ger tes Elektrischer Anschluss Der elektrische Anschluss des Betriebsmittels darf nur durch Fachpersonal erfolgen Vor ffnen der Ger te ist die Spannungsfrei heit sicherzustellen bzw sin...

Page 6: ...ten Bei berm igem Anziehen kann die Schutzart beeintr chtigt werden 6 6 Inbetriebnahme Vor Inbetriebnahme des Betriebsmittels sind die in den einzelnen nationalen Bestimmungen genannten Pr fungen durc...

Page 7: ...voltage 500 V 50 60 Hz Rated current 10 A Perm short circuit back up fuse up to UN 400 V up to UN 500 V 20 A gG 16 A gG Switching capacity AC 3 10 A 10 A Perm ambient temperature Deviating temperatur...

Page 8: ...ding any external metal parts are high quality materials that ensure a corrosion resistance and resistance to chemical substances according to the requirements for use in a normal industrial atmospher...

Page 9: ...ee the respective mounting instructions 6 2 Opening apparatus Electrical connection The electrical connection of the apparatus may only be carried out by specialists IEC EN 60079 14 Before opening the...

Page 10: ...impair the degree of protection 6 6 Putting into operation Before putting the apparatus into operation the tests specified in the individual national regulations shall be performed In addition to this...

Page 11: ...Hz Courant nominal 10 A Fusible de court circuit adm plac en amont jusqu UN 400 V jusqu UN 500 V 20 A gG 16 A gG Puissance de coupure AC 3 10 A 10 A Temp rature ambiante admissible D autres temp ratu...

Page 12: ...ne protection appropri e contre la corrosion et une r sistance aux agents chimiques en atmosph re industrielle normale ont t employ es polyamide antichoc acier sp cial AISI 316 L En cas d utilisation...

Page 13: ...2 Ouverture de l appareil Raccordement lectrique Le raccordement lectrique de l appareil ne doit se faire que par un personnel qualifi CEI EN 60079 14 Avant ouverture de l enveloppe mettre l appareil...

Page 14: ...ques techniques Un serrage excessif des vis peut endommager l appareil 6 6 Mise en service Avant la mise en service de l appareil les v rifications sp cifi es dans les r glements nationaux individuels...

Page 15: ...Notizen Notes Remarques...

Page 16: ...er Crouse Hinds CEAG estas instrucciones de servicio en otro idioma de la Union Europea EST Seda kasutusjuhendit oma riigikeeles v ite k sida oma riigis asuvast asjaomasest Cooper Crouse Hindsi CEAG e...

Reviews: