76
Technical Data
PR202-50-502-22
Effective June 2017
CF2000 System
EATON
www.eaton.com
Micro Zone Monitor Wiring MIU872
To install the device
1.
Fit the box in position using the mounting details below .
2.
Connect the unit according to the diagram in Figure 55 .
3.
Recommended Cable Type: FIRETUF, FP200, MICC .
ote:
N
No addressing of the interface is required . See control panel
operation for details . There are no serviceable parts so no
maintenance procedures apply .
Figure 55. Standard connections MIU872
1.
This unit can only be used with Cooper FXN520 detector base
and compatible .
2.
Only connect cable screen to its adjacent earth terminal .
3.
The end of line resistor provided must always be fitted, even if
the spur is unused .
4.
Maximum spur length - See BS5839 Pt1:2001 for Zone
Coverage .
5.
Maximum number of call points allowed is unlimited .
6.
Detector zone end of line device is EOLM-1 (supplied) .