Fixing Details
Read all the installation instructions before commencing with the
installation . The installation of this panel must be carried out by a
suitably qualified /trained person .
The installation must comply with IEE wiring regulations and with
BS5839 part 1 2002
The electronic components within the fire panel are Static
Sensitive . Do not touch the electronics directly .
Mounting the Backbox
The CF2000 can be flush mount or surface mounted .
1 . For Surface Mount; drill four holes and fix the backbox to
the wall .
2 . For Flush Mount the backbox requires a hole 310mm x
355mm with a depth of 117mm .
Figure 2 shows the back box dimensions .
Figure 2. Back Box dimensions
Installing Cabling
Once the backbox is mounted the next stage is to install the
power and loop cables and fit the glands .