63
Technical Data
PR202-50-502-22
Effective June 2017
CF2000 System
EATON
www.eaton.com
Detector Base Wiring CAB300
Supply Voltage
18 - 30V DC
Cable Size
0 .5 - 2 .5mm²
Recommended cable types FIRETUF, FP200 or MICC
Mounting Hole Centres
50 - 80mm
Wiring Hints
1.
Each terminal is suitable for clamping up to 2 wires
2.
Clamping of 2 wires of very different diameters under one
screw is not recommended .
3.
Suitable for mounting to mounting boxes with 50-80mm fixing
centres .
General
If difficulty is experienced when mounting the sensor, this may be
due to the following:
1.
Wiring causing an obstruction - move or shorten wires .
2.
Although the base is tolerant to uneven mounting surfaces,
a very uneven surface may cause the base to deform when
the mounting screws are tightened down - loosen screws to
reduce this or slide base to a flat position .
WARNING
DO NOT USE HIGH VOLTAGE TESTERS WHEN SENSORS OR
CONTROL PANEL ARE CONNECTED TO THE SYSTEM
Figure 42. Wiring Diagram for CAB300 Sensor Base