19
Technical Data
PR202-50-502-22
Effective June 2017
CF2000 System
EATON
www.eaton.com
Technical Specification (continued)
Outputs
Conventional sounder circuits
Number of sounder circuits
4
Total Sounder Load
1 .0A (FH1204)
Maximum Sounder Circuit Load
800mA
Sounder Circuit Fuses (F1/2/3/4)
1 .6A (Quick Blow)
End of line resistor
6k8
Fire Routing Equipment
Max Load
60mA
Fused (PTC2)
100mA polyswitch
End of Line resistor
6k8
Fire Protecting Equipment
Max Load
60mA
Fused (PTC4)
100mA polyswitch
End of Line resistor
6k8
Fault Routing equipment
Max Load
30mA
Fused (PTC1)
100mA polyswitch
End of Line resistor
6k8
Auxiliary Relays
The auxiliary relays provide fused volt free change over contacts . These contacts are not monitored .
Max Load
24V 1A
Fuse (PTC5)
1 .1A polyswitch
Auxiliary 24V Supply
Nominal Voltage
24V ±10%
Fuse (PTC3)
300 mA polyswitch
Maximum current
30 mA
This output is not to be used for Fire protecting equipment or Fire alarm routing Equipment
Any power taken from the alarm system will affect the standby duration
RS485 Port (Mimic Repeater)
This is a serial output port for driving CF2000 Repeater panels, mimics etc .
This output is short circuit protected
Max Cable Length
2 Km
Min Recommended cable size
1 mm² (Screened)
Mechanical Specification
Weight including batteries
10 .6 Kg
Weight excluding batteries
5 .3 Kg
Dimensions (Standard batteries)
400 mm (L) x 320 mm (H) x 170 mm (D)
Type of Material (backbox)
Mild Steel (Powder Coated)
Type of Material (facia)
PC/ABS
Flammability Rating
UL 94 V0
Total Number of knockouts
24
Diameter of knockout
20 mm
CAUTION
TERMINAL BLOCKS: DO NOT USE EXCESSIVE FORCE WHEN
TIGHTENING THE SCREWS ON THE TERMINAL BLOCK