8.2.
Tests and environmental conditions
Disturbance
tests
Test
Standard & Test class / level
Test value
Emission
EN 61000-6-4
- Conducted
EN 55011, class A
0.01 - 30 MHz
- Emitted
EN 55011, class A
30 - 1 000 MHz
Immunity
EN 61000-6-2 / IEC 60255-26
- 1MHz damped IEC 60255-22-1
±2.5kVp CM, ±1kVp DM
oscillatory wave
- Static
EN 61000-4-2 class IV /
8 kV contact, 15 kV air
discharge (ESD) IEC 60255-22-2
- Fast transients EN 61000-4-4 class IV /
±4 kV, 5/50 ns, 5 kHz
(EFT)
IEC 60255-22-4 class A
- Surge
EN 61000-4-5 class III /
2 kV, 1.2/50
μ
s, CM
IEC
60255-22-5
1
kV,
1.2/50
μ
s, DM
- Conducted
EN 61000-4-6 class III /
0.15 - 80 MHz, 10 Vemf
HF fi eld
IEC 60255-22-6
- Emitted
EN 61000-4-3 class III /
80 - 2700 MHz, 10 V/m
HF fi eld
IEC 60255-22-3
- Voltage
EN 61000-4-29 /
30%/1s, 60%/0.1s, 100%/0.05s
interruptions
IEC 60255-11
- Voltage
EN 61000-4-17 / IEC 60255-11
12% of operating voltage (DC) / 10min
alternative
component
- Voltage dips
EN 61000-4-11
30%/10ms, 100%/10ms
and
short
60%/100ms
interruptions >95%/5000ms
- Power-
EN 61000-4-8
300A/m (continuous), 1000A/m / 1-3s
frequency
magnetic fi eld
- Pulse
EN 61000-4-9
1000A/m, 1.2/50
μ
s
magnetic fi eld
8.2.1. Electrical safety tests
Test
Standard & Test class / level
Test value
- Impulse voltage EN 60255-5, class III
5 kV, 1.2/50
μ
s, 0.5 J
withstand
- Dielectric test
EN 60255-5, class III
2 kV, 50 Hz
- Insulation EN
60255-5
resistance
- Protective
EN 60255-27
bonding
resistance
- Power supply
IEC 60255-1
burden
Summary of Contents for ARCON 2.0 Series
Page 51: ...51 7 6 Block diagram 7 6 1 ARC EM 2 0 Figure Connections of ARC EM 2 0...
Page 54: ...54 7 6 4 ARC EL3 2 0 7 6 5 ARC EC1 2 0...
Page 64: ...64 9 Construction 9 1 Dimensional drawings 9 1 1 ARC EM 2 0 panel and semi flush mounting...
Page 65: ...65 9 1 2 ARC EP10 2 2 0 din rail mounting...
Page 66: ...9 1 3 ARC EP10 2 0 din rail mounting 66...
Page 67: ...67 9 1 4 ARC EL3 2 0 din rail mounting...
Page 68: ...68 9 1 5 ARC EC1 2 0 din rail mounting...
Page 69: ...69 9 1 6 Fiber sensor mounting r min 50 mm...
Page 70: ...70 9 1 7 Point sensor mounting...
Page 82: ...82 10 Application examples 10 1 Applications 10 1 1 With a main busbar system...
Page 83: ...83 10 1 2 With two main busbar systems...
Page 84: ...84 10 1 3 With two main busbar systems and additional zone selection 4 zones...
Page 85: ...85...