58
8.1.4. Trip contacts
ARC-EM/2.0
Number of contacts
4 closing contacts (relays T1-T4)
Rated voltage
250 V ac/dc
Continuous withstand capacity
5 A
Make and carry for 0.5s
30 A
Make and carry for 3s
15 A
Breaking capacity, dc(L/R=40 ms)
At 48 V dc:
1 A
At 110 V dc:
0.44 A
At 220 V dc:
0.22 A
Relay
material
AgNi
90/10
Terminal:
Maximum cross-section area of wire:
2.5
mm²
(13-14
AWG)
- Phoenix MVSTBW or similar
ARC-EP10-2/2.0, ARC-EP10/2.0, ARC-EL3/2.0, ARC-EC1/2.0
Number of contacts
1 closing contact (relay T1)
for ARC-EP10/2.0, ARC-EL3/2.0,
ARC-EC1/2.0
Number of contacts
3 closing contacts (relay T1)
for ARC-EP10-2/2.0
Rated voltage
250 V ac/dc
Continuous withstand capacity
5 A
Make and carry for 0.5s
30 A
Make and carry for 3s
15 A
Breaking capacity, dc(L/R=40 ms)
At 48 V dc:
1 A
At 110 V dc:
0.44 A
At 220 V dc:
0.22 A
Relay
material
AgNi
90/10
Terminal:
Maximum cross-section area of wire
2.5
mm²
(13-14
AWG)
- Phoenix MVSTBW or similar
Summary of Contents for ARCON 2.0 Series
Page 51: ...51 7 6 Block diagram 7 6 1 ARC EM 2 0 Figure Connections of ARC EM 2 0...
Page 54: ...54 7 6 4 ARC EL3 2 0 7 6 5 ARC EC1 2 0...
Page 64: ...64 9 Construction 9 1 Dimensional drawings 9 1 1 ARC EM 2 0 panel and semi flush mounting...
Page 65: ...65 9 1 2 ARC EP10 2 2 0 din rail mounting...
Page 66: ...9 1 3 ARC EP10 2 0 din rail mounting 66...
Page 67: ...67 9 1 4 ARC EL3 2 0 din rail mounting...
Page 68: ...68 9 1 5 ARC EC1 2 0 din rail mounting...
Page 69: ...69 9 1 6 Fiber sensor mounting r min 50 mm...
Page 70: ...70 9 1 7 Point sensor mounting...
Page 82: ...82 10 Application examples 10 1 Applications 10 1 1 With a main busbar system...
Page 83: ...83 10 1 2 With two main busbar systems...
Page 84: ...84 10 1 3 With two main busbar systems and additional zone selection 4 zones...
Page 85: ...85...