50
7.5. Output
relays
7.5.1. ARC-EM/2.0
Connect the circuit breaker’s trip circuits to the following terminals (a maximum of four sepa-
rate trip outputs in two separate groups):
TRIP1:
X1-7, X1-8
(fast, group 1)
TRIP2:
X1-9, X1-10
(fast/CBFP, group 1)
TRIP3:
X1-11, X1-12
(fast, group 2)
TRIP4:
X1-13, X1-14
(fast/CBFP, group 2)
Connect the self-supervision alarm output to an IF change-over contact, either terminals X1-
17, X1-18 (normally open) or X1-19, X1-20 (normally closed).
During normal system operation (no internal fault) and with the auxiliary power supply con-
nected, the terminal X1-17, X1-18 are closed and X1-19, X1-20 are open.
Connect the trip alarm output to the closing terminals X1-15, X1-16.
7.5.2. ARC-EP10/2.0, ARC-EL3/2.0 and ARC-EC1/2.0
Connect the circuit breaker’s trip circuit to the following terminals:
TRIP1:
X2-15,
X2-16
(fast)
The output trip relay of the arc I/O units (ARC-EP10/2.0 and ARC-EL3/2.0) operates during
faults in its own zone. In the current I/O unit (ARC-EC1/2.0), select the protection zone con-
trolling the I/O unit using the programming switches.
7.5.3. ARC-EP10-2/2.0
Connect each output relay to corresponding breaker.
Sensor channel 1 controls Trip output 1 (X2-15, X2-16)
Sensor channel 2 controls Trip output 2 (X2-11, X2-12)
Sensor channel 3 controls Trip output 3 (X2-8, X2-9)
Summary of Contents for ARCON 2.0 Series
Page 51: ...51 7 6 Block diagram 7 6 1 ARC EM 2 0 Figure Connections of ARC EM 2 0...
Page 54: ...54 7 6 4 ARC EL3 2 0 7 6 5 ARC EC1 2 0...
Page 64: ...64 9 Construction 9 1 Dimensional drawings 9 1 1 ARC EM 2 0 panel and semi flush mounting...
Page 65: ...65 9 1 2 ARC EP10 2 2 0 din rail mounting...
Page 66: ...9 1 3 ARC EP10 2 0 din rail mounting 66...
Page 67: ...67 9 1 4 ARC EL3 2 0 din rail mounting...
Page 68: ...68 9 1 5 ARC EC1 2 0 din rail mounting...
Page 69: ...69 9 1 6 Fiber sensor mounting r min 50 mm...
Page 70: ...70 9 1 7 Point sensor mounting...
Page 82: ...82 10 Application examples 10 1 Applications 10 1 1 With a main busbar system...
Page 83: ...83 10 1 2 With two main busbar systems...
Page 84: ...84 10 1 3 With two main busbar systems and additional zone selection 4 zones...
Page 85: ...85...