59
8.1.5. Alarm contacts
ARC-EM/2.0
Number of contacts
2 normally open contacts
(relay
A1&SF*)
1
normally
closed
contact
(SF*)
Rated voltage
250 V ac/dc
Continuous withstand capacity
5 A
Make and carry for 0.5s
10 A
Make and carry for 3s
8 A
Breaking capacity, dc(L/R=40 ms)
At 48 V dc:
1 A
At 110 V dc:
0.25 A
At 220 V dc:
0.05 A
Relay
material
AgNi
90/10
Terminal:
Maximum cross-section area of wire
- Phoenix MVSTBW or similar
2.5 mm² (13-14 AWG)
*) Relay A1 = Trip Alarm
Relay SF = Self-supervision
8.1.6. Communication bus interface
Number of ports
2 in the back plate (ARC-EM/2.0)
2 in the front panel (I/O units)
Electrical connection
RJ 45
Max. number of used units
16 I/O units
3
master
units
Auxiliary voltage supply to I/O units
Floating 24 V dc
Communication
RS485 (15 kV) information / self-supervision
Light/current signal
4 arc protection zones
1
overcurrent
zone
8.1.7. Local serial communication port
ARC-EM/2.0
Number of ports
1 pc. in front panel
Electrical connection
RS 232
Data transfer rate
9600 kb/s (software update)
Summary of Contents for ARCON 2.0 Series
Page 51: ...51 7 6 Block diagram 7 6 1 ARC EM 2 0 Figure Connections of ARC EM 2 0...
Page 54: ...54 7 6 4 ARC EL3 2 0 7 6 5 ARC EC1 2 0...
Page 64: ...64 9 Construction 9 1 Dimensional drawings 9 1 1 ARC EM 2 0 panel and semi flush mounting...
Page 65: ...65 9 1 2 ARC EP10 2 2 0 din rail mounting...
Page 66: ...9 1 3 ARC EP10 2 0 din rail mounting 66...
Page 67: ...67 9 1 4 ARC EL3 2 0 din rail mounting...
Page 68: ...68 9 1 5 ARC EC1 2 0 din rail mounting...
Page 69: ...69 9 1 6 Fiber sensor mounting r min 50 mm...
Page 70: ...70 9 1 7 Point sensor mounting...
Page 82: ...82 10 Application examples 10 1 Applications 10 1 1 With a main busbar system...
Page 83: ...83 10 1 2 With two main busbar systems...
Page 84: ...84 10 1 3 With two main busbar systems and additional zone selection 4 zones...
Page 85: ...85...