80
9.2.5. Multiple master connection via BI/O bus interface
In applications with multiple master units the master units can be interconnected via BI/O
(binary input) bus interface. In this case, each part of the system can control four protection
zones per its own system communication bus. Both, arc and overcurrent information is trans-
ferred between the master units but without address information.
The following BI/O connections are included in the standard scope of delivery:
La> in
X3-8
Arc input, tripping group 1
Lb> in
X3-9
Arc input, tripping group 2
I> in/out
X3-10
Overcurrent input/output
La> out
X3-11
Arc output, tripping group 1
Lb> out
X3-12
Arc output, tripping group 2
GND
X3-13, X3-14
Grounding for all BI/O signals
To obtain transfer of arc information between master units:
• Connect the systems using the BI/O terminals X3-8, 9, 11 or 12 (+).
• Connect both terminals X3-13 (GND).
To obtain transfer of overcurrent information between master units:
• Connect the systems using the BI/O terminals X3-10 (+).
• Connect both terminals X3-14 (GND).
NOTE! Note the polarity of the cables.
NOTE! The system‘s I/O units should be connected to the respective master unit in the same zone.
The fi gure below shows an example connection where arc and current information is transfer-
red in both directions between master units.
X3
X3
La>in
BI/O
La>out
GND
GND
I
/out
>in
I
/out
>in
{
Master unit 1
Master unit 2
Summary of Contents for ARCON 2.0 Series
Page 51: ...51 7 6 Block diagram 7 6 1 ARC EM 2 0 Figure Connections of ARC EM 2 0...
Page 54: ...54 7 6 4 ARC EL3 2 0 7 6 5 ARC EC1 2 0...
Page 64: ...64 9 Construction 9 1 Dimensional drawings 9 1 1 ARC EM 2 0 panel and semi flush mounting...
Page 65: ...65 9 1 2 ARC EP10 2 2 0 din rail mounting...
Page 66: ...9 1 3 ARC EP10 2 0 din rail mounting 66...
Page 67: ...67 9 1 4 ARC EL3 2 0 din rail mounting...
Page 68: ...68 9 1 5 ARC EC1 2 0 din rail mounting...
Page 69: ...69 9 1 6 Fiber sensor mounting r min 50 mm...
Page 70: ...70 9 1 7 Point sensor mounting...
Page 82: ...82 10 Application examples 10 1 Applications 10 1 1 With a main busbar system...
Page 83: ...83 10 1 2 With two main busbar systems...
Page 84: ...84 10 1 3 With two main busbar systems and additional zone selection 4 zones...
Page 85: ...85...