Eaton 93E UPS 15-80 kVA (380/400/415 V)
Installation and Operation Manual
© Eaton Corporation plc 2015. All rights reserved.
Revision: 001
Document ID: 614-01975-00
43 (133)
Type
Article no
Eaton 93E 60kVA
NZMN2-A200
259093
Eaton 93E 80kVA
NZMN2-A320
109669
Use of 4-pole breakers in the AC inputs of the UPS is not recommended.
Neutral transfer must be overlapping (make-before-break).
Cable lugs must be used for mounting the cabling to the UPS power
cabling terminals.
Table 6. UPS external power cable terminations for the Eaton 93E 15-80 kVA
Terminal function
Terminal
Bus landing
Tightening torque
[Nm]
AC input to rectifier
L1, L2, L3, N
M8 screw mounting
12
AC input to bypass
L1, L2, L3, N
M8 screw mounting
12
AC output to critical
load
L1, L2, L3, N
M8 screw mounting
12
DC input from external
battery
Battery (+)
Battery (-)
M8 screw mounting
12
Customer earth, 15-
20 kVA
PE (Earthing)
M6 screw mounting
9
Customer earth, 30-
40 kVA
PE (Earthing)
M8 screw mounting
24
Table 7. Recommended ratings for rectifier input, bypass and output circuit
breakers or fuses
Rectifier input
UPS
output/bypass
Battery
Rated
power
Rated
voltage
[V]
Rated
current
[A]
Fuse
rating
[A]
Rated
current
[A]
Fuse
rating
[A]
Rated
current
[A]
Fuse
rating
[A]
15 kVA
380/400/415 23
40
22
25
39
63
20 kVA
380/400/415 31
40
29
32
52
63