Eaton 93E UPS 15-80 kVA (380/400/415 V)
Installation and Operation Manual
© Eaton Corporation plc 2015. All rights reserved.
Revision: 001
Document ID: 614-01975-00
28 (133)
Mark
With package
kg (lb.)
Without package
kg (lb.)
Eaton 93E-60-N-MBS
246 (542)
207 (456)
Eaton 93E-80-N-MBS
290 (639)
250 (551)
The UPS cabinet uses forced air cooling to regulate internal component
temperature. Air inlets are in the front of the cabinet and outlets are at
the rear of the cabinet. Allow clearance in front of and behind the cabinet
for proper air circulation. The clearances required around the UPS
cabinet are shown in Table 2.
Table 2. UPS cabinet clearances
At the top of the cabinet
300 mm (12") working space
At the front of the cabinet
900 mm (36") working space
At the back of the cabinet
At the right side of the cabinet
At the left side of the cabinet
The basic environmental requirements for the operation of the UPS are
as follows:
•
Ambient temperature range: from +0 to +40 °C (32–104 °F)
•
Recommended operating range: from +20 to +25 °C (68–77 °F)
•
Maximum relative humidity: 95%, non-condensing