Eaton 93E UPS 15-80 kVA (380/400/415 V)
Installation and Operation Manual
© Eaton Corporation plc 2015. All rights reserved.
Revision: 001
Document ID: 614-01975-00
129 (133)
Operating input current
See Table 5, adjustable
Input current harmonic content
5% THD at full load
Power factor
Minimum 0.99
Line surges
6 kV OC, 3 kA SC per ANSI 62.41 and
IEC 8014
Battery voltage
384 Vdc (32 blocks) if using internal
batteries.
384-480 Vdc (32-40 blocks) if using
external batteries.
Note: Do not connect battery strings
with different number of cells in
parallel!
Battery charging capacity (384 Vdc)
15 kVA UPS
5.3 A maximum at any
load up to a 100% load
20 kVA UPS
5.3 A maximum at any
load up to a 100% load
30 kVA UPS
8 A maximum at any
load up to a 100% load
40 kVA UPS
10.6 A maximum at
any load up to a 100%
load
60 kVA UPS
16 A maximum at any
load up to a 100% load
80 kVA UPS
24 A maximum at any
load up to a 100% load
10.2.4
UPS output
UPS output capacity
100% rated current
Output voltage regulation
± 1% (10% to 100% load)
Nominal output voltage
380 Vac, 400 Vac and 415 Vac nominal
Output voltage harmonic content
2% maximum THD (linear load)
5% maximum THD (non-linear load)
Output current