UPS SYSTEM ONELINE DRAWING
091505
A
TYPICAL PARALLEL SYSTEM
(2+1 AND 3+0 CONFIGURATIONS)
5 of 6
164201604---4
NOTE:
1. UPM and system bypass input feeds
must come from the same source.
2. Remove jumper for dual-feed.
3. See Note 27 on page A---21 for
neutral bonding instructions.
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
OUTPUT TO
CRITICAL LOAD
BATTERY CABINET
BATTERY
BREAKER
E4. E5
E9
E10
E11
E12
FUSE
K5
STATIC
SWITCH
FUSE
K3
FUSE
BATTERY
CONVERTER
RECTIFIER
INVERTER
K1
UPM 1
E1
E2
E3
E6E
7E8
E12
A
B
SEE NOTE 2
D
MOB 1
F
E
BATTERY CABINET
BATTERY
BREAKER
E4. E5
E9
E10
E11
E12
FUSE
K5
STATIC
SWITCH
FUSE
K3
FUSE
BATTERY
CONVERTER
RECTIFIER
INVERTER
K1
UPM 2
E1
E2
E3
E6E
7E8
E12
A
B
SEE NOTE 2
D
BATTERY CABINET
BATTERY
BREAKER
E4. E5
E9
E10
E11
E12
FUSE
K5
STATIC
SWITCH
FUSE
K3
FUSE
BATTERY
CONVERTER
RECTIFIER
INVERTER
K1
UPM 3
E1
E2
E3
E6E
7E8
E12
A
B
SEE NOTE 2
D
MOB 3
MOB 2
MIS
MBP
*
*
*
*
*
*
C
C
C
G
MODULE TIE
CABINET
(OPTIONAL)
Installation Information
A-10
EATON
Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual
S
164201604 Rev B
powerware.com
A --
AC Input to UPS Rectifier and Bypass (single-feed) and UPS Rectifier (dual-feed)
B --
AC Input to UPS Bypass (dual-feed)
C --
DC Input from Battery
D --
UPM AC Output to Parallel Tie Point
E --
AC Input Source
F --
System Bypass Input
G --
Output to Critical Load
* --
Overcurrent Protection Provided by Others
Summary of Contents for 9390 UPS 100160 kVA