Installing the UPS System
3-5
EATON
Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual
S
164201604 Rev B
powerware.com
NOTE
In the following step the pallet tilts and acts as a ramp once the cabinet is rolled
beyond the the center of the pallet. Be sure to restrain the cabinet as it continues to roll
down the pallet/ramp. The rear shipping bracket will act as a brake to assist
restraining the cabinet.
W A R N I N G
Do not stand directly in front of the pallet while unloading the cabinet. If unloading
instructions are not closely followed, the cabinet may cause serious injury.
8.
Slowly roll the cabinet toward the front of the pallet. Once the pallet tilts,
continue rolling the cabinet down the pallet until the cabinet is clear of the pallet.
9.
Remove the four bolts securing the rear shipping bracket to the cabinet (see
Figure 3-2). If installing the cabinet permanently, retain the shipping bracket and
securing hardware for later use.
10.
Roll the cabinet to the final installation location.
11.
If installing the cabinet permanently, retain the shipping brackets and hardware;
otherwise, discard or recycle the pallet and shipping brackets in a responsible
manner.
12.
If permanently mounting the system, proceed to Step 15; otherwise, continue to
Step 13.
13.
Secure the UPS cabinet in position by lowering the leveling feet until the cabinet is
not resting on the casters and the cabinet is level.
14.
If installing battery and distribution cabinets, proceed to paragraphs 3.2.2 and
3.2.3; otherwise, proceed to paragraph 3.2.6.
15.
Using the retained hardware, reinstall the shipping brackets removed in Step 6 to
the front and rear of the UPS cabinet with the angle facing outward (see
Figure 3-1 and Figure 3-2).
16.
Secure the cabinet to the floor with contractor-supplied hardware.
17.
If installing battery and distribution cabinets, proceed to paragraphs 3.2.2 and
3.2.3; otherwise, proceed to paragraph 3.2.6.
3.2.2 Battery Cabinet Installation
To install the battery cabinet, refer to the
Powerware 9390 Integrated Battery Cabinet
(Models IBC-S and IBC-L) Installation Manual
. After the battery cabinet is installed, return
to paragraph 3.2.6 to wire the UPS and battery cabinet.
Summary of Contents for 9390 UPS 100160 kVA
Page 1: ...Powerware 9390 UPS 100 160 kVA Installation and Operation Manual...
Page 225: ......
Page 226: ...164201604B 164201604 B...