164201604---2
1 of 2
PHYSICAL FEATURES AND REQUIREMENTS
091505
A
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
Installation Information
A-3
EATON
Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual
S
164201604 Rev B
powerware.com
1.
The UPS equipment operating environment must meet the weight requirements shown in
Table A and the size requirements shown on Drawing 164201604---9.
2.
The UPS cabinet is palleted separately for shipping.
3.
Do not tilt cabinets more than
10
˚
during handling.
4.
Dimensions are in millimeters (inches).
5.
The cabinet can be installed in
line-up-and-match
or
standalone
configurations.
Table A. UPS Cabinet Weight
Model
Voltage
Weight
kg (lb)
Input
Output
Shipping
Installed
Point Loading
Powerware 9390---120/100
208V/220V 208V/220V 531 (1170)
504 (1110)
6 at 84 (185)
480V
480V
467 (1030)
440 (970)
6 at 73 (162)
Powerware 9390---120/120
208V/220V 208V/220V 531 (1170)
553 (1110)
6 at 84 (185)
480V
480V
467 (1030)
440 (970)
6 at 73 (162)
Powerware 9390---160/100
208V/220V 208V/220V
581 (1280)
553 (1220)
6 at 92 (204)
480V
480V
Powerware 9390---160/120
208V/220V 208V/220V
581 (1280)
553 (1220)
6 at 92 (204)
480V
480V
Powerware 9390---160/160
208V/220V 208V/220V
581 (1280)
553 (1220)
6 at 92 (204)
480V
480V
6.
The clearances required around the UPS cabinet are shown in Table B.
Table B. UPS Cabinet Clearances
From Top of Cabinet
Minimum clearance over the UPS cabinet is
457.2 mm (18 in.) for ventilation
From Front of Cabinet
914.4 mm (36 inches) working space
From Back of Cabinet
None required
From Right Side of Cabinet
None required
From Left Side of Cabinet
None required