INTERFACE WIRING INSTALLATION
NOTES AND TERMINAL LOCATIONS
POWERWARE HOT SYNC CAN BRIDGE CARD
CONNECTIONS FOR PARALLEL SYSTEM CONTROL
CONNECTIONS FOR RMP II, RIM II, OR SCM II
BUILDING ALARM 2 REPLACEMENT
J3
NOTE:
All interface wiring is to be provided
by the customer.
CONNECTIONS FOR BYPASS STATUS
9 of 13
Installation Information
A-41
EATON
Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual
S
164201604 Rev B
powerware.com
16.
Conduit must be installed between the UPM cabinets for parallel interface wiring. Install the
interface wiring in separate conduit from the power wiring.
17.
Use Class 1 wiring methods (as defined by the NEC) for parallel interface wiring. The wire
should be shielded twisted pair, rated for 5 amps maximum.
18.
See Table X and Chapter 6 for Powerware Hot Sync CAN Bridge Card interface wiring.
Table X. Powerware Hot Sync CAN Bridge Card Interface Connections
Terminal J3
Name
Description
1
Alarm
Programmable UPS alarm. Activated by a remote
dry contact closure.
2
Alarm Rtn
3
Alarm Relay NC
Normally-closed contact opens when UPS is on
bypass.
4
Alarm Relay Com
Bypass contact return.
5
Alarm Relay NO
Normally-open contact closes when UPS is on
bypass.
6
TX
Remote Monitor Panel II (RMP II), Relay Interface
Module II (RIM II), and Supervisory Contact
Module II (SCM II) connections.
7
TX
8
CAN L
Computer Area Network (CAN) Input for parallel
operation.
9
CAN H
10
Shield