POWER WIRING INSTALLATION NOTES
091505
A
164201604---5
NOTE:
Customer ground can be run in any conduit listed in Table J.
5 of 15
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
Installation Information
A-16
EATON
Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual
S
164201604 Rev B
powerware.com
Table I. UPS Cabinet Power Cable Terminations for the Powerware 9390---120/100,
9390---120/120, 9390---160/100, 9390---160/120, and 9390---160/160 (208V/220V Input and
208V/220V Output), and the Powerware 9390---160/100, 9390---160/120, and 9390---160/160
(480V Input and 480V Output)
Terminal Function
Terminal Function Size of Pressure
Termination
Tightening
Torque
Nm (lb in)
Type
Screw
AC Input to UPS Rectifier
and Bypass
(Single Input)
E1
Phase A
2 --- #2---600 kcmil
56.5 (500)
1/2 in. Hex
E2
Phase B
2 --- #2---600 kcmill
56.5 (500)
1/2 in. Hex
E3
Phase C
2 --- #2---600 kcmil
56.5 (500)
1/2 in. Hex
AC Input to UPS Rectifier
(Dual Input)
E1
Phase A
2 --- #2---600 kcmil
56.5 (500)
1/2 in. Hex
E2
Phase B
2 --- #2---600 kcmil
56.5 (500)
1/2 in. Hex
E3
Phase C
2 --- #2---600 kcmill
56.5 (500)
1/2 in. Hex
AC Input To Bypass
(Dual Input)
E6
Phase A
2 --- #2---600 kcmil
56.5 (500)
1/2 in. Hex
E7
Phase B
2 --- #2---600 kcmil
56.5 (500)
1/2 in. Hex
E8
Phase C
2 --- #2---600 kcmil
56.5 (500)
1/2 in. Hex
Single-Feed to Dual-Feed
Transfer Wires from
Rectifier Input Terminals
to Bypass Input Terminals
Rectifier
Phase A
N/A
12.5 (110)
M8 Hex Bolt
Bypass
Phase A
N/A
12.5 (110)
M8 Hex Bolt
Rectifier
Phase B
N/A
12.5 (110)
M8 Hex Bolt
Bypass
Phase B
N/A
12.5 (110)
M8 Hex Bolt
Rectifier
Phase C
N/A
12.5 (110)
M8 Hex Bolt
Bypass
Phase C
N/A
12.5 (110)
M8 Hex Bolt
AC Output to
Critical Load
E9
Phase A
2 --- #2---600 kcmil
56.5 (500)
1/2 in. Hex
E10
Phase B
2 --- #2---600 kcmil
56.5 (500)
1/2 in. Hex
E11
Phase C
2 --- #2---600 kcmill
56.5 (500)
1/2 in. Hex
DC Input from
Battery to UPS
E4
Positive
2 --- #2---600 kcmil
56.5 (500)
1/2 in. Hex
E5
Negative
2 --- #2---600 kcmil
56.5 (500)
1/2 in. Hex
Input and Output Neutral
E12
Neutral
8 --- #2---600 kcmil
56.5 (500)
1/2 in. Hex
Customer Ground
Ground
Ground
8 --- #14---1/0
5.6 (50)
Slotted