UPS Operating Instructions
10-2
EATON
Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual
S
164201604 Rev B
powerware.com
7.
Observe the following messages appear sequentially on the power module (PM)
status line:
DC STARTING
INVERTER STARTING
INVERTER SYNCING
READY
ONLINE
The rectifier and inverter turn on. The inverter continues to ramp up to full
voltage.
8.
Close the battery breaker any time after INVERTER SYNCING or CLOSE BATTERY
appears on the display.
Once the inverter reaches full voltage, and the battery breaker is closed, the UPS
output contactor K3 closes and the static switch turns off. Power is now supplied
to the critical load in Normal mode. It takes approximately 1 minute for the UPS
to achieve Normal mode.
9.
The UPS is now operating in Normal mode and the
NORMAL
status indicator is
illuminated.
10.1.2 Starting the UPS in Bypass Mode
If the inverter output of the UPS is not available and the critical load needs to be
energized, perform the following procedure:
C A U T I O N
In Bypass mode, the critical load is not protected from commercial power interruptions and
abnormalities.
1.
Close the UPS input feeder circuit breaker.
2.
If the UPS is dual feed, close the UPS Bypass input feeder circuit breaker.
3.
Observe the UPS control panel becoming active, indicating logic power.
4.
Press the
CONTROLS
pushbutton on the main menu bar. The System Controls
screen appears.
5.
On the System Controls screen, the power module (PM) status should indicate
SHUTDOWN.
6.
Press the
BYPASS
pushbutton on the System Controls menu bar.
The critical load is immediately supplied by the bypass source, in Bypass mode.
7.
The UPS is now operating in Bypass mode and the
BYPASS
status indicator is
illuminated.
Summary of Contents for 9390 UPS 100160 kVA
Page 1: ...Powerware 9390 UPS 100 160 kVA Installation and Operation Manual...
Page 225: ......
Page 226: ...164201604B 164201604 B...