Using the Control Panel
9-6
EATON
Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual
S
164201604 Rev B
powerware.com
9.2.3 Unit Meter Screens
The Unit Meter screens show the UPS meter readings for the unit (or units, if a parallel
system is installed). The default voltage displayed on these screens is phase-to-neutral.
However, an authorized Eaton Customer Service Engineer can change the screens to display
the voltage phase-to-phase (A-B, B-C, C-A).
Press the
METERS
pushbutton on the main menu bar to display the Unit Meter screens.
Figure 9-6 through Figure 9-10 show the Unit Meter screens.
To scroll through the meter screens, press the
or
pushbuttons on the menu bar. The
current UPS readings are displayed in the information area of the screen.
NOTE
The UNIT designation after the meter type, and the SYSTEM and UNIT menu
bar pushbutton selections, are visible only when a parallel system is installed.
The Output screen shows output voltage (phase-to-neutral), output current (each phase),
and frequency being supplied by the UPS, as well as the kVA, kW, and power factor
measurements.
V1
V2
V3
KVA
KW
PF
I1
I2
I3
***
***
***
***
***
***
***
***
***
FREQ
***
OUTPUT --- UNIT
LEAD
UNIT
SYSTEM
Figure 9-6. Unit Output Meter Screen