PHYSICAL FEATURES AND REQUIREMENTS
091505
A
164201604---2
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
Installation Information
A-4
EATON
Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual
S
164201604 Rev B
powerware.com
7.
The basic environmental requirements for operation of the UPS system are:
Ambient Temperature Range:
0---40
˚
C (32---104
˚
F)
Recommended Operating Range:
20---25
˚
C (68---77
˚
F)
Maximum Relative Humidity:
95%, noncondensing
The UPS ventilation requirements are shown in Table C.
Table C. Air Conditioning or Ventilation Requirements During Full Load Operation
Ratings
Voltage
Heat Rejection
BTU/hr
¢
1000/hr (kg-cal/hr)
Input
Output
100 kVA
208/220
208/220
29.6 (7.45)
100 kVA
480
480
27.4 (6.90)
120 kVA
208/220
208/220
35.5 (8.94)
120 kVA
480
480
32.8 (8.28)
160 kVA
208/220
208/220
47.3 (11.9)
160 kVA
480
480
43.8 (11.0)
Ventilation required for cooling air exhaust: approximately 9.44 liter/sec (2000 cfm).