11.6
Supervisory Contact Module
An optional Supervisory Contact Module (SCM) establishes an interface between
the Parallel Capacity/Redundant system manufacturer’s equipment and the
customer’s monitor. This interface allows the customer to monitor operational
status of the Parallel Capacity/Redundant system equipment. A maximum of two
monitoring accessories (RMPs, RIMs, or SCMs) can be installed. See Table 11−1
for the number of accessories permitted. Figure 11−3 shows the SCM, input
connections on TB1, and output connections on TB2.
TB2
Figure 11−3.
Supervisory Contact Module
The SCM provides signals for the following indications:
•
SYSTEM NORMAL
TB2−1 through TB2−3
•
NO REDUNDANCY
TB2−4 through TB2−6
•
ON GENERATOR
TB2−7 through TB2−9
•
BYPASS NOT AVAILABLE
TB2−10 through TB2−12
•
ON BATTERY
TB2−13 through TB2−15
•
UPS ALARM
TB2−16 through TB2−18
•
ON BYPASS
TB2−19 through TB2−21
•
SHUTDOWN IMMINENT
TB2−22 through TB2−24
Refer to the applicable Powerware 9315 Installation manual chapter,
Installing a
Supervisory Contact Module
, for TB2 contact configurations.