9
−
2
EATON
Powerware 9315 Parallel Capacity/Redundant System
164201150 Rev. E
www.powerware.com
9.2
Using the LCD Screen
The LCD screen at the top of the Control Panel provides an operator interface with
the Parallel Capacity/Redundant system. Figure 9−2 identifies the display fields
discussed in the following sections.
Uninterruptible Power System
System Normal
ALARM: NONE
NOTICES: NONE
Meters
System
Load Amps
Events Statistics Graphics Setup
Input
Output
Bypass
Battery
VAB
480
VBC
VCA
KW
379
KVA
399
IA
IB
IC
FREQ
60.0
PF
0.95
V
540
I
18
Meters
480
480
480
480
480
VAB
480
VBC
VCA
480
480
IA
IB
IC
361
361
361
IN
000
VAB
480
VBC
VCA
480
480
FREQ
60.0
KVA
300
KW
240
PF
0.80
Battery
15 JUL 1998 09:25:42
48.6
Minutes
A
E
D
C
B
F
G
Versions
+
Figure 9−2.
Parts of the LCD Screen
(Typical for Powerware 9315 300 480/480V Unit)
A
The
UPS status area
contains three lines that display the current state of the UPS. The first
line shows the present operational mode of the UPS. The second line shows the highest level
of the current active alarms, and the third line shows any notices the UPS has posted. (For
more information about alarms and notices, refer to Chapter 11, Responding to System
Events.")
B
The
battery charge box
shows the minutes of battery capacity available.
C
The
menu box
shows the currently selected menu and lists the options available on that
menu. The title at the top of the menu box is also shown below on the menu bar (
E
). Press
the and pushbuttons to scroll up and down through the options in the menu box.
D
The currently selected
option
is highlighted in the menu box. Press the and pushbuttons
to move the highlight up or down. The data in the information area (
G
) changes accordingly.
E
The
menu bar
lists the titles of the menus. The title of the menu currently displayed in the
menu box is highlighted. When you press the
and
pushbuttons to move the highlight
left or right, the data in the menu box and the information area change accordingly.
F
The
time stamp
shows the current date and time. This date and time are recorded in the
Event Log when a notice or alarm is activated.
Summary of Contents for 9315
Page 1: ...Powerware 9315 UPS Parallel Capacity Redundant System Installation and Operation Manual ...
Page 136: ......
Page 205: ......
Page 206: ...164201150 Rev E 164201150E ...