16
−
2
EATON
Powerware 9315 Parallel Capacity/Redundant System
164201150 Rev. E
www.powerware.com
16.3
SBM Output
Output Voltage
(UPM Dependent)
480 VAC nominal (60 Hz only)
600 VAC nominal (60 Hz only)
400 VAC nominal (50/60 Hz)
Output Frequency Range
"
3 Hz of nominal (50 Hz or 60 Hz)
Output Current
Model 600:
600 Amps
Model 800:
800 Amps
Model 1000:
1000 Amps
Model 1200:
1200 Amps
Model 1600:
1600 Amps
Model 2000:
2000 Amps
Overload Capability
Alarm only. Trip Delay customer adjustable in
accordance with breaker manufacturer
specifications.
16.4
Environmental Specifications
Operating Temperature
0 to 40°C without derating. The recommended
operating temperature is 25°C.
Operating Altitude
Maximum 1500m (5000 ft) at 40
_
C without
derating
Storage Temperature
−20 to +70°C (prolonged storage above 40°C
will cause rapid battery self-discharge)
Relative Humidity (operating and
storage)
95% maximum noncondensing
Acoustical Noise
N/A
EMI Suppression
Meets FCC Regulation 47, Part 15, Subpart J, for
class A devices
Electrostatic Discharge (ESD)
Immunity
Meets IEC 801−2 specifications. Withstands up
to 25 kV without damage and with no disturbance
or adverse effect to the critical load.