Powerware 9315 Parallel Capacity/Redundant System
164201150 Rev. E
www.powerware.com
4.
Connect RIM wiring to the terminal block using the terminations shown in
Table 5−1.
Table 5−1. RIM Wire Terminations
From RIM A
To SBM
Remarks
TB1−4
TB3−1
TWISTED WIRES (4)
1−2 TURNS PER
3 INCHES
TB1−5
TB3−2
TB1−6
TB3−3
TB1−7
TB3−4
From RIM B (if used)
To SBM
Remarks
TB1−4
TB3−5
TWISTED WIRES (4)
1−2 TURNS PER
3 INCHES
TB1−5
TB3−6
TB1−6
TB3−7
TB1−7
TB3−8
5.
Contact your local field service office for verification and testing of the RIM
and its connections prior to making connections to J1−J4.
You can order interface cables separately for connecting to the 15-Pin D-Sub
Connectors.
6.
Repeat steps 1 through 5 for each RIM you are installing.
7.
If you are installing an RMP or SCM in addition to an RIM, proceed to Chapter
4 or 6, respectively; otherwise, secure the SSBM by reversing the steps
contained in procedure To Prepare the SBM for Wiring to an RMP, RIM, SCM,
or Remote EPO" of Chapter 2.