background image

A−11

EATON

 

Powerware 9315 Parallel Capacity/Redundant System

164201150     Rev. E  

www.powerware.com

DESCRIPTION:

DRAWING NO:

SHEET:

164201150−3

TYPICAL PARALLEL CAPACITY/
REDUNDANT SYSTEM WITH 2000A SBM

COMMON BATTERY SYSTEM

1

1

1

1

3

4

2 of 2

 

5

5

1

3

4

UTILITY POWER INPUT TO UPM

SBM OUTPUT TO CRITICAL LOAD

UTILITY POWER INPUT TO BYPASS BUS

5

POWERNET DUAL REDUNDANT NETWORK

SBM INTERFACE 

 TERMINAL BLOCK TB1

UPM INTERFACE 

 TERMINAL BLOCK TB1

2

UPM OUTPUT TO SBM INPUT

2

NOTE:

1. Accommodates one to eight UPMs.

Four UPM system shown.

2. The input transformer cabinet may be

installed on either the left or the right
side of the UPM cabinet.

3. Refer to the 

Powerware

®

 9315 UPS

Installation 

manual provided with the

UPMs, for UPM, battery, and optional
input transformer installation
information.

Summary of Contents for 9315

Page 1: ...Powerware 9315 UPS Parallel Capacity Redundant System Installation and Operation Manual ...

Page 2: ... the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to ...

Page 3: ...ach Cabinet 1 3 2 Installing the Parallel Capacity Redundant System 2 1 2 1 Preliminary Installation Information 2 1 2 2 Installing the SBM Cabinet 2 2 2 3 Installing the SMB Cabinet 2 2 2 4 Installing the UPM Cabinets 2 3 2 5 Installing SBM Wiring 2 3 2 6 Installing SMB Wiring 2 4 2 7 Prepare for Installing Optional Accessories 2 4 2 7 1 To Prepare the SBM for Wiring to an RMP RIM SCM or Remote E...

Page 4: ...Optional 7 7 7 3 2 Redundant CBP Mode Optional 7 8 8 Operational Controls and Features 8 1 8 1 General 8 1 8 2 SBM Standard Features 8 1 PowerNet 8 2 Computer Interface 8 2 Summary Alarm Contacts 8 2 Building Alarm Monitoring 8 2 8 2 1 Control Panel 8 1 8 2 2 SBM Circuit Breakers 8 1 8 2 3 EMERGENCY UPM OFF 8 2 8 2 4 Customer Interface Panel 8 2 8 2 5 Customer Convenience Outlet 8 2 8 2 6 Installa...

Page 5: ...erware 9315 625 thru 9315 750 UPMs 10 8 10 3 1 Initial Setup 10 8 10 3 2 Manual Start 10 9 10 3 3 Auto Start 10 10 10 3 4 Single UPM Shutdown 10 10 10 3 5 SBM Shutdown to Bypass 10 11 10 3 6 Restarting a Single UPM 10 11 10 3 7 Using the UPM EMERGENCY UPM OFF Pushbutton 10 12 10 3 8 To Use the UPM EMERGENCY UPM OFF Pushbutton 10 12 10 3 9 Resetting the UPM after an EMERGENCY UPM Shutdown 10 12 10 ...

Page 6: ...nformation 13 7 13 5 2 Entire Log Ctrl P 13 8 13 5 3 Meters Printout Ctrl M 13 9 13 5 4 System Information Printout Ctrl A 13 9 13 6 System Configuration 13 10 13 6 1 System Configuration Mode Main Menu 13 10 13 6 2 Program Building Alarms 13 10 13 6 3 Enable Disable Default Functions 13 11 13 6 4 Customize Alarm Messages 13 12 13 6 5 Program Unit Name 13 13 13 6 6 Change Password 13 13 13 6 7 Bat...

Page 7: ...inal Modem Configuration 14 8 14 6 SBM Setup Configuration 14 9 14 6 1 User Selected Events 14 10 15 Maintaining the Parallel Capacity Redundant System 15 1 15 1 General 15 1 15 2 Important Safety Instructions 15 1 15 3 Performing Preventive Maintenance 15 3 15 4 Maintenance Training 15 4 16 Product Specifications 16 1 16 1 Model Numbers 16 1 16 2 SBM Input 16 1 16 3 SBM Output 16 2 16 4 Environme...

Page 8: ... Capacity Redundant System in Battery Mode 7 5 Figure 7 4 Path of Current Through the Parallel Capacity Redundant System in Maintenance Bypass Mode 7 7 Figure 7 5 Path of Current Through the Parallel Capacity Redundant System in Redundant CBP Mode 7 9 Figure 8 1 1200A SBM Controls and Indicators 8 4 Figure 8 2 2000A SBM Controls and Indicators 8 5 Figure 9 1 Parallel Capacity Control Panel 9 1 Fig...

Page 9: ...dundant System 164201150 Rev E www powerware com Figure 13 1 Port 1 Pin Assignments 13 2 Figure 13 2 Port 2 Pin Assignments 13 3 Figure 13 3 Setup Serial Port 1 Screen 13 4 Figure 13 4 Event History Log 13 8 Figure 13 5 System Meters Screen 13 9 ...

Page 10: ...x EATON Powerware 9315 Parallel Capacity Redundant System 164201150 Rev E www powerware com This Page Intentionally Left Blank ...

Page 11: ...ss Module with optional System Maintenance Bypass SMB two or more UPMs and battery racks or cabinets Each UPM may have its own battery rack or may share the same battery rack with the other UPMs Your UPMs functions automatically and requires very little attention during normal operation However you should read and understand the procedures described in this manual to ensure trouble free operation ...

Page 12: ...TY POWER INPUT TO UPM SBM OUTPUT TO CRITICAL LOAD UTILITY POWER INPUT TO BYPASS BUS 5 POWERNET DUAL REDUNDANT NETWORK SBM INTERFACE TERMINAL BLOCK TB1 UPM INTERFACE TERMINAL BLOCK TB1 2 UPM OUTPUT TO SBM INPUT 2 NOTE Accommodates one to eight UPMs Four UPM system shown Figure 1 Typical Parallel Capacity Redundant System ...

Page 13: ... system you are installing dictates which parts of this manual you should read Everyone should read the Introduction Chapters 1 and 2 and Chapters 7 through 12 Introduction The Introduction provides a brief description of the Parallel Capacity Redundant system a description of the content of each chapter safety text conventions used in the manual and reference information Section I Chapter 1 Getti...

Page 14: ...tem features and options Chapter 12 Responding to System Events lists all the alarm messages and notices that occur during operation of the Parallel Capacity Redundant system Chapter 13 Serial Communications describes the serial communications features of the Parallel Capacity Redundant system Chapter 14 Remote Notification contains instructions for using the remote notification feature of the Par...

Page 15: ...ields behind the doors However the parallel redundant system is a sophisticated power system and should be handled with appropriate care following these guidelines Keep surroundings clean and free from excess moisture Do not operate the parallel redundant system close to gas or electric heat sources The system is not intended for outdoor use The operating environment should be maintained within th...

Page 16: ...l accessories including dimensional and connection point drawings are provided 164201036 Powerware 9315 200 kVA 300 kVA UPS Operation 164201119 Powerware 9315 400 kVA 500 kVA UPS Operation Describes the UPS cabinet Control Panel and Monitor Panel and explains the functions of the UPS discusses the standard features of the UPS and optional accessories provides procedures for starting and stopping t...

Page 17: ...EATON Powerware 9315 Parallel Capacity Redundant System 164201150 Rev E www powerware com Section I Installation ...

Page 18: ...EATON Powerware 9315 Parallel Capacity Redundant System 164201150 Rev E www powerware com This Page Intentionally Left Blank ...

Page 19: ...ll features accessories and or options as applicable Chapter 3 7 Complete the Installation Checklist Chapter 2 8 Have authorized service personnel perform preliminary operational checks and startup NOTE Startup and operational checks should be performed only by authorized service personnel This service is usually offered as part of the sales contract for your Parallel Capacity Redundant system Con...

Page 20: ...oling to regulate internal component temperature Air inlets are in the front of the cabinet and outlets are in the top You must allow clearance in front of and above each cabinet for proper air circulation 1 1 3 Environment Considerations The life of the Parallel Capacity Redundant system will be adversely affected if the installation does not meet the following guidelines 1 The system must be ins...

Page 21: ...ONED WOODEN PALLET Figure 1 1 Cabinet as Shipped with Outer Packaging and Pallet 1 Carefully inspect the outer packaging for evidence of damage during transit CAUTION Do not install a damaged cabinet Report any damage to the carrier and contact your local sales or service office immediately 2 Use a forklift or other material handling equipment to move the cabinet to a convenient unpacking area Ins...

Page 22: ...le them in a responsible manner 7 After removing the protective covering inspect the contents for any evidence of physical damage and compare each item with the Bill of Lading If damage has occurred or shortages are evident contact Powerware Corporation Customer Service Department immediately to determine the extent of the damage and its impact upon further installation NOTE While awaiting install...

Page 23: ...onduit landing plates are to be removed to add conduit landing holes as required Plate material is 16 gauge steel 0 06 in thick The Remote Emergency Power Off EPO and the EMERGENCY UPM OFF pushbuttons open all breakers in the SBM shut down the UPMs and isolate power from your critical load Local electrical codes may also require tripping protective devices upstream from the UPMs The SBM cabinet mu...

Page 24: ...e SBM cabinet is clear of the cushioned pallet pull the pallet from under the UPS cabinet Discard or recycle them in a responsible manner 6 Carefully lower the SBM cabinet until the cabinet base contacts the floor 7 Remove lifting eyes from SBM cabinet 2 3 Installing the SMB Cabinet NOTE When the SBM and SMB are installed at the same time the SMB is shipped installed and wired to the SBM The follo...

Page 25: ...ation 1 Install power wiring between the UPMs SBM SMB if provided and critical load Each UPM is individually wired to the SBM UPM input bus Refer to Appendix A of this manual for wiring and termination requirements and wiring access information 2 Install control wiring between UPMs and the SBM and between the SBM and SMB PowerNet network is wired serially daisy chained between UPMs and SBM Wire du...

Page 26: ...Panel refer to Appendix A for location of the access plate 3 Refer to Chapters 3 4 5 or 6 as applicable for installation instructions 2 8 Initial Startup Startup and operational checks should be performed only by authorized service personnel Contact service in advance usually a two week notice is required to reserve a preferred startup date 2 9 Completing the Installation Checklist The final step ...

Page 27: ...l Capacity Redundant system is clean and dust free It is recommended that the Parallel Capacity Redundant system be installed on a sealed concrete pad or a sealed concrete floor Adequate work space exists around the SBM UPMs and other cabinets Adequate lighting is provided around the Parallel Capacity Redundant system A 120VAC service outlet is located within 25 feet of the Parallel Capacity Redun...

Page 28: ..._____________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ______________________________________________...

Page 29: ...es as shown in Figure 3 1 See Drawing 164201150 16 in Appendix A for wiring information enclosure dimensions side views and knockout patterns EMERGENCY OFF UNINTERRUPTIBLE POWER SYSTEM to SBM to other equipment Figure 3 1 Remote EPO Control NOTE Before installing an Remote EPO be sure you have prepared the SBM according to the instructions in Chapter 2 3 ...

Page 30: ...B1 4 TB2 1 Twisted wires 2 14 18 gauge TB1 5 TB2 2 Table 3 2 Remote EPO 1 TB2 2 REMOTE EPO SWITCH TWISTED WIRES 2 Remote EPO switch rating is 24 VDC 1 Amp minimum if supplied by user NOTE This switch must be a dedicated switch not tied into any other circuits 4 If you are installing multiple Remote EPO stations wire additional stations in parallel with the first Remote EPO 5 If required install in...

Page 31: ... the System Bypass Module SBM You can flush mount or surface mount an RMP on a desktop or on a wall wherever you have a serial interface line A maximum of two monitoring accessories RMPs RIMs or SCMs can be installed See Table 4 1 for the number of accessories permitted Figure 4 1 shows an RMP Drawing 164201150 17 in Appendix A shows the enclosure dimensions and knockout patterns Table 4 1 Optiona...

Page 32: ...4 2 EATON Powerware 9315 Parallel Capacity Redundant System 164201150 Rev E www powerware com WIRES MUST BE TWISTED FLUSH MOUNT SURFACE MOUNT FOR HANGING Figure 4 1 Remote Monitor Panel RMP ...

Page 33: ...on refer to the enclosed switchboard vendor drawings for the location of the conduit landing plate 3 In the spare parts kit locate the RMP adapter cable assembly Figure 4 2 Mate the DB 9 connector on the back of the terminal block to the DB 9 connector Port 1 on the Customer Interface Panel of the SBM refer to Drawing 164201150 13 in Appendix A Use two screws from the spare parts kit to secure the...

Page 34: ...P is not present the RMP will self test all indicators flash and the horn beeps at one second intervals If this occurs check all harness connectors and the fuse for proper seating If all connections are secure but the RMP continues to self test replace the fuse with the spare included in the hardware kit If this does not correct the problem contact your local field service office for verification ...

Page 35: ...y support up to eight critical loads A maximum of two monitoring accessories RMPs RIMs or SCMs can be installed Refer to Chapter 4 Table 4 1 for the number of accessories permitted Figure 5 1 shows the RIM with its four 15 pin connectors labeled J1 through J4 Drawing 164201150 18 in Appendix A outlines the enclosure dimensions FLUSH MOUNT SURFACE MOUNT CONTINUES Relay Interface Module FOR HANGING ...

Page 36: ...on of the conduit landing plate 3 If not already installed locate the RMP adapter cable assembly Figure 5 2 in the spare parts kit Mate the DB 9 connector on the back of the terminal block to the DB 9 connector Port 1 on the Customer Interface Panel of the SBM refer to Drawing 164201150 13 in Appendix A Use two screws from the spare parts kit to secure the terminal block bracket to the Customer In...

Page 37: ... 2 TURNS PER 3 INCHES TB1 5 TB3 6 TB1 6 TB3 7 TB1 7 TB3 8 5 Contact your local field service office for verification and testing of the RIM and its connections prior to making connections to J1 J4 You can order interface cables separately for connecting to the 15 Pin D Sub Connectors 6 Repeat steps 1 through 5 for each RIM you are installing 7 If you are installing an RMP or SCM in addition to an ...

Page 38: ...5 4 EATON Powerware 9315 Parallel Capacity Redundant System 164201150 Rev E www powerware com This Page Intentionally Left Blank ...

Page 39: ...Capacity Redundant system status A maximum of two monitoring accessories RMPs RIMs or SCMs can be installed Refer to Chapter 4 Table 4 1 for the number of accessories permitted See Drawing 164201150 19 in Appendix A for enclosure dimensions side views and knockout patterns WIRES MUST BE TWISTED SURFACE MOUNT FOR HANGING TB2 Figure 6 1 Supervisory Contact Module NOTE Before installing an SCM be sur...

Page 40: ...he location of the conduit landing plate 3 If not already installed locate the RMP adapter cable assembly see Figure 6 2 in the spare parts kit Mate the DB 9 connector on the back of the terminal block to the DB 9 connector Port 1 on the Customer Interface Panel of the SBM refer to Drawing 164201150 13 in Appendix A Use two screws from the spare parts kit to secure the terminal block bracket to th...

Page 41: ...emarks TB1 4 TB3 5 TWISTED WIRES 4 1 2 TURNS PER 3 INCHES TB1 5 TB3 6 TB1 6 TB3 7 TB1 7 TB3 8 5 Contact your local field service office for verification and testing of the SCM and its connections prior to making connections to terminal strip TB2 shown in Figures 6 1 and 6 3 6 Repeat steps 1 through 5 for each SCM you are installing 7 If you are installing an RMP or RIM in addition to an SCM procee...

Page 42: ... GENERATOR BYPASS NOT AVAILABLE ON BATTERY UPS ALARM ON BYPASS SHUTDOWN IMMINENT Note Supervisory contacts are rated at 2 0 amps at 28 Vdc or 120 Vac and 0 15 amp at 115 Vdc Supervisory contacts require external power supply Internal 24 Vdc is not capable of supplying contact current Figure 6 3 Supervisory Contact Module TB2 ...

Page 43: ...EATON Powerware 9315 Parallel Capacity Redundant System 164201150 Rev E www powerware com Section II Operation ...

Page 44: ...EATON Powerware 9315 Parallel Capacity Redundant System 164201150 Rev E www powerware com This Page Intentionally Left Blank ...

Page 45: ... Parallel Capacity Redundant System The output of the system is normally supplied by several Uninterruptible Power Modules UPMs Multiple UPMs are connected with their outputs in parallel to provide a load level greater than the rating of one UPM and for redundancy The paralleled UPMs supply the output load with protected power as long as the load does not exceed the combined rating of the parallel...

Page 46: ...ependent networks that are connected to each component network node in the parallel system Data is always transmitted on both networks simultaneously Each network node monitors both PowerNets Failure of one of the two will only result in an alarm condition In addition the applications at each node are designed such that messages can be lost on the network without affecting the operation of the sys...

Page 47: ...ystem when operating in Normal mode Path of Electrical Power UPM1 UPM2 UPM3 UPM4 SS FBP CBP CBS BYPASS INPUT OUTPUT TO CRITICAL LOAD BATT UPM INPUT BATT BATT BATT SBM open Figure 7 1 Path of Current Through the Parallel Capacity Redundant System in Normal Mode If the utility AC power is interrupted or is out of specification the UPMs automatically switch to Battery mode to support the critical loa...

Page 48: ...ctrical Power open Figure 7 2 Path of Current Through the Parallel Capacity Redundant System in Bypass Mode You can transfer the SBM from Normal mode to Bypass mode manually However the SBM switches automatically to Bypass mode whenever the UPMs can no longer supply the critical load If the SBM transfers to Bypass mode from Normal mode due to an output voltage deviation the SBM automatically attem...

Page 49: ...y mode UPM1 UPM2 UPM3 UPM4 SS FBP CBP CBS BYPASS INPUT OUTPUT TO CRITICAL LOAD BATT UPM INPUT BATT BATT BATT SBM Path of Electrical Power open Figure 7 3 Path of Current Through the Parallel Capacity Redundant System in Battery Mode When the discharging battery voltage reaches the lower limit of UPM operational capability the critical load is transferred by the SBM to Bypass mode if it is availabl...

Page 50: ...o optional modes of operation in this Parallel Capacity Redundant system In Maintenance Bypass mode optional the SMB bypass supplies the load and isolates the SSBM and UPMs for maintenance purposes In Redundant CBP mode optional if the CBP breaker fails to close during a manual or automatic operation the SSBM automatically closes the MBP breaker to maintain power to the critical load ...

Page 51: ...pass source supplies the commercial AC power to the load directly CAUTION The critical load is not protected while the Parallel Capacity system is in Maintenance Bypass mode Figure 7 4 shows the path of electrical power through the Parallel Capacity Redundant system when operating in Maintenance Bypass mode UPM1 UPM2 UPM3 UPM4 SS FBP CBP CBS BYPASS INPUT OUTPUT TO CRITICAL LOAD BATT UPM INPUT BATT...

Page 52: ... critical load is not protected while the Parallel Capacity system is in Maintenance Bypass or Bypass mode Once Redundant CBP operation has occurred the SBM must be isolated to allow CBP breaker maintenance without impact on the system s critical load To achieve SBM isolation the Redundant CBP controls have been interlocked with the System Maintenance Bypass controls To exit from Redundant CBP ope...

Page 53: ...are com MBP MIS UPM1 UPM2 UPM3 UPM4 SS FBP CBP CBS BYPASS INPUT OUTPUT TO CRITICAL LOAD BATT UPM INPUT BATT BATT BATT SSBM SMB MAINTENANCE BYPASS INPUT Path of Electrical Power open open open Figure 7 5 Path of Current Through the Parallel Capacity Redundant System in Redundant CBP Mode ...

Page 54: ...7 10 EATON Powerware 9315 Parallel Capacity Redundant System 164201150 Rev E www powerware com This Page Intentionally Left Blank ...

Page 55: ...creen to display the current status of the Parallel Capacity Redundant system You can view a statistical history and log of system events and display a real time graphic representation of power flowing through the system components Backlit status indicators show the operating mode of the SBM and alert you to system events The SYSTEM MODE switch also located on this panel is used to start and stop ...

Page 56: ... link the SBM to the features described in Chapter 13 Serial Communications and Chapter 14 Remote Notification Summary Alarm Contacts Alarm contacts are provided for connection to equipment at your facility such as a light an audible alarm or a computer terminal The equipment you connect to these contacts alerts you to an SBM alarm This feature is described further in Chapter 11 Using Features and...

Page 57: ...ltiple RMPs at remote locations to increase your monitoring capabilities This option is described further in Chapter 11 Using Features and Options 8 3 2 Relay Interface Module An optional Relay Interface Module RIM uses relay contact closures to indicate the operating status and alarm condition of the SSBM The module uses a serial interface line and may support up to eight critical loads This opti...

Page 58: ...Powerware 9315 Parallel Capacity Redundant System 164201150 Rev E www powerware com CONTROL PANEL UPM OUTPUT BREAKER BACKFEED SYSTEM PROTECTION BREAKER BYPASS BREAKER Figure 8 1 1200A SBM Controls and Indicators ...

Page 59: ...Powerware 9315 Parallel Capacity Redundant System 164201150 Rev E www powerware com UPM OUTPUT BREAKER BACKFEED PROTECTION BREAKER SYSTEM BYPASS BREAKER CONTROL PANEL Figure 8 2 2000A SBM Controls and Indicators ...

Page 60: ...roper cooling airflow and to protect personnel from dangerous voltages inside the unit The system contains its own power source Lethal voltages are present even when the system is disconnected from utility power WARNING Only AUTHORIZED SERVICE PERSONNEL should perform service or maintenance on the Parallel Capacity Redundant system If service or routine maintenance is required Ensure all power is ...

Page 61: ...safety agents Everyone in your organization who works with your system should understand the meaning of these symbols ON The principal power switch is in the On position OFF The principal power switch is in the Off position PHASE The word phase CAUTION REFER TO MANUAL Stop and refer to the Operator s Manual for more information RISK OF ELECTRIC SHOCK There is a risk of electric shock present and y...

Page 62: ...8 8 EATON Powerware 9315 Parallel Capacity Redundant System 164201150 Rev E www powerware com This Page Intentionally Left Blank ...

Page 63: ...black square area on the front of the SBM see Figure 9 1 TO BYPASS TO NORMAL SYSTEM MODE PUSH IN TO RESET EMERGENCY UPM OFF NORMAL BATTERY BYPASS NOTICE ALARM STANDBY Figure 9 1 Parallel Capacity Control Panel The Control Panel contains 1 a red EMERGENCY UPM OFF pushbutton 2 a flat liquid crystal display LCD screen 3 a horizontal row of pushbuttons 4 a vertical column of backlit status indicators ...

Page 64: ...perational mode of the UPS The second line shows the highest level of the current active alarms and the third line shows any notices the UPS has posted For more information about alarms and notices refer to Chapter 11 Responding to System Events B The battery charge box shows the minutes of battery capacity available C The menu box shows the currently selected menu and lists the options available ...

Page 65: ... indicating their functions Press the and pushbuttons to move through the options in a menu or to scroll through the list of alarms and notices in the event log Press the and pushbuttons to move through the menu titles on the menu bar Press them simultaneously to silence the horn or to test the lamps behind the status indicators Press the pushbutton to toggle the use of the and pushbuttons between...

Page 66: ...e horn To silence the horn press the and the pushbuttons simultaneously The Notice indicator may be lit along with other indicators Alarm This red symbol is lit when a situation requires immediate attention The LCD screen shows the highest priority active alarms All alarms are accompanied by an audible horn To silence the horn press the and the pushbuttons simultaneously The Alarm indicator may be...

Page 67: ...he UPS The Meters menu is displayed in the menu box with the System option highlighted In the information area the system meters show their current readings Uninterruptible Power System System Normal Meters System Load Amps Events Statistics Graphics Setup Input Output Bypass Battery VAB 480 VBC VCA KW 379 KVA 399 IA IB IC FREQ 60 0 PF 0 95 V 540 I 18 Meters 480 480 480 480 480 VAB 480 VBC VCA 480...

Page 68: ...rrent of the UPS The graph shows the current for each phase Figure 9 4 shows the Load Amps Meters screen Uninterruptible Power System System Normal Meters System Load Amps Events Statistics Graphics Setup Meters Output Current 125 100 75 50 25 0 Phase A Phase B Phase C Battery 48 5 Minutes Versions ALARM NONE NOTICES NONE 15 JUL 1998 09 25 42 Figure 9 4 Load Amps Meters Screen ...

Page 69: ...aphics Setup Meter History Loading Uninterruptible Power System System Normal Events Meters Software Versions Part Number Monitor Rectifier Inverter 143650369 143650347 143650348 01 17 Battery 48 5 Minutes Version System Versions ALARM NONE NOTICES NONE 15 JUL 1998 09 25 42 Figure 9 5 Versions Meters Screen ...

Page 70: ...16 41 30 4 16 41 29 1 COMMAND Keyswitch On STATUS Auto Mode COMMAND Rectifier Commanded On STATUS Inverter On STATUS Rectifier On STATUS Inverter Contactor 3 Closed STATUS Bypass Contactor K4 Open 03 STATUS Inverter Normal Battery 48 5 Minutes Date Time May ALARM NONE NOTICES NONE 15 JUL 1998 09 25 42 Figure 9 6 Event History Log Screen A small return arrow appears in the upper right corner of the...

Page 71: ...lear they are removed from the Active System Events listing Figure 9 7 shows the Active System Events screen Uninterruptible Power System ALARM ON BATTERY SHUTDOWN IMMINENT Events Statistics Graphics Setup Meters Events Active History Active System Events NOTICE Input power unavailable NOTICE Bypass Not Available ALARM Shutdown Imminent Battery Minutes 48 5 Versions System Normal NOTICES NONE 15 J...

Page 72: ...rm 4 Building Alarm 5 Building Alarm 6 UPS Bypass Battery Generator Logic Availability UPS Bypass 0 1 0 0 2 2 3 2 3 3 0 0 0 0 11 9 8 5 8 9 0 99 0 81 48 5 Minutes Battery Month Total DAYS HR MN Time On 0035 20 59 0000 00 30 0000 00 02 0000 00 00 0035 21 30 ALARM NONE NOTICES NONE 15 JUL 1998 09 25 42 Figure 9 8 Unit Statistics Screen The left column shows the number of UPS incidents for the current...

Page 73: ...ATIC SWITCH FBP CBP MBP MBP INPUT INPUT BYPASS KWA KV Amps Phase CAPACITY LOAD 500 420 222 0 0 0 NOTE Number of UPMs showing on MIMIC screen is dependent on number of units installed at site 15 JUL 1998 09 25 42 Figure 9 9 Mimic Screen The Mimic screen shows the internal components of the UPS cabinet The flow of current through the components is highlighted NOTE The number of UPMs displayed on the...

Page 74: ...n arrow appears in the upper right corner of the Time Setup screen This arrow is a reminder that you can press the pushbutton on the Monitor Panel to toggle the pushbuttons between the menu box and the information area When the scroll bar is in the information area the return arrow is in the menu box When the scroll bar is in the menu box the return arrow is in the information area When the scroll...

Page 75: ...corner of the Port Setup screen This arrow is a reminder that you can press the pushbutton on the Monitor Panel to toggle the pushbuttons between the menu box and the information area When the scroll bar is in the information area the return arrow is in the menu box When the scroll bar is in the menu box the return arrow is in the information area When the scroll bar appears in the information are...

Page 76: ...9 14 EATON Powerware 9315 Parallel Capacity Redundant System 164201150 Rev E www powerware com This Page Intentionally Left Blank ...

Page 77: ...m operates properly 2 Refer to Chapter 9 of this manual for description of SBM controls and monitor panel functions 3 Refer to the applicable Powerware 9315 UPS Operation manual provided with the UPMs for UPM operating instructions 10 2 Operation of SBM with Powerware 9315 200 thru 9315 500 UPMs 10 2 1 Initial Setup 1 Ensure the System Bypass Module SBM circuit breakers are set as follows UPM Outp...

Page 78: ...s shown on the SBM mimic screen 7 On first UPM set BATTERY switch to NORMAL 8 On first UPM set MODE switch to NORMAL 9 On first UPM turn the START switch to the right for 2 seconds and then release 10 When UPM Battery Disconnected alarm and notification is received close first UPM battery disconnect breaker 11 On first UPM turn the START switch to the right momentarily The rectifier turns on then ...

Page 79: ...ilable The status indicators on the SBM monitor screen indicate when the Parallel Capacity Redundant system is in Bypass mode and Normal mode 8 Observe that CBS is open and CBP is closed 9 When UPM Battery Disconnected alarm and notification message is received close UPM battery disconnect breakers The UPM inverters turns on When each inverter reaches full voltage K3 closes Logic power is supplied...

Page 80: ...d load side of K3 will still have voltage present 10 2 5 SBM Shutdown to Bypass 1 On SBM turn the SYSTEM MODE key switch to BYPASS momentarily 2 Observe CBS opens and CBP closes 3 On SBM monitor screen verify On Bypass message appears System is now on bypass 4 Set UPM battery disconnect breakers to open 5 When UPM Battery Disconnected alarm and notification message is received open CB1 on all UPMs...

Page 81: ...LOAD OFF Pushbutton NOTE The UPM LOAD OFF pushbutton will only interrupt the ability for that module to deliver power to the critical bus The redundant modules will continue to support the critical load To remove all power from the critical load use the SBM EMERGENCY UPM OFF pushbutton Load Off is initiated by the covered red UPM LOAD OFF pushbutton on the Monitor Panel This pushbutton is protecte...

Page 82: ...IPPED position 3 The UPM is now reset To restart the UPM follow the procedure in Chapter 4 Starting and Stopping the UPS 10 2 10 Using the SBM EMERGENCY UPM OFF Pushbutton An SBM Emergency UPM Off is initiated by the covered red EMERGENCY UPM OFF pushbutton on the SBM Control Panel This pushbutton is protected by a clear plastic shield to prevent accidental activation In an emergency you can press...

Page 83: ...opening and closing and the Emergency UPM Off PUSH IN TO RESET pushbutton on the SBM Control Panel pops out 10 2 12 Resetting the Parallel Capacity Redundant System after an EMERGENCY UPM OFF CAUTION Do not attempt to restart the UPM after Load Off until the cause of the emergency has been identified and cleared The Emergency UPM Off PUSH IN TO RESET pushbutton is a small white button on the SBM C...

Page 84: ... OPEN optional 2 Ensure the UPS circuit breakers for all UPMs are set as follows UPS Input Breaker CB1 Open UPS Battery Breaker CB2 MBB Open UPS Output Breaker CB3 Open 3 Ensure the Emergency UPM OFF PUSH TO RESET pushbuttons on the SBM and all UPMs are pressed in NOTE When power is applied in the following step circuit breakers CBS CBP and FBP will charge if not already charged 4 Close upstream U...

Page 85: ...eaker CB1 has closed by verifying breaker position on LCD mimic screen The rectifier and input rectifier cooling fans blowers should be running 7 Confirm UPS Battery Breaker CB2 MBB has closed by viewing breaker position on LCD Mimic screen NOTE If CB2 is a manual battery breaker manually close CB2 after UPM Battery Disconnected alarm and notification is received The inverter and output inverter c...

Page 86: ...ge the UPS CB3 breakers close It takes less than one minute for the UPMs to achieve Normal mode The UPMs are now ready to supply power to the critical load 6 Once the Parallel Capacity Redundant system is redundant the critical load is automatically transferred from bypass to the UPMs via the CBS breaker and system is operating in Normal mode NOTE If transfer is not completed within one minute the...

Page 87: ...UPM 1 Close upstream UPM input feeder breaker 2 Observe UPM monitor screen becoming active as an indication of logic power 3 Verify UPM is shown on the SBM mimic screen 4 On UPM set BATTERY switch to ENABLE 5 On UPM turn MODE key switch to NORMAL for three seconds 6 Confirm the UPS breaker CB1 has closed by viewing breaker position on LCD Mimic screen The rectifier and input rectifier cooling blow...

Page 88: ...OTE The UPM REMOTE EMERGENCY LOAD OFF REPO functions in the same way as the UPM EMERGENCY UPM OFF pushbutton on the UPM Monitor panel 10 3 8 To Use the UPM EMERGENCY UPM OFF Pushbutton 1 Raise the clear plastic shield covering the red EMERGENCY UPM OFF pushbutton on the UPM Monitor Panel 2 Press the EMERGENCY UPM OFF pushbutton UPS breakers CB1 and CB3 and Battery breaker CB2 MBB open The EMERGENC...

Page 89: ...Power to the critical load is de energized and UPMs powered down UPM CB1 breakers trip and the UPM is cut off from utility power This function requires additional EPO kit available from Powerware The SBM including Bypass remains locked off until you reset the EMERGENCY UPM OFF pushbutton To restart the UPS after pressing the EMERGENCY UPM OFF pushbutton follow the procedure Resetting the Parallel ...

Page 90: ...PM Off PUSH IN TO RESET pushbutton is a small white button on the SBM Control Monitor Panel The PUSH TO RESET pushbutton pops out when the Emergency UPM Off pushbutton on the SBM Control Monitor Panel is activated To reset the Parallel Capacity Redundant system 1 Press the Emergency UPM Off PUSH IN TO RESET pushbutton until it clicks in and remains recessed 2 The Parallel Capacity Redundant system...

Page 91: ...ntenance momentarily 4 Observe MBP closes and MIS opens System is now on maintenance bypass 5 To shutdown SBM and UPMs follow procedure under SBM Shutdown to Bypass WARNING Power is present at SBM CBP and FBP inputs until upstream SBM bypass input feeder circuit breaker is opened 6 On SBM open CBP and FBP breakers 10 5 Transfer from Maintenance Bypass NOTE Refer to Appendix A for location of Maint...

Page 92: ...1 10 16 EATON Powerware 9315 Parallel Capacity Redundant System 164201150 Rev E www powerware com This Page Intentionally Left Blank ...

Page 93: ...nel You should use twisted pair wires for each alarm input and common If the SBM is equipped for a Powerware Sync Control or Hot Tie Control not all Building Alarms will be available for customer use See Appendix A Drawing 164201150 13 for affected areas 11 3 General Purpose Relay Contacts Two general purpose relay contacts are provided as a standard feature on the SBM The alarm contacts one notic...

Page 94: ...t status indicators and a local horn You can flush mount or surface mount an RMP on a desktop wall or wherever you have a serial interface line A maximum of two monitoring accessories RMPs Relay Interface Modules RIMs or Supervisory Contact Modules SCMs can be installed See Table 11 1 for the number of accessories permitted Figure 11 1 shows an RMP Figure 11 1 Remote Monitor Panel Table 11 1 Optio...

Page 95: ... The bypass source is supplying the critical load Usually this means that the UPS is not energized The load is not protected in Bypass mode and a horn sounds after 30 seconds UPS ALARM The UPS system is issuing an alarm Conditions that affect the current UPS mode are indicated by the alarm lamps and horn on the UPS ON BATTERY The UPS battery backup is supplying the critical load The utility power ...

Page 96: ...le 11 1 for the number of accessories permitted Figure 11 2 shows the RIM with its four 15 pin connectors labeled J1 through J4 Figure 11 2 Relay Interface Module The RIM can provide these signals UPS AVAILABLE pins 1 and 12 Contacts are closed when the UPS is offline UPS OFF LINE pins 3 and 13 Contacts are closed when the UPS is operating in Normal mode UTILITY FAILURE pins 6 and 15 Contacts are ...

Page 97: ... can be installed See Table 11 1 for the number of accessories permitted Figure 11 3 shows the SCM input connections on TB1 and output connections on TB2 TB2 Figure 11 3 Supervisory Contact Module The SCM provides signals for the following indications SYSTEM NORMAL TB2 1 through TB2 3 NO REDUNDANCY TB2 4 through TB2 6 ON GENERATOR TB2 7 through TB2 9 BYPASS NOT AVAILABLE TB2 10 through TB2 12 ON B...

Page 98: ...nal Battery Disconnect for Common Battery Racks An optional external DC circuit breaker provides a manual means of disconnecting a battery rack from the UPS modules in the Parallel Capacity Redundant system The circuit breaker is enclosed in a wall mounted box You can install it anywhere between the remote DC supply and the UPS according to national and local codes The breaker switch should be set...

Page 99: ...werware 9315 UPS Operation manual provided with the UPMs for UPM system events 12 2 System Event Horns The system event horn beeps according to the type of event it is signifying When the UPS detects an alarm that requires your attention the horn beeps at second intervals When a notice occurs the horn beeps at 2 second intervals 12 3 System Event Lights The status indicators on the SSBM Control Pa...

Page 100: ... displayed on the Active screen of the Monitor panel INVERTER ALARMS Inverter Failure Inverter AC Over Voltage Inverter AC Under Voltage Inverter Over Frequency Inverter Under Frequency Inverter DC Over Voltage Bypass Phase Rotation Inverter Phase Rotation Service Required UPS Tripped Shutdown Imminent UPS Off Battery Contactor K2 Failed Bypass Contactor K4 Failed Inverter Contactor K3 Failed Bypa...

Page 101: ...red Rectifier Setup Required MONITOR ALARMS Overload Warning Load Over 100 Load Over 125 Battery Test Failed Battery Test Failed EEPROM Write Failed Logic Power Supply Failure Fan Failure UPS Failure Other UPS is On Bypass Other UPS Status is Unknown Emergency Bypass Failure Redundant Module Failure Check KW Sensing Check Parallel Setup Parallel System Overload On Battery more than 30 Seconds Chec...

Page 102: ... Will NOT Open UPM Breaker CBS Will NOT Close Bkfeed Brkr FBP Will NOT Open Bkfeed Brkr FBP Will NOT Close UPM Phase Rotation Bypass Phase Rotation PowerNet Channel A RX Down PowerNet Channel B RX Down PowerNet Channel A TX Down PowerNet Channel B TX Down STSW NOT Available STSW SCR SHORTED Load Over 100 Load Over 125 STSW Disconnected K1 Relay Failure PowerNode Calibration Required PowerNode Setu...

Page 103: ...M 3 Not Reporting UPM 4 Not Reporting UPM 5 Not Reporting UPM 6 Not Reporting UPM 7 Not Reporting UPM 8 Not Reporting UPM 1 Alarm UPM 2 Alarm UPM 3 Alarm UPM 4 Alarm UPM 5 Alarm UPM 6 Alarm UPM 7 Alarm UPM 8 Alarm UPM 1 Phone Home UPM 2 Phone Home UPM 3 Phone Home UPM 4 Phone Home UPM 5 Phone Home UPM 6 Phone Home UPM 7 Phone Home UPM 8 Phone Home ...

Page 104: ... Voltage Battery Disconnected Battery Not Charged Phase A Current Limit Phase B Current Limit Phase C Current Limit Battery Voltage Low Inv Logic Power Failure RECTIFIER NOTICES Input AC Over Voltage Input AC Under Voltage Input Over Frequency Input Under Frequency Power Supply Over Voltage Power Supply Under Voltage Input Transient DC Voltage Low DC Voltage High Equalizing Battery Testing Battery...

Page 105: ...twork Down Power Off Switch Rectifier Network Down Inverter Network Down Monitor Network Down Battery Time Low Batt Test Requires Calibration Battery Time Low Monitor Logic Power Failure Building Alarm 1 Active Building Alarm 2 Active Building Alarm 3 Active Building Alarm 4 Active Building Alarm 5 Active Building Alarm 6 Active Testing Battery Battery Test Aborted load Battery Test Aborted utilit...

Page 106: ...tage UPM AC Under Voltage UPM Over Frequency UPM Under Frequency Bypass AC Over Voltage Bypass AC Under Voltage Bypass Over Frequency Bypass Under Frequency Bypass is Not Available Not Enough UPMs System NOT Redundant PowerNode Calibration Fail PowerNode Calibration Pass No Bypass Sync Check EPO Reset Pn Logic Power Failure ...

Page 107: ...M or remote terminal and or printer The Communications Panel also contains terminals TB1 thru TB7 for connecting your equipment to the SBM Refer to drawing 164201150 13 in Appendix A for location of the Customer Interface Panel inside the SBM 13 3 Connecting Equipment to a Serial Port The SBM is designed to accept a wide variety of Data Communication Equipment DCE such as terminals printers and co...

Page 108: ...2 TXD RS232 RXD NOT USED RETURN NOT USED 485 485 RETURN PORT 1 DB 9 Figure 13 1 Port 1 Pin Assignments Table 13 1 Pin Assignments for Port 1 DB 9 Pin Symbol Description Comments 1 24V 24 volts DC 2 TXD Transmit Data Input to UPS 3 RXD Receive Data Output from UPS 5 RTN Return 7 485 RS485 Data 8 485 RS485 Data 9 RTN Return ...

Page 109: ...D NOT USED NOT USED PORT 2 DB 25 Figure 13 2 Port 2 Pin Assignments Table 13 2 Pin Assignments for Port 2 DB 25 Pin Symbol Description Comments 1 GND Chassis Ground 2 TXD Transmit Data Input to UPS 3 RXD Receive Data Output from UPS 4 RTS Request to Send Input to UPS 5 CTS Clear to Send Output from UPS 6 DSR Data Set Ready Output from UPS 7 RTN Return 8 12V 12 volts Output from UPS always true 20 ...

Page 110: ...rial Port 1 Rate 9600 Data Stop 8 1 Handshaking XON XOFF Save NO Time Mode TERMINAL Port 2 Battery 100 Percent ALARM NONE NOTICES NONE 15 JUL 1998 09 25 42 Figure 13 3 Setup Serial Port 1 Screen A small return arrow appears in the upper right corner of the Setup Port screen This arrow is a reminder that you can press the pushbutton on the Monitor Panel to toggle the pushbuttons between the menu bo...

Page 111: ...service personnel System Config Allows you to set building alarms battery tests etc Check with your Sales or Service Representative for availability Computer Provides a proprietary Binary Computer Mode BCM Interface for Powerware facility monitoring or network communication via ConnectUPS Remote Monitor Sends all system event information to an RMP RIM or SCM Available for Port 1 only Port 1 and Po...

Page 112: ...rt ignoring all inputs from handshaking lines D XON XOFF If handshaking is enabled the SBM uses special characters XON and XOFF to handshake with the host terminal The XON character is defined to be ASCII value 11 hex and the XOFF character is defined to be ASCII value 13 hex Upon reception of an XOFF command the SBM halts transmission until an XON command is received In the same way if the termin...

Page 113: ... SS Second 2 digits hh Hundredths of Second 2 digits KYWD Keyword ALARM NOTICE COMMAND or STATUS System Diagnostic Information CR Carriage Return Character ASCII 13 LF Line Feed ASCII 10 An alarm message is prefixed by the word CLEAR whenever an alarm is entered into the Event History Log with a cleared status 13 5 1 Printing Selected Information If a port is operating in Terminal mode and is conn...

Page 114: ...in chronological order with the most recent event listed last Figure 13 4 shows a sample Event History Log printout Event History Log Event Description MAY 12 12 12 12 12 12 12 12 JUN 04 16 41 19 3 16 41 29 1 16 41 42 4 16 42 05 5 16 42 46 8 16 43 15 8 16 43 42 4 16 44 29 1 12 16 35 9 COMMAND Keyswitch On STATUS Auto Mode COMMAND Rectifier Commanded On STATUS Inverter On STATUS Rectifier On STATUS...

Page 115: ... source The Battery area displays the DC voltage V and the DC current I Figure 13 5 shows a sample Meters printout Input Output Bypass Battery VAB 480 VBC VCA KW 505 KVA 530 IA IB IC FREQ 60 0 PF 0 95 V 540 I 0 640 480 480 640 640 VAB 480 VBC VCA 480 480 IA IB IC 480 480 480 IN 0 VAB 480 VBC VCA 480 480 FREQ 60 0 KVA 400 KW 320 PF 0 80 Uninterruptible Power System UPS System Normal Alarm None Noti...

Page 116: ...mpted to enter the password for this mode Please Enter Password The default password is POWER1 You may modify this password using the change password function in the following menu When the valid password is entered the main menu will be displayed Program Mode Main Menu 1 Program Building Alarms 2 Program Unit Name 3 Adjust Output Voltage 4 Change Password 5 Battery Test Setup 6 Modify Low Battery...

Page 117: ... Disable Building Alarm Number Enter CR for No Change Enter Selection Where Function indicates the function the building alarm is being programmed for The line following the Enabled Building Alarm Number s label indicates which building alarms are currently enabled for the function In this example Building Alarms 1 and 4 are enabled A building alarm can only be programmed for one special function ...

Page 118: ... following will be displayed Building Alarm Active Message Building Alarm 1 default message Enter New Message or CR for No Change At this level you can enter a custom message 30 characters maximum to display when Building Alarm 1 is activated If a custom message is entered to activate the building alarm a custom message should also be entered to deactivate After the message or a carriage return is...

Page 119: ...minal mode If a change is desired the new unit name should be entered at the prompt The unit name is 45 characters maximum and includes spaces and any punctuation If the user wants to center the text portion of the name the appropriate number of leading spaces should be included when entered 13 6 6 Change Password If Change Password is selected from the main menu the following menu is displayed Ch...

Page 120: ...Day of Week Sunday 1 1 7 Enter Week of Month 1 5 Enter Hour of Test 0 23 Enter Minute of Test 0 59 NOTE Follow each entry with CR CR with no entry will return to Battery Test Setup Menu Enter the information at the prompt with a carriage return to schedule the battery test If entry 4 is selected from the Battery Test Setup menu you will be prompted to enter Y to cancel all pending tests This selec...

Page 121: ... service personnel to calibrate system meters Factory test engineers calibrate the SBM meters prior to shipping so the SBM arrives at your site correctly calibrated After use field service personnel may need to use Calibration mode to recalibrate one or more meter settings NOTE Calibration mode is for use by service personnel ONLY To prevent inadvertent modification this mode can be accessed only ...

Page 122: ...1 13 16 EATON Powerware 9315 Parallel Capacity Redundant System 164201150 Rev E www powerware com This Page Intentionally Left Blank ...

Page 123: ...l an external modem refer to Chapter 13 Serial Communications Connection to the SBM is made when a user calls the SBM on the phone The user has exactly the same capabilities as if using a terminal connected directly to the SBM RS 232 port Remote Notification differs from the basic Terminal mode with the addition of Call Answer Call Out and Housekeeping functions The Call Answer function allows the...

Page 124: ...Answer into Terminal mode Call Out to a remote terminal and Housekeeping Remote Notification also allows access to any functions available in the Terminal mode from a remote computer or terminal 14 3 1 Call Answer When the modem receives a call the SBM is alerted to wait for a connect signal from the modem When the modem answers and finishes handshaking the SBM acknowledges the modem connect signa...

Page 125: ... nnn space mmm LF CR where nnn UPS_Remote_Notification Default 40 characters maximum space ASCII space character 0x20 mmm Event message for notice or alarm 40 characters maximum LF ASCII line feed character 0x0A CR ASCII carriage return character 0x0D If calling a pager service and the service answers the modem can delay momentarily and before dialing the pager number Refer to Configuring the Mode...

Page 126: ... and Call Out is enabled 14 4 Hardware Requirements The following hardware components are required to connect the Remote Notification function Modem Basic external PC modem supporting the following AT commands T Tone dialing F Load factory defaults E0 Do not echo characters in command state N0 Handshake only at speed specified by S37 Q0 Return result codes in both originate and answer mode V0 Disp...

Page 127: ...ram on the computer Test the connection to the modem by typing A T and ENTER The modem should respond with either OK or 0 zero If the modem does not respond consult the modem manufacturer s manual to confirm your setup If the modem still does not respond then seek technical assistance from your modem manufacturer After connection perform Basic Modem Configuration and the remaining sections of this...

Page 128: ...dd a in the number anywhere that a delay is needed This will cause a one second delay More than one delay may be added to the number for example enter AT Z0 T 9 1 Area Code Phone Number 4 To program a group one number key in A T Z 0 zero T xxxxxxx then press ENTER 5 To program a group two number key in A T Z 1 T xxxxxxx then press ENTER 6 Confirm that the modem responds with OK or 0 zero 7 Key in ...

Page 129: ... than one delay may be added to the number for example enter AT Z0 T 9 1 Area Code Phone Number Pauses Numeric Message For areas with pulse dialing the T should be inserted before the numeric message to switch to tone dialing The numeric message can only be delivered using tone dialing Keying in the pound character at the end of the numeric message is very important It prevents the pager service f...

Page 130: ...ters that require keying in prior to pressing ENTER 1 Connect the modem to the PC as described in the modem manufacturer s manual 2 Key in A T then press ENTER 3 Confirm that the modem responds with OK or 0 zero 4 Key in A T E 0 zero then press ENTER 5 Confirm that the modem responds with OK or 0 zero 6 Key in A T then press ENTER 8 Confirm that the modem responds with OK or 0 zero and that the AT...

Page 131: ...setup screen and configure Port 2 as follows NOTE The modem should be connected to the SBM as described in the modem manufacturer s manual before configuring the SBM communications port MODE Remote Notify RATE The baud rate at which the modem will communicate to other modems 2400 baud DATA STOP 8 1 Standard 8 data bits 1 stop bit no parity HANDSHAKING Disabled SAVE Yes To save new configuration Th...

Page 132: ...315 Parallel Capacity Redundant System 164201150 Rev E www powerware com 14 6 1 User Selected Events Insert a check at each alarm or notice in the appropriate Group 1 or Group 2 block to indicate the configuration of your SBM ...

Page 133: ...de Inverter Failure Bypass Over Frequency Inverter Over Frequency Bypass Under Frequency Inverter Phase Rotation Input Breaker CB1 Open Inverter Setup Required Battery Contactor K2 Open Inverter Under Frequency Battery DC Under Voltage 100 Overload Shutdown Battery Discharged 125 Overload Shutdown Battery Not Charged Over Temperature Shutdown Battery Voltage Low Shutdown Imminent Phase A Current L...

Page 134: ...erature Warning DC Voltage Low Rectifier Calibration Required Equalizing Battery Rectifier DC Over Voltage Input AC Over Voltage Rectifier DC Under Voltage Input AC Under Voltage Rectifier Failure Input Over Frequency Rectifier Setup Required Input Transient Temperature Sensor Failure Input Under Frequency Input Battery Current Limit Logic Power Failed Power Supply Over Voltage Power Supply Under ...

Page 135: ...y Time Low Monitor Calibration Required Building Alarm 1 Active Monitor Setup Required Building Alarm 2 Active Overload Warning Building Alarm 3 Active Power Supply Failure Building Alarm 4 Active Building Alarm 5 Active Building Alarm 6 Active Inverter Network Down Monitor Logic Pwr Fail Monitor Network Down No Active Events Output AC Over Voltage Output AC Under Voltage Output Over Frequency Out...

Page 136: ......

Page 137: ... and bypass power has been removed After disconnecting the utility power and the DC power authorized service personnel should wait at least 5 minutes before attempting internal access to the UPS module WARNING Servicing and maintenance should be performed by service qualified personnel only WARNING LETHAL VOLTAGE PRESENT This unit should not be operated with the cabinet doors open or protective co...

Page 138: ...and maintenance When replacing batteries use the same number of sealed lead acid batteries Proper disposal of batteries is required Refer to your local codes for disposal requirements WARNING HAZARDOUS WASTE Do not incinerate or dispose of batteries indiscriminately Observe local and national code WARNING Do not dispose of batteries in a fire They may explode Do not open or mutilate the battery or...

Page 139: ... the parameters specified in Chapter 16 Product Specifications Ensure the SBM and UPS modules are in Normal mode Normal status indicator is lit If alarm lamps are lit or the Normal status indicators are not lit contact Powerware Customer Support Perform the following checks MONTHLY Ensure all status indicator lamps are operative Press the and pushbuttons simultaneously to test the lamps Monitor sy...

Page 140: ...e Corporation gives you a competent working knowledge of the Parallel Capacity Redundant system operation and teaches you how to perform first level corrective maintenance For more information about training and other services contact the Powerware Corporation Training Coordinator in Raleigh North Carolina or call Powerware Corporation field service at 1 800 843 9433 ...

Page 141: ...M 800 Powerware 9315 1200 SBM 1000 Powerware 9315 1200 SBM 1200 Powerware 9315 2000 SBM 1200 Powerware 9315 2000 SBM 1600 Powerware 9315 2000 SBM 2000 The following sections detail the input output and environmental specifications for the SBM 16 2 SBM Input Input Voltage UPM Dependent 480 VAC nominal 60 Hz only 400 VAC nominal 50 60 Hz only 600 VAC nominal 60 Hz only Input Frequency Range 3 Hz of ...

Page 142: ...ccordance with breaker manufacturer specifications 16 4 Environmental Specifications Operating Temperature 0 to 40 C without derating The recommended operating temperature is 25 C Operating Altitude Maximum 1500m 5000 ft at 40_C without derating Storage Temperature 20 to 70 C prolonged storage above 40 C will cause rapid battery self discharge Relative Humidity operating and storage 95 maximum non...

Page 143: ...tem 164201150 5 1200A System Bypass Module SBM 164201150 6 Location of 1200A SBM Terminals 164201150 7 1200A System Maintenance Bypass SMB 164201150 8 Location of 1200A SMB Terminals 164201150 9 2000A System Bypass Module 164201150 10 Location of 2000A SBM Terminals 164201150 11 2000A System Maintenance Bypass SMB 164201150 12 Location of 2000A SMB Terminals 164201150 13 SBM Customer Interface Pan...

Page 144: ...from SBM or optional SMB to Critical Load Full Load Current minimum conductor size 3O 1 Neutral 1 gnd number per O AWG or kcmil ea 500 2 400 3 350 4 500 4 Read and understand the following notes while planning your installation 1 Refer to national and local electrical codes for acceptable external wiring practices 2 Material and labor for external wiring requirements are to be provided by designat...

Page 145: ...ad Current minimum conductor size 3O 1 Neutral 1 gnd number per O AWG or kcmil ea Bus Plate Supplied by Power ware Bus Plate Supplied by Power ware Bus Plate Supplied by Power ware AC OUTPUT AC Output from SBM or optional SMB to Critical Load Full Load Current minimum conductor size 3 O 1 Neutral 1 gnd number per O AWG or kcmil ea 500 4 400 6 500 6 7 Non linear loads can create neutral currents th...

Page 146: ...3 Phase C 8 2 bolt mounting 76 56 1 2 AC Input from SBM to optional SMB E8 Phase A 4 4 0 500 kcmil Pressure Termination 42 4 32 2 3 8 E9 Phase B 4 4 0 500 kcmil Pressure Termination 42 4 32 2 3 8 E10 Phase C 4 4 0 500 kcmil Pressure Termination 42 4 32 2 3 8 AC Input to optional SMB Bypass E1 Phase A 4 4 0 500 kcmil Pressure Termination 42 4 32 2 3 8 E2 Phase B 4 4 0 500 kcmil Pressure Termination...

Page 147: ...t mounting 76 56 1 2 E3 Phase C 6 2 bolt mounting 76 56 1 2 AC Input to optional SMB Bypass Separate Feed E1 Phase A 10 2 bolt mounting 76 56 1 2 E2 Phase B 10 2 bolt mounting 76 56 1 2 E3 Phase C 10 2 bolt mounting 76 56 1 2 AC Output from SBM to Critical Load E5 Phase A 6 2 bolt mounting 76 56 1 2 E6 Phase B 6 2 bolt mounting 76 56 1 2 E7 Phase C 6 2 bolt mounting 76 56 1 2 AC Output from option...

Page 148: ...have a AT trip ratings and a maximum Amp Interrupting Capability KAIC as shown in Table F Table F SBM Breaker Trip Ratings and Amp Interrupting Capability Powerware 9315 System Bypass module SBM Model 600 800 1000 1200 1600 2000 All Models Trip Rating KAIC 1200A SBM 600 800 1000 1200 N A N A 35 2000A SBM N A N A N A 1200 1600 2000 65 15 Output overcurrent protection and output disconnect switch ar...

Page 149: ...ecommended Operating Range 20 25 C 68 77 F Maximum Relative Humidity 95 noncondensing Table H Equipment Weight and Point Loading Weight Point Loading Component Kg lb Kg lb 1200A System Bypass Module 530 1170 N A 2000A System Bypass Module 1227 2700 N A 1200A System Maintenance Bypass 204 450 N A 2000A System Maintenance Bypass 454 1000 N A 23 The 1200A and 2000A System Maintenance Bypass SMB cabin...

Page 150: ... UPM cabinet 3 Refer to the Powerware 9315 UPS Installation manual provided with the UPMs for UPM battery and optional input transformer installation information TYPICAL PARALLEL CAPACITY REDUNDANT SYSTEM WITH 1200A SBM SEPARATE BATTERY SYSTEM 1 1 1 1 3 4 1 3 4 UTILITY POWER INPUT TO UPM SBM OUTPUT TO CRITICAL LOAD UTILITY POWER INPUT TO BYPASS BUS 1 of 2 5 5 POWERNET DUAL REDUNDANT NETWORK SBM IN...

Page 151: ...RITICAL LOAD UTILITY POWER INPUT TO BYPASS BUS 5 POWERNET DUAL REDUNDANT NETWORK SBM INTERFACE TERMINAL BLOCK TB1 UPM INTERFACE TERMINAL BLOCK TB1 2 UPM OUTPUT TO SBM INPUT NOTE 1 Accommodates one to eight UPMs Four UPM system shown 2 The input transformer cabinet may be installed on either the left or the right side of the UPM cabinet 3 Refer to the Powerware 9315 UPS Installation manual provided...

Page 152: ...CRITICAL LOAD UTILITY POWER INPUT TO BYPASS BUS 5 POWERNET DUAL REDUNDANT NETWORK SBM INTERFACE TERMINAL BLOCK TB1 UPM INTERFACE TERMINAL BLOCK TB1 2 UPM OUTPUT TO SBM INPUT NOTE 1 Accommodates one to eight UPMs Four UPM system shown 2 The input transformer cabinet may be installed on either the left or the right side of the UPM cabinet 3 Refer to the Powerware 9315 UPS Installation manual provide...

Page 153: ...RITICAL LOAD UTILITY POWER INPUT TO BYPASS BUS 5 POWERNET DUAL REDUNDANT NETWORK SBM INTERFACE TERMINAL BLOCK TB1 UPM INTERFACE TERMINAL BLOCK TB1 2 UPM OUTPUT TO SBM INPUT 2 NOTE 1 Accommodates one to eight UPMs Four UPM system shown 2 The input transformer cabinet may be installed on either the left or the right side of the UPM cabinet 3 Refer to the Powerware 9315 UPS Installation manual provid...

Page 154: ... E5 E4 E5 E4 E5 E4 E5 E9 E12 E9 E12 E9 E12 E9 E12 E8 E10 E5 E7 UPS OUTPUT TO CRITICAL LOAD 3 PHASE 3 OR 4 WIRE AC INPUT TO MODULE 4 3 PHASE 3 WIRE AC INPUT TO MODULE 3 3 PHASE 3 WIRE AC INPUT TO MODULE 2 3 PHASE 3 WIRE AC INPUT TO MODULE 1 3 PHASE 3 WIRE AC INPUT TO SYSTEM BYPASS 3 PHASE 3 OR 4 WIRE AC INPUT TO MAINT BYPASS 3 PHASE 3 OR 4 WIRE E23 E25 E23 E25 E23 E25 E23 E25 E26 E28 E26 E28 E26 E2...

Page 155: ...E5 E4 E5 E4 E5 E4 E5 E9 E12 E9 E12 E9 E12 E9 E12 E8 E10 E5 E7 UPS OUTPUT TO CRITICAL LOAD 3 PHASE 3 OR 4 WIRE AC INPUT TO MODULE 4 3 PHASE 3 WIRE AC INPUT TO MODULE 3 3 PHASE 3 WIRE AC INPUT TO MODULE 2 3 PHASE 3 WIRE AC INPUT TO MODULE 1 3 PHASE 3 WIRE AC INPUT TO SYSTEM BYPASS 3 PHASE 3 OR 4 WIRE AC INPUT TO MAINT BYPASS 3 PHASE 3 OR 4 WIRE E26 E28 E26 E28 E26 E28 E26 E28 E23 E25 E23 E25 E23 E25...

Page 156: ...neutral feeder must be installed when the output neutral is used If no bypass neutral is installed the output neutral is to be bonded to the chassis in the SBM through the minimum size copper conductor listed in Table I In either case fully rated neutral conductors are to be run from the output of each UPM to the neutral buss bar inside the SBM Table I Minimum Size Copper Bonding Jumper SBM Model ...

Page 157: ...city Redundant System 164201150 Rev E www powerware com Dimensions are in millimeters inches DESCRIPTION DRAWING NO SHEET 164201150 5 1 of 2 1200A SYSTEM BYPASS MODULE 1200A SBM FRONT VIEW 1879 60 90 79 863 60 74 00 3 57 34 00 CONTROL PANEL ...

Page 158: ...RAWING NO SHEET 164201150 5 2 of 2 1200A SYSTEM BYPASS MODULE 1200A SBM TOP VIEW 1200A SBM SIDE VIEW ACCESS AREA FOR CUSTOMER INTERFACE PANEL CONTROL WIRING CONDUIT LANDING AREA INPUT OUTPUT AND BYPASS CONDUIT LANDING PLATE 587 38 247 65 425 45 587 38 530 23 1016 00 FRONT 1016 00 1879 60 90 79 3 57 74 00 40 00 40 00 20 88 23 13 16 75 9 75 23 13 ...

Page 159: ...164201150 6 1 of 4 LOCATION OF 1200A SBM TERMINALS NEUTRAL CONNECTION E4 UPM OUTPUT BREAKER STATIC SWITCH GROUND BACKFEED SYSTEM PROTECTION BREAKER BYPASS BREAKER NOTE Refer to the Powerware 9315 UPS Installation manual provided with the UPMs for UPM battery and optional input transformer terminal locations LIFTING EYE 120V 0 2A MBM KEYSWITCH CONVENIENCE OUTLET ...

Page 160: ...RAL GROUND E1 E2 E3 18 11 14 00 AC INPUT FROM UPMs AC OUTPUT TO E8 E9 E10 CRITICAL LOAD E5 E6 E7 CONNECTION E4 A B C A B C A B C NEUTRAL 28 58 101 60 INPUT 50 80 14 22 25 40 44 45 1 75 TYP 1 00 0 56 TYP 2 00 GROUND 0 25 THICK 44 45 1 75 TYP 14 22 0 56 TYP 44 45 1 75 TYP 4 00 1 13 CONNECTION E4 0 50 THICK NOTE Refer to the Powerware 9315 UPS Installation manual provided with the UPMs for UPM batter...

Page 161: ...inches DESCRIPTION DRAWING NO SHEET 164201150 6 3 of 4 LOCATION OF 1200A SBM TERMINALS CUSTOMER INTERFACE PANEL AC INPUT AC OUTPUT AC INPUT TO BYPASS TO CRITICAL LOAD FROM UPMs NOTE Refer to the Powerware 9315 UPS Installation manual provided with the UPMs for UPM battery and optional input transformer terminal locations REAR ...

Page 162: ...L A1 50 80 AC INPUT TO AC OUTPUT ABB S7 1200A TO CRITICAL LOAD BYPASS AND AC INPUT FROM UPMs 101 60 28 58 14 29 44 45 25 40 1 00 typ 1 75 typ 0 56 typ 1 13 4 00 2 00 typ FRONT AC INPUT TO BYPASS E1 E2 E3 AC OUTPUT TO CRITICAL LOAD E8 E9 E10 AC INPUT FROM UPMs E5 E6 E7 0 50 THICK A B C A B C A B C NOTE Refer to the Powerware 9315 UPS Installation manual provided with the UPMs for UPM battery and op...

Page 163: ... in millimeters inches DESCRIPTION DRAWING NO SHEET 1 of 2 1200A SYSTEM MAINTENANCE BYPASS SMB FRONT VIEW 164201150 7 The 1200A System Maintenance Bypass SMB is not designed for stand alone operation and therefore cannot be remotely located The SMB must be located and attached to the right side of the SBM NOTE ...

Page 164: ...VIEW 1016 00 1879 60 90 79 3 57 74 00 40 00 TOP VIEW 1016 00 40 00 INPUT OUTPUT AND CONTROL WIRING CONDUIT LANDING PLATE 1200A SYSTEM MAINTENANCE BYPASS SMB 164201150 7 The 1200A System Maintenance Bypass SMB is not designed for stand alone operation and therefore cannot be remotely located The SMB must be located and attached to the right side of the SBM NOTE LIFTING EYE ...

Page 165: ... NO SHEET 164201150 8 1 of 3 LOCATION OF 1200A SMB TERMINALS The 1200A System Maintenance Bypass SMB is not designed for stand alone operation and therefore cannot be remotely located The SMB must be located and attached to the right side of the SBM NOTE MAINTENANCE MAINTENANCE AC INPUT FROM SBM BYPASS BREAKER MBP ISOLATION BREAKER MIS E8 E9 E10 A B C ...

Page 166: ... DRAWING NO SHEET 2 of 3 164201150 8 LOCATION OF 1200A SMB TERMINALS The 1200A System Maintenance Bypass SMB is not designed for stand alone operation and therefore cannot be remotely located The SMB must be located and attached to the right side of the SBM NOTE FRONT AC OUTPUT TO CRITICAL LOAD E5 E6 E7 A B C AC INPUT TO BYPASS E1 E2 E3 A B C ...

Page 167: ...WING NO SHEET 3 of 3 164201150 8 LOCATION OF 1200A SMB TERMINALS The 1200A System Maintenance Bypass SMB is not designed for stand alone operation and therefore cannot be remotely located The SMB must be located and attached to the right side of the SBM NOTE FRONT AC INPUT TO BYPASS AC INPUT FROM SBM PREWIRED AT FACTORY AC OUTPUT TO CRITICAL LOAD ...

Page 168: ... E www powerware com Dimensions are in millimeters inches DESCRIPTION DRAWING NO SHEET 164201150 9 1 of 2 2000A SYSTEM BYPASS MODULE 2000A SBM FRONT VIEW 1727 20 90 79 2082 80 3 57 82 00 68 00 UPM OUTPUT BREAKER BACKFEED PROTECTION BREAKER SYSTEM BYPASS BREAKER CONTROL PANEL ...

Page 169: ...IPTION DRAWING NO SHEET 164201150 9 2 of 2 2000A SYSTEM BYPASS MODULE 2000A SBM TOP VIEW 2000A SBM SIDE VIEW FRONT FRONT 2082 80 1034 28 1016 00 40 00 40 72 82 00 BYPASS CONDUIT OUTPUT CONDUIT INPUT CONDUIT LANDING PLATE LANDING PLATE LANDING PLATE CONTROL WIRING ACCESS AREA FOR CUSTOMER INTERFACE PANEL CONDUIT LANDING AREA 1016 00 40 00 ...

Page 170: ... E8 E9 E10 A B C DESCRIPTION DRAWING NO SHEET 1 of 6 AC OUTPUT TO CRITICAL LOAD E5 E6 E7 164201150 10 LOCATION OF 2000A SBM TERMINALS GROUND NEUTRAL E4 NOTE Refer to the Powerware 9315 UPS Installation manual provided with the UPMs for UPM battery and optional input transformer and terminal locations FRONT VIEW 120V 0 2A SMB KEY SWITCH CONVENIENCE OUTLET ...

Page 171: ... OF 2000A SBM TERMINALS GROUND NEUTRAL E4 FBP STATIC SWITCH SECTION CBP SECTION CBS SECTION REAR VIEW NEUTRAL 28 58 101 60 INPUT 50 80 14 22 25 40 44 45 1 75 TYP 1 00 0 56 TYP 2 00 GROUND 0 25 THICK 44 45 1 75 TYP 14 22 0 56 TYP 44 45 1 75 TYP 4 00 1 13 CONNECTION E4 0 50 THICK 332 56 13 09 190 50 7 50 LIFTING EYE NOTE Refer to the Powerware 9315 UPS Installation manual provided with the UPMs for ...

Page 172: ...UPMs E8 E9 E10 A B C DESCRIPTION DRAWING NO SHEET 3 of 6 AC OUTPUT TO CRITICAL LOAD E5 E6 E7 A B C 164201150 10 LOCATION OF 2000A SBM TERMINALS CUSTOMER INTERFACE PANEL CBS CBP FBP TOP VIEW NOTE Refer to the Powerware 9315 UPS Installation manual provided with the UPMs for UPM battery and optional input transformer and terminal locations FRONT ...

Page 173: ...LS FRONT LEFT SIDE VIEW POWERNODE PANEL A1 AC INPUT FROM UPMs E8 E9 E10 A B C 50 80 101 60 28 58 14 29 44 45 25 40 1 00 typ 1 75 typ 0 56 typ 1 13 4 00 2 00 typ MODULE INPUT E8 E9 E10 0 50 THICK BUS 1117 60 44 00 NOTE Refer to the Powerware 9315 UPS Installation manual provided with the UPMs for UPM battery and optional input transformer and terminal locations CBS SECTION ...

Page 174: ...50 10 LOCATION OF 2000A SBM TERMINALS FRONT CENTER SECTION VIEW VIEWED FROM LEFT SIDE CBB SECTION 942 34 37 10 50 80 101 60 28 58 14 29 44 45 25 40 1 00 typ 1 75 typ 0 56 typ 1 13 4 00 2 00 typ CRITICAL LOAD E5 E6 E7 0 50 THICK BUS NOTE Refer to the Powerware 9315 UPS Installation manual provided with the UPMs for UPM battery and optional input transformer and terminal locations ...

Page 175: ...01150 10 LOCATION OF 2000A SBM TERMINALS FRONT RIGHT SIDE VIEW FBP STATIC SWITCH SECTION 50 80 101 60 28 58 14 29 44 45 25 40 1 00 typ 1 75 typ 0 56 typ 1 13 4 00 2 00 typ BYPASS INPUT E1 E2 E3 0 50 THICK BUS 482 60 19 00 NOTE Refer to the Powerware 9315 UPS Installation manual provided with the UPMs for UPM battery and optional input transformer and terminal locations ...

Page 176: ... NO SHEET 1 of 2 164201150 11 2000A SYSTEM MAINTENANCE BYPASS SMB The 2000A System Maintenance Bypass SMB is not designed for stand alone operation and therefore cannot be remotely located The SMB must be located and attached to the right side of the SBM NOTE MAINTENANCE BYPASS BREAKER MAINTENANCE ISOLATION BREAKER ...

Page 177: ... DRAWING NO SHEET 2 of 2 2000A SYSTEM MAINTENANCE BYPASS SMB 164201150 11 INPUT OUTPUT AND CONTROL WIRING CONDUIT LANDING PLATE FRONT The 2000A System Maintenance Bypass SMB is not designed for stand alone operation and therefore cannot be remotely located The SMB must be located and attached to the right side of the SBM NOTE LIFTING EYE FRONT ...

Page 178: ...EET 1 of 4 LOCATION OF 2000A SMB TERMINALS 164201150 12 The 2000A System Maintenance Bypass SMB is not designed for stand alone operation and therefore cannot be remotely located The SMB must be located and attached to the right side of the SBM NOTE LIFTING EYE MAINTENANCE BYPASS BREAKER MAINTENANCE ISOLATION BREAKER NEUTRAL CONNECTION E4 GROUND CONNECTION ...

Page 179: ...e 2000A System Maintenance Bypass SMB is not designed for stand alone operation and therefore cannot be remotely located The SMB must be located and attached to the right side of the SBM NOTE AC INPUT TO BYPASS BUS PLATE CONNECTION OR SEPARATE FEED E3 E2 E1 C B A NEUTRAL CONNECTION E4 GROUND CONNECTION BUS PLATE AC INPUT FROM SBM BUS PLATE CONNECTION ONLY E10 E9 E11 C B A AC OUTPUT TO CRITICAL LOA...

Page 180: ...000A SMB TERMINALS 164201150 12 The 1200A System Maintenance Bypass SMB is not designed for stand alone operation and therefore cannot be remotely located The SMB must be located and attached to the right side of the SBM NOTE FRONT OUTPUT TO CRITICAL LOAD E5 E6 E7 A B C AC INPUT TO BYPASS SEPARATE FEED E1 E2 E3 A B C MAINTENANCE BYPASS BREAKER MBP MAINTENANCE ISOLATION BREAKER MIB ...

Page 181: ...nches DESCRIPTION DRAWING NO SHEET 4 of 4 LOCATION OF 2000A SMB TERMINALS 164201150 12 The 1200A System Maintenance Bypass SMB is not designed for stand alone operation and therefore cannot be remotely located The SMB must be located and attached to the right side of the SBM NOTE FRONT AC OUTPUT TO CRITICAL LOAD E5 E6 E7 A B C ...

Page 182: ...k in separate conduits The wire should be rated at 24 volts 1 amp minimum The recommended wire for the PowerNet network is shielded 20 gauge twisted pair Belden 8762 Powerware Part Number 175090703 or equivalent 4 Control wiring run may not exceed 100 meters 5 Refer to sheet 2 for typical control wiring routing Use Arrangement C for a more robust network 6 Connect control wiring and terminating re...

Page 183: ...3 UPM 4 SBM TERMINATION POINTS TERMINATION POINTS TYPICAL POWERNET NETWORK Arrangement A 164201150 13 CHANNEL A CHANNEL B UPM 1 UPM 2 UPM 3 UPM 4 SBM TERMINATION POINTS TERMINATION POINTS Arrangement B CHANNEL A CHANNEL B UPM 1 UPM 2 UPM 3 UPM 4 SBM TERMINATION POINT TERMINATION POINTS Arrangement C Robust Network Routing CHANNEL A CHANNEL B WIRING AND TERMINATIONS CHAN B TERMINATION POINT CHAN A ...

Page 184: ... PowerNet Interface Terminal Block 10 1 Terminating Resistor Location Channel A 120 ohm 1 4 watt 5 Terminating Resistor Channel B 120 ohm 1 4 watt 5 Terminating Resistor 164201150 13 A 42 EATON Powerware 9315 Parallel Capacity Redundant System 164201150 Rev E www powerware com ...

Page 185: ...Compression Terminal Block with removable customer wiring plug Remote EPO Building Alarms 1 through 3 TB3 Compression Terminal Block with removable customer wiring plug Building Alarms 4 through 6 TB4 Compression Terminal Block with removable customer wiring plug On UPS Monitoring On Bypass Monitoring Summary Alarm Notice Contact TB6 Compression Terminal Block Optional Powerware 9315 Sync Control ...

Page 186: ... UPS modules 10 EPO TO UPS MODULE TB2 1 REMOTE EPO Contacts used to activate remote EPO of SBM and UPS 2 REMOTE EPO RTN 3 NOT USED 4 NOT USED 5 BLDG ALARM 1 Programmable UPS alarm Activated by a remote contact closure 6 BLDG ALARM 1 RTN Programmable UPS alarm Activated by a remote contact closure 7 BLDG ALARM 2 Programmable UPS alarm Activated by a remote contact closure 8 BLDG ALARM 2 RTN 9 BLDG ...

Page 187: ...Bypass status of Parallel Capacity Redundant System 4 ON BYPASS RTN 5 RELAY 1 NC General purpose NO and NC relay contacts 6 RELAY 1 NO 7 RELAY 1 RTN 8 RELAY 2 NC General purpose NO and NC relay contacts 9 RELAY 2 NO 10 RELAY 2 RTN TB6 1 Bypass A Optional Powerware 9315 Sync Control Control Connections 2 Bypass B 3 Bypass C 4 Sync Reference A 5 Sync Reference B 6 Sync Reference C 7 Output A 8 Outpu...

Page 188: ... 164201150 13 A 46 EATON Powerware 9315 Parallel Capacity Redundant System 164201150 Rev E www powerware com Table L Summary Alarm Relay Contacts 14 15 13 11 12 10 RELAY 1 TB2 RELAY 2 CONTACT RATING Maximum Switched Voltage 32 VAC 42 VDC Maximum Carrying Current 1A ...

Page 189: ...ork in separate conduits The wire should be rated at 24 volts 1 amp minimum The recommended wire for the PowerNet network is shielded 22 gauge twisted pair Belden 8761 or equivalent 4 Control wiring run may not exceed 100 meters 5 Connect control wiring and terminating resistor if applicable to the removable portion of the terminal block 6 Terminate each redundant PowerNet network at the end modul...

Page 190: ... INTERFACE PANEL POWERWARE 9315 200 TO 500 UPMs 2 of 4 Powerware 9315 200 kVA 300 kVA PowerNet Interface Panel Location 164201150 14 INTERFACE PANEL A 48 EATON Powerware 9315 Parallel Capacity Redundant System 164201150 Rev E www powerware com ...

Page 191: ... INTERFACE PANEL POWERWARE 9315 200 TO 500 UPMs 3 of 4 164201150 14 Powerware 9315 400 kVA 500 kVA PowerNet Interface Panel Location INTERFACE PANEL A 49 EATON Powerware 9315 Parallel Capacity Redundant System 164201150 Rev E www powerware com ...

Page 192: ...PowerNet Channel B PowerNet EPO to UPM Optional Table N UPM PowerNet Interface Panel Inputs and Outputs Terminal Block TB Pin Name Description PowerNet 1 CHANNEL A POWERNET HIGH Channel A connection of PowerNet from SBM Used to control and monitor UPMs 2 CHANNEL A POWERNET LOW 3 CHANNEL A POWERNET GND 4 NOT USED 5 NOT USED 6 CHANNEL B POWERNET HIGH Channel B connection of PowerNet from SBM Used to...

Page 193: ...m the power wiring Install the twisted pair of each redundant PowerNet network in separate conduits The wire should be rated at 24 volts 1 amp minimum The recommended wire for the PowerNet network is shielded 20 gauge twisted pair Belden 8762 or equivalent The recommended wire for the power supplies is 14 gauge twisted pair 4 Control wiring run may not exceed 100 meters 5 Connect control wiring to...

Page 194: ...164201150 15 Powerware 9315 750 CAN A and CAN B Interface Location CUSTOMER INTERFACE CAN A CAN B UPM CAN INTERFACE POWERWARE 9315 625 750 UPMs A 52 EATON Powerware 9315 Parallel Capacity Redundant System 164201150 Rev E www powerware com ...

Page 195: ...d monitor UPMs A1TB1 2 CAN A J2 4 CHANNEL A POWERNET LOW A1TB1 3 CAN A J2 5 CHANNEL A POWERNET GND A1TB7 1 CAN A J2 1 CONTROL POWER 12VDC Control power connection for Channel A CAN Logic Board from SBM A1TB7 2 CAN A J2 2 CONTROL POWER GND A1TB1 6 CAN B J2 3 CHANNEL B POWERNET HIGH Channel B connection of PowerNet from SBM Used to control and monitor UPMs A1TB1 7 CAN B J2 4 CHANNEL B POWERNET LOW A...

Page 196: ...to the modules from the SBM 3 Use Class 1 wiring methods as defined by the NEC for control wiring Install the control wiring in separate conduit from the power wiring The wire should be rated at 24 volts 1 amp minimum 4 Refer to Table P of this drawing and to applicable chapters for information about installing control remote EPO 5 Refer to drawings 164201150 5 and 164201150 9 for location of the ...

Page 197: ... 164201150 Rev E www powerware com 114 3 4 50 115 8 4 56 11 9 0 47 95 3 3 75 SQUARE 88 9 3 50 Knockout pattern typ 5 sides Dimensions are in millimeters inches DESCRIPTION DRAWING NO SHEET 164201150 16 REMOTE EMERGENCY POWER OFF 2 of 2 TO SBM TO OTHER EQUIPMENT ...

Page 198: ... MAX DISTANCE BETWEEN REMOTE MONITOR AND SBM NOT TO EXCEED 500 FEET 41 1 1 62 25 4 1 00 190 5 7 50 88 9 3 50 215 9 8 50 100 1 3 94 74 7 2 94 171 5 6 75 KNOCKOUTS PROVIDED ON FIVE SURFACES BE TWISTED FLUSH MOUNT SURFACE FOR HANGING 14 18 gauge Dimensions are in millimeters inches MOUNT DESCRIPTION DRAWING NO SHEET 164201150 17 REMOTE MONITOR PANEL 1 of 1 285 7 11 25 7 75 75 197 47 8 50 216 58 ...

Page 199: ...NUES AT UPS MAX WIRE SIZE NO 14 AWG MIN WIRE SIZE NO 18 AWG Relay Interface Module 88 9 3 50 190 5 7 50 215 9 8 5 196 8 7 75 FOR HANGING WIRING CONDUIT AND WIRING SUPPLIED BY CUSTOMER Maximum distance between RIM and SBM not to exceed 500 feet Wires must be twisted Dimensions are in millimeters inches DESCRIPTION DRAWING NO SHEET 164201150 18 RELAY INTERFACE MODULE 1 of 2 ...

Page 200: ...0 Rev E www powerware com 15 PIN D SUB CONNECTORS 25 4 1 00 KNOCKOUTS PROVIDED ON FIVE SURFACES 285 7 11 25 273 1 10 75 215 9 8 50 171 5 6 75 74 6 2 94 100 0 3 94 Dimensions are in millimeters inches DESCRIPTION DRAWING NO SHEET 164201150 18 RELAY INTERFACE MODULE 2 of 2 ...

Page 201: ...MER MAX DISTANCE BETWEEN REMOTE MONITOR AND SBM NOT TO EXCEED 500 FEET 41 1 1 62 25 4 1 00 190 5 7 50 88 9 3 50 7 75 215 9 8 50 100 1 3 94 74 7 2 94 171 5 6 75 KNOCKOUTS PROVIDED ON FIVE SURFACES BE TWISTED FLUSH MOUNT SURFACE FOR HANGING Dimensions are in millimeters inches MOUNT DESCRIPTION DRAWING NO SHEET 164201150 19 SUPERVISORY CONTACT MODULE 1 of 1 285 7 11 25 75 197 47 8 50 216 58 ...

Page 202: ...A 60 EATON Powerware 9315 Parallel Capacity Redundant System 164201150 Rev E www powerware com This Page Intentionally Left Blank ...

Page 203: ... commissioning of the Product b if the Product is moved to a new location by someone other than an authorized Eaton Customer Service Engineer in the USA or Agent outside of the USA or c if the Product s serial numbers have been removed or are illegible Any Warranted Items repaired or replaced pursuant to this Warranty will be warranted for the remaining portion of the original Warranty subject to ...

Page 204: ...62 EATON Powerware 9315 Parallel Capacity Redundant System 164201150 Rev E www powerware com This Page Intentionally Left Blank ...

Page 205: ......

Page 206: ...164201150 Rev E 164201150E ...

Reviews: