Parameter
Setting
Description
Spot Heat Protection
checked /
unchecked
This parameter enables the Heat
Protection via using Spot Temperature
Sensor. Spot Temperature sensor must
be enabled in "Temperature Sensor"
page to show this parameter.
Controller Algorithm
PID
/ Alternative PI
Controller algorithm can be selected via
using this parameter.
Proportional Band
1...
30
...255 x 0.1°C
This parameter shown when the
"Controller Algorithm" is selected as
"PID"
Ti
0...
60
...255 min
This parameter shown when the
"Controller Algorithm" is selected as
"PID"
Td
0
...255 min
This parameter shown when the
"Controller Algorithm" is selected as
"PID"
Proportional Gain KP
1…
66
…255
This parameter shown when the
"Controller Algorithm" is selected as
"Alternative PI". Proportional gain of PI
algorithm
Integral Gain Ki
1…
32
…255 /1000
This parameter shown when the
"Controller Algorithm" is selected as
"Alternative PI". Integral gain of PI
algorithm, given value divided by 1000.
Reverse Differential Action
Band
5…
15
…255 x 0.1
This parameter shown when the
"Controller Algorithm" is selected as
"Alternative PI". Reverse Differential
Action Band, given value multiplied by
0.1
Additional Stage Activation Always /
On Difference to Setpoint
Additional Stage can be activated
always or depends to setpoint
difference.
Activation Difference
(Away from Setpoint)
10...
40
...255 x 0.1K
Additional stage will be activated
depends on temperature difference
between current temperature and
setpoint. Given value will be multiplied
with 0.1