Parameter
Function
Description
LCD
from Internal or External Sensor on LCD Screen
External Sensor
Temperature Shown on
KNX
Internal Sensor
This parameter allows to show current temperature
from Internal or External Sensor via KNX object
“Current Temperature.
External Sensor
Spot Temperature
Sensor
changed /
unchanged
This parameters allows the limit the room temperature
via using an external KNX Temperature sensor. It is
using for heat / cool protection. When the heat or cool
limit temperature is reached, the thermostat controller
output will be set to zero. When this parameter is
activated, a
"Spot Temperature Sensor"
object will be
appeared.
Sensor Temp. Unit
Celsius
Spot sensor temp unit can be set as desired. If the
“Same” is selected, the temp unit will be the same as
well as Main Temperature Unit.
Fahrenheit
Same
Heat Limit Temperature 0...
28
...255 K
Heat Protection Value of Spot Temperature Sensor
Cool Limit Temperature 0...
18
...255 K
Cool Protection Value of Spot Temperature Sensor
Limit Protection
Deactivation Hysteresis 1...
20
...255 x0.1K
This parameter determines the heat/cool limit
deactivation hysteresis levels.It prevents switching
between protection and regular mode due to small
temperature changes.
Limit Protection
Activation Delay
0
...65535 s
This parameter determines the switching delay to
protection mode when the limit reached. It prevents
switching between protection and regular mode due to
limit temperature reaching for a short time.
Monitoring Timeout
15...
60
...65535 s
If “SpotTemperature Sensor” object value has not been
updated at the end of the monitoring timeout, the
temperature reading will fallback to Internal Sensor.
Table 24