4.4.4.4.1
Parameters
Parameter
Setting
Description
Control Value
Normal
/ Inverse
Invert the output of the controller. For
example, if normal output is %80, then
inverted output is %20.
Sending of Control Value
Cyclic /
Cyclic and Change
Control values will be sent cyclically only or
cyclical and "Minimum Change" of heating
control value is reached.
Cyclic Sending Interval
1…
5
…255 min
Time period to send heating control value
over “Heating Control Value”
communication object.
Minimum Change
1...
4
...25 %
This parameter appears when the "Sending
of Control Value" is selected as "Cyclic and
Change". It determines minimum control
output change for transmitting the heating
control value.
Maximum Control Signal
0…
100 %
Maximum control signal value.
Minimum Control Signal
0
…100 %
Minimum control signal value
Spot Heat Protection
checked /
unchecked
This parameter enables the Heat
Protection via using Spot Temperature
Sensor. Spot Temperature sensor must be
enabled in "Temperature Sensor" page to
show this parameter.
Controller Algorithm
PID
/ Alternative PI
Controller algorithm can be selected via
using this parameter.
Proportional Band
1...
30
...255 x 0.1°C
This parameter shown when the "Controller
Algorithm" is selected as "PID"
Ti
0...
60
...255 min
This parameter shown when the "Controller
Algorithm" is selected as "PID"
Td
0
...255 min
This parameter shown when the "Controller
Algorithm" is selected as "PID"
Proportional Gain KP
1…
66
…255
This parameter shown when the "Controller
Algorithm" is selected as "Alternative PI".
Proportional gain of PI algorithm
Integral Gain Ki
1…
32
…255 /1000
This parameter shown when the "Controller
Algorithm" is selected as "Alternative PI".
Integral gain of PI algorithm, given value
divided by 1000.