4.3.1 Parameters
Parameter
Function
Description
Temperature Unit
Celsius(
°C
)
/
Fahrenheit(
°F
)
Select temperature unit. After selection all temperature
related parameters and communication objects should
be enter as selected unit.
Internal Sensor Offset -128…
0
…127 (x0.1K)
Offset value entered here will be added to measured
temperature. It can be used to compensate for
temperature difference caused by thermostat
placement. Entered value will be multiplied with 0.1
Send Temperature
Cyclic
/ Cyclic and
Change
Selects whether temperature will be sent periodically or
periodically and in case of a change in temperature.
Minimum change value defined in “Minimum
Difference” parameter.
Cyclic Sending Interval 10…
30
…65535 s
Cyclic time period to send temperature from “Current
Temperature” communication object.
Minimum Change
1
…255 (0.1K)
Only visible if “Send Temperature” selected as “Cyclic
and Change”. Selects minimum change in temperature
that will trigger transmission of temperature.
Temperature
Measurement
Internal Sensor
Temperature info can be taken from internal, external
KNX temp sensor or weighted average of both sensors.
If External or Weighted is selected, “
External
Temperature Sensor
” group object will be appeared.
External Sensor
Weighted Average
External Sensor Temp.
Unit
Celsius
External sensor temp unit can be set as desired. If the
“Same” is selected, the temp unit will be the same as
well as Main Temperature Unit.
Fahrenheit
Same
External Sensor
Monitoring Timeout
15…
30
…65535 s
If “External Temperature Sensor” object value has not
been updated at the end of the monitoring timeout, the
temperature reading will fallback to Internal Sensor.
External Sensor Weight 1...
50
...99 %
This parameter appears when the Temperature
Measurement is selected as "Weighted Average". In
this case, External Temperature value weightness can
be selected.
For e.g. Weight is 20% , Internal Sensor is 24°C and
External Sensor is 26°C. The result will be =
(24x0.8)+(26x0.2) =
24.4°C
Temperature Shown on
Internal Sensor
This parameter allows to show current temperature