Product Manual Rosa Thermostat
EAE KNX Rosa Thermostat
Rosa Thermostat PM R1.0
©
EAE Technology
www.eaetechnology.com
Page26 / 77
4.2.1.3.1
Parameters
Parameter
Setting
Description
Mode of Buttons
LeftUpRightDown
Left Down Right Up
Select which rocker button is “Up
Button”andwhichrockerbutton
is “Down Button”.
Control Type
Shutter/Venetian Blind
Blind/Roller/Awning
Selects control type of blinds.
Shutter/Venetian Blind function
includes “Lamella Control” and
Blind/Roller/Awningfunctiondoes
not include “Lamella Control”.
Function of LED
LED Permanently Off
LED always off
LED Permanently On
LED always on
Status Indication
Visualizeblind’sstateusingstatus
LEDsofupanddownbuttons.*
[5]
Operation Indication
StatusLEDofthepressed
rocker button will be on for the
time period selected at “Light
Duration of LED” parameter
at “General” tab.
Long Press Duration
300ms/ 400ms/ 500ms/ 600ms/
800ms
/1s /1.2s /1.5s/ 2s /3s /
4s / 5s / 6s / 7s / 8s / 9s / 10s
Timeinterval toswitchfrom short
press to long press
Table 10
*[5]
LED Function – Status Indication
Statusindicationoperatesthesamewayfor“Shutter/VenetianBlind”and“Blind/Roller/Awning”. LEDsstatus
respective to blind’s state is given below
Up Button - Status LED
Down Button - Status LED
Moving upward
Blink
Off
Moving downward
Off
Blink
At top position
On
Off
At bottom position
Off
On
Stop between top - bottom
Off
Off
Table 11
When “Function of Led” selected as “Status Indication”, “Top Position” and “Bottom Position”
communication objects given below mustbe linked tothe appropriategroup addresses for the status LEDs to
function correctly.