Product Manual Rosa Thermostat
EAE KNX Rosa Thermostat
Rosa Thermostat PM R1.0
©
EAE Technology
www.eaetechnology.com
Page53 / 77
4.4.4.3.1
Parameters
Parameter
Setting
Description
Control Value
Normal
/ Inverse
Invert the output of the controller. For example, if
normal output is 1, then inverted output is 0.
Cyclic Sending Interval
1…
5
…255
Time period to send heating control value over
“Heating Control Value” communication object.
Hysteresis (1/10 K)
1…1
0
…255
Hysteresis value (Chapter 4.4.3.1.3)
Spot Heat Protection
checked /
unchecked
This parameter enables the Heat Protection via
using Spot Temperature Sensor. Spot Temperature
sensor must be enabled in "Temperature Sensor"
page to show this parameter.
Table 33
4.4.4.3.2
Communication Objects
No
Object Name
Function
Data Type
Flags
61
Heat Control Value
Send
1 bit
CT
DPT 1.002
Heating actuator will be controlled through this communication object.
Table 34
4.4.4.4
Fan Coil
Figure 17
Heating control parameters for fan coil controller type should be configured here. For more information
about on/off controller read Chapter 4.4.3.1.4.