Product Manual Rosa Thermostat
EAE KNX Rosa Thermostat
Rosa Thermostat PM R1.0
©
EAE Technology
www.eaetechnology.com
Page45 / 77
4.4.2
Communication Objects
No Object Name
Function
Data Type
Flags
57
Operating Mode
Select Operating Mode
1 byte DPT 5.011
CW
Comfort mode
Enable
1 bit DPT 1.003
CW
58
Night Mode
Enable
1 bit DPT 1.003
CW
59
Away Mode
Enable
1 bit DPT 1.003
CW
60
Protect Mode
Enable
1 bit DPT 1.003
CW
“Operating Mode” is visible when “Switchover Comm Object Type” is “1 byte”. Values for enabling
different operating modes;
0: Comfort Mode, 1: Night Mode, 2: Away Mode, 3: Protect Mode.
“Comfort Mode”, “Night Mode”, “Away Mode” and “Protect Mode” are visible when “Switchover Comm
Object Type” is “Bit Objects”. Sending “True (1)” to this communication objects enables respective
operating mode.
63
Switchover
Control Mode
1 bit DPT 1.100
CRWT
Switchover
Control Mode Status
1 bit DPT 1.100
CRT
Switchover
Control Mode
1 byte DPT 20.105
CRWT
Switchover
Control Mode Status
1 byte DPT 20.105
CRT
64
Switchover
Status Control Mode
(0=Cooling, 1=Heating)
1 bit DPT 1.100
CRT
When “Switchover Type” is “Automatic” acts as a status communication object and sends current control
mode telegram from this communication object.
When “Switchover Type” is “Manual (via Object)” acts as a control communication object and current
control mode can be changed using this communication object.
74
Status Operating Mode
Operating Mode Status
1 byte DPT 5.010
CRT
Status Comfort
Enabled
1 bit DPT 1.002
CRT
75
Status Night
Enabled
1 bit DPT 1.002
CRT
76
Status Away
Enabled
1 bit DPT 1.002
CRT
77
Status Protect
Enabled
1 bit DPT 1.002
CRT
“Status Operating Mode” is visible when “Status Comm Object Type” is “1 byte”. Values for different
operating modes;
0: Comfort Mode, 1: Night Mode, 2: Away Mode, 3: Protect Mode.
“Status Comfort”, “Status Night”, “Status Away” and “Status Protect” are visible when “Status Comm
Object Type” is “4 bits”. When “Status Comm Object Type” is “4 bits” and an operating mode switchover
occurs a “False (0)” telegram will be send from previous operating modes communication object.
For example; while in Night mode and “Enable Away Mode” telegram received,
Status Night -> False then Status Away -> True
Table27