4.5.2 Communication Objects
No Object Name
Function
Data Types Flags
50 Regulation
On/Off
1 bit
CWT
DPT 1.002
Thermostat regulation can be turned on/off using this communication object. Also, when regulation
controlled through “Operating Mode Button”, the regulation status will be sent using this communication
object.
55
Current Temperature °C
Temperature 2 byte
DPT 9.001
CRT
Current Temperature °F
Temperature 2 byte
DPT 9.027
CRT
Current temperature value will be sent Celsius or Fahrenheit using this communication object, when the
room temperature has changed or cyclically.(configured “Temperature Sensor” tab)
56
Current Setpoint (
°C
)
Temperature
2 byte
DPT 9.001
CRT
Current Setpoint (
°F
)
Temperature
2 byte
DPT 9.027
CRT
Setpoint value will be sent by Celsius or Fahrenheit(configured “Temperature Sensor” tab) using this
communication object, when user has changed setpoint via thermostat.
70
Change Setpoint (
°C
)
Temperature
2 byte
DPT 9.001
CW
Change Setpoint (
°F
)
Temperature
2 byte
DPT 9.027
CW
Setpoint Temperature for CURRENT mode can be set using this communication object.Temperature value
should be compatible with selected “Temperature Unit” and setpoint limitations.
79
Setpoint Comfort °C
Temperature
2 byte
DPT 9.001
CW
Setpoint Comfort °F
2 byte
DPT 9.027
Setpoint Heating Comfort °C
2 byte
DPT 9.001
Setpoint Heating Comfort °F
2 byte
DPT 9.027