Settings
60
© 2017 DynaGen Technologies Inc
TOUGH Series Manual
AC Monitor > O.C. Protection:
Name
Range
Description
Basic Alarm
[Menu]
See
.
IDMT Protect
Disable
Breaker Trip
Shutdown Trip
See
IDMT Settings
[Menu]
Imbalance Mode
Disable
Breaker Trip
Shutdown Trip
See
.
Imbalance Set
[Menu]
Break Trip Fail
Disable
Enable
Shuts down the generator if the generator circuit breaker fails to
trip.
If the
switched output is active - due to
or
- and if after 10s the measured generator
current is still above 10% of the Rated Current the generator will
shut down.
4.6.3.1 Basic Alarms
The controller can give a warning and/or shutdown on over current. If
is enabled then it overrides the High Failure shutdown
but the warning is still active.
AC Monitor > O.C. Protection > Basic Alarm:
Name
Range
Description
High Warn
Disable, 1 ~ 125%
Reading at which a warning occurs.
High Fail
Disable, 1 ~ 125%
Reading at which a failure occurs.
Percentages are based on the Rated Amps setting. The warning and failure setpoints apply to each phase separately and not to
the sum of the phases.
4.6.3.2 IDMT
Sets an inverse time trip curve for over-current. When set this overrides the
AC Monitor > O.C. Protection:
Name
Range
Description
IDMT Protect
Disable
Breaker Trip
Shutdown Trip
Disable
: Disables the IMDT feature.
Breaker Trip
: If IDMT is active the
output is activated to switch off the main generator breaker.
This is a latching feature.
The operator must press the
and
keys to reset
the feature.
Shutdown Trip
: shuts down the engine.
IDMT Settings > TDS Const (Time
Dial Setting)
0.1 ~ 30
Sets the slope of the IDMT curve. This controls the sensitivity
of the trip to over current.
IDMT Settings > IDMT Reset
1 ~ 600 seconds
How long the current must drop and stay below the rated
current to reset the IDMT.
Summary of Contents for TG410
Page 4: ...3 2017 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Page 11: ...Installation 10 2017 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Page 12: ...Installation 11 2017 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Page 17: ...Installation 16 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Page 20: ...Installation 19 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Page 22: ...Installation 21 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Page 40: ...Settings 39 2017 DynaGen Technologies Inc TOUGH Series Manual ...