Settings
28
© 2017 DynaGen Technologies Inc
TOUGH Series Manual
Name
Active Mode
Description
active is the LED indicator will alternate between the green and red colors.
The LED goes back to it's original state when the switched input is no longer
active.
Fuel In Basin
Global
Controller displays 'Fuel In Basin' warning when active.
Battle Mode
After Cranking
Controller ignores all warnings and failures when active. Displays 'Battle
Running' when active. If a failure occurs during Battle Mode it is 'latched' and
the engine will shutdown on failure when the controller leaves Battle Mode.
Start Inhibit
Global
Controller ignores all start commands and the engine cannot start when
active. Once Start Inhibit becomes inactive, starting is enabled again. If the
engine is running, activating this input will shut down the engine.
RPM Switch (Primary
RPM / 60Hz -
Secondary RPM / 50Hz
Select)
Auto
Used for changing between Primary and Secondary RPM for an engine or
50Hz / 60Hz for a generator. See
information.
ECM Preheat (ECM
Preheat Signal)
Cranking (during the
Preheat countdown
only)
Controls preheating using a switched input. See Switched Input in the
Remote Reset
Global
Allows the controller to be reset from a failure mode.
- Momentary action for 3 - 5s in FAILURE mode will place the controller in
OFF mode.
- Momentary action for 3 - 5s in OFF mode will place the controller in AUTO
mode.
- Momentary action for 3 - 5s in RUN mode will place the controller in AUTO
mode. Cool-down is skipped.
NOTE
: More than one Active Mode can be selected.
The active modes is only configurable if the Function menu is set to one of the configurable switched input functions.
It is fixed for all other functions.
Switched I/O > Switched IN X > Trigger:
Name
Description
Close +BAT
Input is active when +Battery is present at the terminal.
Close GND
Input is active when Ground is present at the terminal
Close +BAT/GND
Input is active when Battery or Ground is present at the terminal.
Open
Input is active when nBattery or Ground is present at the terminal.
NOTE
: When running wires over long distances (over 20ft / 6.1m), it is recommended to use +BATTERY as the trigger
method.
Summary of Contents for TG410
Page 4: ...3 2017 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Page 11: ...Installation 10 2017 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Page 12: ...Installation 11 2017 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Page 17: ...Installation 16 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Page 20: ...Installation 19 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Page 22: ...Installation 21 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Page 40: ...Settings 39 2017 DynaGen Technologies Inc TOUGH Series Manual ...