Settings
58
© 2017 DynaGen Technologies Inc
TOUGH Series Manual
Name
Range
Description
Setpoints > High Warn (Over-
Frequency Warning)
Disable, 101 ~ 150%
Reading at which a warning occurs.
Setpoints > High Fail (Over-
Frequency Failure)
Disable, 101 ~ 150%
Reading at which a failure occurs.
4.6.2.1 RPM / Frequency Select
The controller has the ability to change between Primary RPM / 60Hz and Secondary RPM / 50Hz through the use of a switched
input.
The following settings must be set in order for this feature to function:
·
Switched I/O > Switched In A/B/C/D/E > Function > RPM Switch (Primary RPM / 60Hz - Secondary RPM / 50Hz Select).
The switched input is only monitored before a start signal has been received. Once a start signal has been received
changing the status of the switched input will have no effect.
·
AC Monitor > Genset Freq. > Freq. Source > Auto Selection
·
Sensors > Engine Speed > RPM Switch > Primary (Primary RPM / 60Hz)
·
Sensors > Engine Speed > RPM Switch > Secondary (Secondary RPM / 50Hz)
The table below shows the correspondence between the switched input status and the RPM / Frequency.
Switched Input
Speed / Frequency
Inactive
Primary RPM / 60Hz
Active
Secondary RPM / 50Hz
NOTE
: If enabled, the J1939 TSC1 PGN will be broadcasted according to the selected speed. Otherwise only the
warning and failure setpoints are affected by this function.
Summary of Contents for TG410
Page 4: ...3 2017 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Page 11: ...Installation 10 2017 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Page 12: ...Installation 11 2017 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Page 17: ...Installation 16 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Page 20: ...Installation 19 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Page 22: ...Installation 21 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Page 40: ...Settings 39 2017 DynaGen Technologies Inc TOUGH Series Manual ...