Settings
41
© 2017 DynaGen Technologies Inc
TOUGH Series Manual
Name
Range
Description
If the Run Time is disabled then the start/output is held until the
Stop Level is reached (if enabled) or until the controller is reset or
powered down or, in the case of Start on Low / Start on High, until
the user presses the OFF button.
Note that the run time is not exact. Up to 10 seconds may be
added to the beginning of the run time counter and up to 4 seconds
to the end. The run time begins when a start request is received so
crank time, preheat time, etc is included in the Run Time.
Mode Settings > Start Level
Disable
Temperature: 32 ~ 999, 1
0
F increments
Pressure: 1 ~ 6000, 1 psi
increments
Level: 1 ~ 99, 1 %
increments
Voltage: 0.1 ~99.9, 0.1 V
increments
Current: 1 ~ 999, 1 A
increments
(Only applies if Func. Select is
not
set to Fault Monitor) The level at
which the auxiliary switched output turns on or the engine starts.
If this is set to Disable, the Aux sensor action defined in Func.
Select is disabled. The Auxiliary sensor becomes display only
(unless Func. Select is set to Fault Monitor).
Mode Settings > Stop Level
(Only applies if "Func. Select" is
not
set to Fault Monitor) The level
at which the auxiliary switched input turns off or the engine is
stopped.
If Stop Level is disabled the start/output condition is maintained until
the Run Time expires (if enabled) or until the controller is reset or
powered down or in the case of a start until the user presses the
OFF button.
Setpoints > Low Warning
(Only applies if "Func. Select" is set to Fault Monitor) Reading at
which a warning occurs.
Setpoints > Low Failure
(Only applies if "Func. Select" is set to Fault Monitor) Reading at
which a failure occurs.
Setpoints > High Warning
(Only applies if "Func. Select" is set to Fault Monitor.) Reading at
which a warning occurs.
Setpoints > High Failure
(Only applies if "Func. Select" is set to Fault Monitor.) Reading at
which a failure occurs.
1
1 ~ 600 minutes for firmware versions below 1.78.
If using
Output on Low
or
Output on High
one of the switched outputs events must be set to one of the following corresponding to
the Aux. Sensor being configured per the table below.
(Switched I/O > Switched Out A/B/C/D/EF > Events menus)
Name
Description
Aux Sensor 1
Used by the Aux. Sensor 1
Output On Low
or
Output on High
feature.
Aux Sensor 2
Used by the Aux. Sensor 2
Output On Low
or
Output on High
feature.
Aux Sensor 3
Used by the Aux. Sensor 3
Output On Low
or
Output on High
feature.
Aux Sensor 4
Used by the Aux. Sensor 4
Output On Low
or
Output on High
feature.
The display resolution of the auxiliary sensors that are displayed on the screen are different than the resolution used for the
purpose of the comparisons that determine if the start level, stop level, low warning, etc are in effect. The resolutions are given
below.
Sensor Unit Type
Comparison Resolution
Temperature
1
0
F
Pressure
1 psi
Level
1 %
Summary of Contents for TG410
Page 4: ...3 2017 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Page 11: ...Installation 10 2017 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Page 12: ...Installation 11 2017 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Page 17: ...Installation 16 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Page 20: ...Installation 19 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Page 22: ...Installation 21 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Page 40: ...Settings 39 2017 DynaGen Technologies Inc TOUGH Series Manual ...