Using the Controller
23
© 2017 DynaGen Technologies Inc
TOUGH Series Manual
3.1
Modes, Starting and Stopping
The following table describes the different operating modes of the controller:
Modes
Mode / State
Description
OFF
When in the OFF mode, the engine cannot be remotely started.
Auto
When in the Auto mode, the engine waits to receive a start command.
Running
When engine is Running, the controller monitors engine parameters and waits to receive a stop
command.
Failure
When a failure occurs, the controller shuts down the engine and displays the reason for failure.
The unit must be reset using the front panel OFF button with the exception of Modbus.
Menu
When in the menu mode, settings can be changed and the events history may be viewed.
The following table describes the different methods for starting a controller. Unless using the Manual Run method to start the
controller, the controller must be in AUTO mode.
Starting Methods
Methods
Description
Manual Run
Pressing the Run button will start the engine. You must press the OFF button to shut down the
engine.
When this input is active the engine will start. When the input becomes inactive the engine will
shut down.
Switched inputs Momentary Start and Momentary Stop can be used for starting and stopping of
the engine. Unlike other inputs, they only have to be activated for a short period of time.
When the battery voltage drops below a certain level the engine will start and run for a
predetermined amount of time.
When the scheduled exerciser interval occurs the engine will start and run for a predetermined
amount of time.
When a scheduled event occurs the engine will start and run for the programed amount of time.
When a properly configured Auxiliary sensor falls below / rises above a certain point the engine
will start as determined by the Auxiliary Sensors -> Mode Select settings.
When a certain command is sent to the controller over Modbus the engine will start. See the
Modbus Reference Manual for more information.
J1939 Start
Start/stop command send over the J1939 CANbus. For example from the TR100 or a remote
telemetry device. The controller will display either "J1939 Run" or "J1939 Remote" as the reason
for starting.
ECM Power On
This is not a starting mode like the others. In AUTO mode if the Auto button is held for 3s the
fuel output is turned on for 1 hour. "ECM Power On" will be displayed on the screen. Pressing
and holding again within the hour will refresh for another hour. This feature can be used to turn
on or activate equipment powered by the fuel output. Often this is used by a tech to power the
ECM on an electronic engine so a diagnostic tool can obtain information from the ECM.
WARNING
: See the
section for more information on how it affects starting and stopping.
Summary of Contents for TG410
Page 4: ...3 2017 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Page 11: ...Installation 10 2017 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Page 12: ...Installation 11 2017 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Page 17: ...Installation 16 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Page 20: ...Installation 19 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Page 22: ...Installation 21 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Page 40: ...Settings 39 2017 DynaGen Technologies Inc TOUGH Series Manual ...